IMPORTANT SAFETY INSTRUCTIONS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS! SAVE THESE INSTRUCTIONS AND DELIVER THEM TO THE OWNER AFTER INSTALLATION
- To reduce the risk of death, personal injury, or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards please read all warnings and instructions included with and on the fixture box and all fixture labels.
- Before installing, servicing, or performing routine maintenance on this equipment, follow these general precautions.
- Installation and service of luminaires should be performed by a qualified licensed electrician.
- Maintenance of the luminaires should be performed by a person(s) familiar with the luminaires’ construction and operation and any hazards involved. Regular fixture maintenance programs are recommended.
- It will occasionally be necessary to clean the outside of the refractor/lens. The frequency of cleaning will depend on ambient dirt level and minimum light output which is acceptable to the user. The refractor/lens should be washed in a solution of warm water and any mild, non-abrasive household detergent, rinsed with clean water, and wiped dry. Should the optical assembly become dirty on the inside, wipe the refractor/lens and clean in the above manner, replacing damaged gaskets as necessary.
- DO NOT INSTALL DAMAGED PRODUCTS! This luminaire has been properly packed so that no parts should have been damaged during transit. Inspect to confirm. Any part damaged or broken during or after assembly should be replaced.
- Recycle: For information on how to recycle LED electronic products, please visit www.epa.gov.
- These instructions do not purport to cover all details or variations in equipment nor to provide every possible contingency to meet in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s or owner’s purposes, this matter should be referred to Acuity Brands Lighting, Inc.
WARNING RISK OF ELECTRIC SHOCK
- Disconnect or turn off the power before installation or servicing.
- Verify that the supply voltage is correct by comparing it with the luminaire label information.
- Make all electrical and grounded connections in accordance with the National Electrical Code (NEC) and any applicable local code requirements.
- All wiring connections should be capped with UL-approved recognized wire connectors.
CAUTION RISK OF INJURY
- Wear gloves and safety glasses at all times when removing luminaire from cartons, installing, servicing, or performing maintenance.
- Avoid direct eye exposure to the light source while it is on.
WARNING RISK OF BURN
- Allow lamp/fixture to cool before handling. Do not touch the enclosure or light source.
- Do not exceed the maximum wattage marked on the luminaire label.
- Follow all manufacturer’s warnings, recommendations, and restrictions for driver type, burning position, mounting locations/methods, replacement, and recycling.
CAUTION RISK OF FIRE
- Keep combustible and other materials that can burn, away from the lamp/lens.
- Do not operate in close proximity to persons, combustible materials, or substances affected by heat or drying.
CAUTION: RISK OF PRODUCT DAMAGE
- Never connect components under load.
- Do not mount or support these fixtures in a manner that can cut the outer jacket or damage wire insulation.
- Unless individual product specifications deem otherwise: Never connect an LED product to dimmer packs, occupancy sensors, timing devices, or other related control devices. LED fixtures must be powered directly off a switched circuit.
- Unless individual product specifications deem otherwise: Do not restrict fixture ventilation. Allow for some volume of airspace around fixture. Avoid covering LED fixtures with insulation, foam, or other material that will prevent convection or conduction cooling.
- Unless individual product specifications deem otherwise: Do not exceed fixtures maximum ambient temperature.
- Only use fixture in its intended location.
- LED products are Polarity Sensitive. Ensure proper Polarity before installation.
- Electrostatic Discharge (ESD): ESD can damage LED fixtures. Personal grounding equipment must be worn during all installation or servicing of the unit.
- Do not touch individual electrical components as this can cause ESD, shorten lamp life, or alter performance.
- Some components inside the fixture may not be serviceable. In the unlikely event, your unit may require service, stop using the unit immediately and contact an ABL representative for assistance.
- Always read the fixtures complete installation instructions prior to installation for any additional fixture specific warnings.
- Verify that the power distribution system has proper grounding. Lack of proper earth ground can lead to fixture failure and may void the warranty.
All luminaires that contain electronic devices that generate frequencies above
9kHz from any component within the luminaire comply with
Part 15 of the FCC Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful interference (2) This device
must accept any interference received, including interference that may cause
undesired operation.
Failure to follow any of these instructions could void product warranties. For a complete listing of product Terms and Conditions, please visit www.acuitybrands.com. Acuity Brands Lighting, Inc. assumes no responsibility for claims arising out of improper or careless installation or handling of its products.
ABL LED General Warnings, Form No. 503.203
© 2010 Acuity Brands Lighting, Inc. All rights reserved. 12/01/10
Important Cleaning Note:
Use a cleaner that does not contain Ethanol such as Joy® Non-Ultra (Joy® Ultra
contains Ethanol and cannot be used).
Overview
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
-
WARNING: FAILURE TO FOLLOW THESE INSTRUCTIONS AND WARNINGS MAY RESULT IN DEATH, SERIOUS INJURY OR
SIGNIFICANT PROPERTY DAMAGE – For your protection, read and follow these warnings and instructions carefully before installing or maintaining this equipment. These instructions do not attempt to cover all installation and maintenance situations. If you do not understand these instructions or additional information is required, contact Holophane or your local Holophane distributor. -
WARNING: RISK OF ELECTRIC SHOCK – NEVER CONNECT TO, DISCONNECT FROM, OR SERVICE WHILE EQUIPMENT IS ENERGIZED.
-
WARNING: DO NOT USE ABRASIVE MATERIALS OR SOLVENTS. USE OF THESE SUBSTANCES MAY DAMAGE FIXTURES, WHICH MAY RESULT IN PERSONAL INJURY.
-
WARNING: RISK OF PERSONAL INJURY – This product may have sharp edges. Wear gloves to prevent cuts or abrasions when removing
from the carton, handling, installing, and maintaining this product. -
WARNING: The battery used in this device may present a risk of fire or chemical burn if mistreated. Temperature range 32 ° F -122 ° F (0°C -50°C) with Non-CW units and -22 ° F -122 ° F (-30°C – 50°C) for CW units. Do not disassemble or heat above 70° C (158° F) or incinerate. Battery should not be used in an application where the temperature is lower than what is rated on the spec sheet. Replace the battery only as directed on the battery label and page 4 of these instructions. Use of an unauthorized battery voids the warranty and UL listing of this product and may present a risk of fire or explosion.
-
Disconnect A.C. power before servicing.
-
All servicing should be performed by qualified personnel.
-
Consult your local building code for approved wiring and installation.
-
For use Outdoors. Failure to ensure conduit connections are properly protected against water ingress during installation may void the warranty.
-
Do not mount near gas or electric heater.
-
Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
-
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
-
Do not use this equipment for other than intended use.
SAVE THESE INSTRUCTIONS AND DELIVER THEM TO THE OWNER AFTER INSTALLATION
INSTALLATION and MOUNTING
- IMPORTANT: Provide each unit with a single-phase AC un-switched power supply from a 120 V to 347 V circuit used for normal lighting. PRODUCT DAMAGE WILL OCCUR IF THE RATED INPUT VOLTAGE IS EXCEEDED.
- WARNING: During the installation of remotes, input wires from the main unit to remote units must NOT be connected to each other or connected to the ground. Failure to do so will lead to the failure of the main unit.
- NOTE: The battery must be connected to the charger board prior to applying AC power to the unit. Battery damage may occur if the battery is connected for longer than 24 hours without continuous AC power provided. See also “Important Battery Information”, page 3.
- NOTE: The maximum mounting height of DSL46 SP640L is 28.5 feet, the DSL46 SP1100L is 41.4 feet and the DSL46 SP2200L is 62.4 feet respectively, to meet the minimum illumination requirements of NFPA 101 (current Life Safety Code).
- NOTE: Before installation, choose a location that allows adequate clearance for sliding the Rear Housing onto the Mounting Bracket (minimum 6-1/2” above the top edge of the Bracket)
- NOTE: Do not connect the battery or power unit until remote units (if applicable) are fully connected and wires are isolated from other potentials (i.e. remote wires shall be isolated from earth ground).
MOUNTING BRACKET
Universal Mounting Bracket
- Wall/Ceiling mounting- Locate the mounting bracket in the desired location using “Wall/Ceiling Mounting Holes” (see Fig. 1). Install using four (4) 30 lbs. minimum pullout rated fasteners. The mounting surface should be suitable to support 120 lbs.
- Pole/Column Mounting-
- Unistrut Mounting holes for most standard configurations.
- Steel Banding Slots for routing around poles and I-beams. (See “Pole Mount Banding “above”).
After the Mounting Bracket is in place and the conduit is near, slide the enclosure downward onto the Mounting Bayonets (See Figure 2). The enclosure will be in place when the snap-lock feature is engaged in the hole in the Mounting Bracket.
SURFACE CONDUIT MOUNTING
-
At the top left or either side of the housing, drill a hole sized for the chosen conduit fitting. Conduit entry points can accommodate a hole up to 1” in diameter and have a wall thickness of up to .25”. Secure mounting plate to a wall surface using fasteners with a minimum pullout rating of 30 lbs. each.
IMPORTANT: prior to drilling out a hole in the top conduit location, remove the charger board assembly to ensure no damage occurs to the charger board. -
Remove any debris from the enclosure, as it may harm electronic components or compromise the enclosure seal. Install a UL-listed, water-tight fitting that is suitable to the size of the incoming conduit and hole drilled in step 1. The fitting must prevent water ingress at the sealing joint with the enclosure, as well as from moisture that may be inside the conduit itself. Make code-approved wire connections to the AC power supply and remote lamps (if applicable).
IMPORTANT: Follow any manufacturer recommendations when attaching the conduit to the conduit fitting. Failure to do so can lead to moisture buildup in the conduit which may leak into the housing and damage the unit .
NOTE:
Emergency lighting systems should be tested in accordance with NFPA 101 or as
often as local codes require, to ascertain that all components are
operational.
NOTE:
Allow batteries to charge for 24 hours before initial testing.
Manual testing:
If the batteries are sufficiently charged, either press and release the “TEST”
button or use the RTKITHLP (remote tester accessory for SDRT units) on the
bottom of the unit to activate a 60-second test, during which the lamps will
turn on. Triggering either option a second time will enable 90-minute tests
indicated by 5 flashes of the lamps. Triggering either option a third time
will disable manual testing.
Self-Diagnostics (SDRT feature)
Units with this option automatically perform a 5-minute self-diagnostic test
of the charging electronics, battery, and lamps every 30 days, and a 90-minute
test every year, indicating system status as shown in the table at right. The
first self-test occurs after 15 days of continuous AC Power.
Postponing a self-test:
If an automatic self-test occurs at a time when it is not desirable for the
unit lamps to be on, it can be postponed for 8 hours either by pressing and
releasing the “TEST” button or by using RTKITHLP (remote tester accessory).
Canceling emergency operation:
While in emergency Mode, press and hold the “TEST” button for several seconds
or activate using the RTKITHLP (remote tester accessory), during which the
status indicator will flash until the lamps turn off. This restores the AC
Reset state in which the unit is shipped.
Load-Learning feature:
Self-Diagnostic units automatically ‘learn’ their total connected lamp load
during the first scheduled self-test (~15 days). The load-learn clear process
can be initiated manually and should be initiated whenever the total connected
lamp load of the unit is changed, or potentially troubleshooting a lamp error
(unit indicates a lamp error yet all lamps are operating correctly) or a lamp
is replaced.
To clear the current load-learn, press and hold the “TEST” button for 7 seconds (count green flashes), during this period the lamps will turn on. After 7 seconds, release the button, the lamps will turn off within 2 seconds indicating the load clear is complete. If lamps stay on longer, the load clear was not successful and the process should be repeated. A new load learns will automatically take place at the next discharge from a fully charged state (solid green status indicator).
Clearing a failure indication:
After a failure, condition has been corrected and power is restored to the
unit, clear the failure indication either by pressing the “TEST” button once
or by using the RTKITHLP (remote tester accessory).
IMPORTANT BATTERY INFORMATION:
Batteries are perishable items. For best results, it is recommended that the
batteries receive an initial charge within the first twelve months of the
manufacture date of the fixture. In many cases, batteries beyond the initial
charge recommendation time frame will recover if fully charged soon after
installation. If such a battery does not recover after a full initial charge,
it should be replaced. The manufacture date can be found on the outside of the
unit packaging and on the product label as part of the Date Code/Series. The
first two digits in the date code represent the year and the second two digits
represent the month.
Unit Status Indications
The “TEST” button illuminates to indicate the following conditions:
Indication: | Status: |
---|---|
Off | Unit is off |
Flashing green | Unit is in Emergency operation or Test |
Solid amber | Battery is charging |
Solid green | The battery is fully charged |
Flashing R / G | Manual test, battery not fully charged (SDRT) |
1x red flashing | Battery failure (SDRT) |
2x red flashing | Lamp failure (SDRT) |
3x red flashing | Charger/electronics failure (SDRT) |
Flashing R/Amber | Unable to charge |
Solid Red | Battery is disconnected |
Remote Test (SDRT):
(RTKITHLP sold separately) Units with the self-diagnostics/remote test feature
allow manual test activation using a laser pointer. Aim the laser beam
straight onto the circular area labeled near the “TEST” button for a few
moments to activate a 60-second test. (See also “Manual testing”) A test in
progress may be canceled by aiming the beam at the test area again. NOTE: The
remote tester should not be used to initiate the Load Learning feature.
MAINTENANCE
TO OPEN THE UNIT:
- Unscrew the two nylon screws on the top of the product with a screwdriver.
- Open the unit and service the unit if necessary. When closing, ensure that wires are not pinched and proceed to screw the two nylon screws back into position.
BATTERY REPLACEMENT
- Disconnect the battery from the charger board. Release the battery strap.
- Replace the battery, secure the strap snugly, and reconnect to the charger board.
- Re-assemble the unit
BATTERY HANDLING WARNINGS:
- Dispose of used batteries promptly.
- Keep away from children.
- Do not disassemble.
- Do not dispose of it in the fire.
LAMP REPLACEMENT
- With the unit open, disconnect the lamp head harness from the charger board. Refer to the wiring diagram from page 6 for lamp head connectors on the charger board.
- Remove the lamp head bracket from the housing by removing two screws. Remove the nut and washer from the lamp head and carefully remove the lamp head from the bracket.
- To reinstall the lamp head, route the harness through the bracket, washer, and nut and then tighten the nut down a ¼ turn after the gasket begins to compress. Attach the lamp head bracket to the housing and then connect the lamp head harness to the charger board (see page 6 for the wiring diagram).
CHARGER BOARD REPLACEMENT
- Lift the charger board tray and open the dielectric cover. Disconnect all harnesses connected to the charger board.
- To remove the charger board from the tray release the snaps (5x) and remove them. To install the new charger board place over snaps in the correct orientation with a dielectric cover installed under the charger board as shown. Press down firmly until snaps engage.
- Reconnect all harnesses and position the end of the charger board tray onto guide rails and push down until you hear a “snap”. Route wires along the side of the guide rail to avoid wires from pinching. Battery harness must be routed through a flap in the dielectric cover.
LAMP AIMING and WIRING DIAGRAM
LAMP AIMING
- With the unit open, loosen the nut and screw and aim the lamp head to the desired position.
- With lamp heads aimed, begin by tightening the nut until the gasket is fully compressed. (Torque spec: 12 in-lbs)
- With the nut secure, tighten the screw to finish the aiming procedure. (Torque spec: 10 in-lbs)
WIRING DIAGRAM
FCC STATEMENT
Federal Communications Commission (FCC) Requirements:
This device complies with FCC Title 47, Part 15, Subpart B. This device does
not cause harmful interference.
LIFE SAFETY SOLUTIONS
TEL: 740-345-9631
www.Holophane.com.
© 2020, Acuity Brands Lighting, Inc.
All Rights Reserved.
References
- Acuity Brands | Lighting, Controls, and Building Management Solutions
- U.S. Environmental Protection Agency | US EPA
- Holophane | Lighting solutions for commercial, industrial, emergency and outdoor applications.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>