CTM SC-1200 series 1200W Pure Sine Wave Inverter / Charger Instruction Manual

June 9, 2024
CTM

CTM SC-1200 series 1200W Pure Sine Wave Inverter / Charger
CTM SC-1200 series 1200W Pure Sine Wave Inverter /
Charger

Feature

  • Bi-directional All-in-One Design

  • Compact Size
    Highly Integration = Installation hassle-free

  • Certifed by UL
    UL458 & Supplement SA / CSA C22.2 No. 107.1-01
    UL1741 / CSA C22.2 No. 107.1-01 / KKK-A-1822F (For Ambulance)

  • 5-in-1 Operating Modes
    1. Inverter mode 2. Charger mode 3. Power Sharing 4. Power Generation
    5. Power Support

| | SC-1200-112| SC-1200-124| SC-1200-212| SC-1200-224
---|---|---|---|---|---
Inverter Mode| | | | |
Input| Nominal Voltage| 12 VDC| 24 VDC| 12 VDC| 24 VDC
| Input Voltage Range (±0.5V)| Input Voltage Range (±0.5V)| 21.0 ~ 33.0 VDC| 10.5 ~ 16.5 VDC| 21.0 ~ 33.0 VDC
| Input Over-Voltage Protection (±0.5V)| 16.5 VDC| 33.0 VDC| 16.5 VDC| 33.0 VDC
| Input Over-Voltage Warning (±0.5V)| 15.5 VDC| 31.0 VDC| 15.5 VDC| 31.0 VDC
| Input Under-Voltage Protection (±0.5V)| 10.5 VDC| 21.0 VDC| 10.5 VDC| 21.0 VDC
| Input Current (Max)| 132 A| 66 A| 132 A| 66 A
| No Load Current| < 3.0 A @12.5V| < 1.5 A @25V| < 3.0 A @12.5V| < 1.5 A @25V
| Stand-By Current| < 0.4 A| < 0.2 A| < 0.4 A| < 0.2 A
Output| Continuous Output Power| 1200 VA ± 3%
| Surge Power| Load 101%~115% (1 Min) / 2400 VA (2 Sec)
| Frequency| 50/60 Hz ± 0.3 Hz (User-selectable)| | |
| Output Voltage| 100 / 110 / 115 / 120VAC ±3%| | 200 / 220 / 230 / 240VAC ±3%
| Max. E‑ciency (Full Load)| 89%| 90%| 89%| 90%
| Output Waveform| Pure Sine Wave (THD < 5% @ 12.5V/25V/115VAC, linear load) / (THD < 3% @ 12.5V/25V/230VAC, linear load)
| INV. AC Output| 12A MAX| | 6A MAX|
| AC Output
| 30A MAX| | 22A MAX|
Protection| Input Protection| Over / Under Voltage, Reverse Polarity (Internal Fuse)
| AC Output Protection| Short-Circuit, Overload
| AC Input Protection| 30 Amp Circuit Breaker| | 16 Amp Circuit Breaker|
| Battery Temperature protection| By a RJ-11 connector to battery Temperature sensor
Charger Mode
AC input| Nominal Voltage / Frequency| 110 VAC, 50 / 60Hz (User-selectable)| | 230 VAC, 50 / 60Hz (User-selectable)
| Input Voltage Range| 90 ~ 132 VAC| | 180 ~ 264 VAC
| Input Frequency Range| 50Hz:47 ~ 53 Hz / 60Hz:57 ~ 63 Hz
| Nominal Current| 8.2A (@110VAC)| | 3.9A (@230VAC)
| E‑ciency (Max.)| >88%
| AC Input| 30 A MAX| | 16 A MAX|
| Power Factor Correction (PFC)| >0.95 (Max.)
Auxiliary DC Output| Output Voltage| Battery Voltage
| Output Current| 20A Max
DC Output| Charging Current Range| 12.5 / 25 / 37.5 / 50A| 6.25 / 12.5 / 18.75 / 25A| 12.5 / 25 / 37.5 / 50A| 6.25 / 12.5 / 18.75 / 25A
| Max. Output Voltage| 14.4 VDC@ GEL TYPE| 28.8 VDC @ GEL TYPE| 14.4 VDC @ GEL TYPE| 28.8 VDC @ GEL TYPE
| Battery Temperature Compensation| -25 mV per ℃| -50 mV per ℃| -25 mV per ℃| -50 mV per ℃
| Battery Control (3-stage Battery Chargers)| Bulk / Absorption / Float| | |
Signal and Control| Remote Control Panel (Optional)| CR-20C / CR-16B / CR-8| | |
| Dry Contact Terminal| By a relay| | |
| Relay Speci­cation| 30 Amp / 120 VAC @ 110V system| 16 Amp / 250 VAC @ 230V system
Environment| | | | |
Operating Temperature| Full Load| -20 ℃ ~ 50 ℃
| | |
Range| Power de-rating| 40 W / ℃, 51~60 ℃| | |
| Storage| 30 ℃~70 ℃| | |
Operating Humidity Range| | Max 93%, Non-condensing| | |
Cooling| | Temperature & Load Controlled Cooling Fan| | |
Safety Standards| | UL458 & Supplement SA / UL1741| | EN 62368-1|
E-mark| | | | Certi­ed CISPR 25; ISO7637-2|
EMC Standards| | | | EN55032 Class A, EN55024 Class A EN61000-3-2, 3-3 , EN61000-4-2, 3, 4, 5, 6, 8, 11|
Other| | | | |
Dimension (W x H x D)| | 251 x 116 x 386mm| | |
Net Weight| | 4.55Kg| | |

Max Inverter output define inverter 100% load output at Vac =100V / 200V
Max AC output define AC input current + Inverter output current, cannot over AC input limit.
Max AC input current Limit by the Breaker
For SC-1200 -112 and -124, the operating temperature range certified by UL Safety Standard is -20°C ~ 40°C.
*SC series is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures

The Battery Charger

The Battery Charger

The Battery Charger

Front panel

Ⓐ AC Output
Ⓑ AC Input
Ⓒ  Chassis ground
Ⓓ Main switch
Ⓔ DIP switch
Ⓕ Function LED
Ⓖ AC input breaker
Ⓗ AC Output terminal (L/N)
Ⓘ AC Input terminal (L/N)
Ⓙ AC In/Output ground terminal

Function LED

BAT : Display input voltage

LED Status DC12V DC24V
Red < 11.0V < 22.0V
Orange 11.0 ~ 11.5V 22.0 ~ 23.0V
Green 11.5 ~ 15.0V 23.0 ~ 30.0V
Orange 15.0 ~ 15.5V 30.0 ~ 31.0V
Red >15.5V >31.0V

Load: Display AC loads (PF=1)

LED Status SC-1200 / SC-2000
Red > 115%
Orange 100 ~ 115%
Green 0 ~ 100 %
Dark Charger Mode

Status : Display System Status

LED Status Status
Green Normal
Green Slow Blink OTP
Green Fast Blink UTP
Orange PLL/Frequency Fail
Orange Slow Blink AC in UVP/OVP
Orange Fast Blink AC IN OCP
Red OLP / SCP
Red Slow Blink Battery UVP
Red Fast Blink Battery OVP

Charger : Display Charger Stage

LED Status SC-1200 / SC-2000
Orange Blink Bulk
Orange Absorption
Green Float
Red Charger Error
Green Fast Blink Active
Green Slow Blink Equalization
Dark Inverter Mode

The Battery Charger

Temperature reading form BTS

Mechanical Drawings

Mechanical Drawings

Dip switch Function

Dip Switch Function
S1 ****

Output Voltage Select

S2
S3| Frequency Select
S4| ****

AC Input Current Limit Select

S5
S6
S7| ****

Battery Type Select

S8
S9| ****

Charger Current Select

S10
S11| DC Source on/off
S12| Saving Function on/off

AC Input Current Limit Select (S4,S5,S6)

AC Input Current

100~120V / 200~240V

| S4| S5| S6
---|---|---|---
3A / 2A| OFF| OFF| OFF
6A / 4A| ON| OFF| OFF
9A / 6A| OFF| ON| OFF
12A / 8A| ON| ON| OFF
15A / 10A| OFF| OFF| ON
20A / 12A| ON| OFF| ON
25A / 14A| OFF| ON| ON
30A / 16A| ON| ON| ON

Charger Current Select Function (S9,S10)

Charger Current S9 S10
25% OFF OFF
50% ON OFF
75% OFF ON
100% ON ON

Saving Function Switch ON/OFF Function (S12)

Saving function S12
OFF OFF
ON ON

Output Voltage switch Function (S1,S2)

Output Voltage S1 S2
100V / 200V OFF OFF
110V / 220V ON OFF
115V / 230V OFF ON
120V / 240V ON ON

Output Frequency switch Function (S3)

Frequency S3
50HZ OFF
60HZ ON

Battery Type Select Function (S7,S8):

Battery Type S7 S8
GEL OFF OFF
Flooded ON OFF
AGM OFF ON
Customer ON ON
Battery Type Bulk Absorption
--- --- ---
GEL 14.40V 14.10V
Flooded 14.70V 14.60V
AGM 14.70V 14.30V
Customer 14.70V 14.50V

DC Source Output On/Off Function (S11)

ESB function S11
OFF OFF
ON ON

Power Saving Load Function

SC series -212, -224 Default: 40VA
Entering the saving power Load<32VA
Wake up the saving power Load>40VA
SC series -112, -124 Default: 20VA
--- ---
Entering the saving power Load<16VA
Wake up the saving power Load>20VA

Rear panel

Rear panel

BAT. TEMP. Port (RJ-11) \

BAT. TEMP. Port \(RJ-11\)

Pin Number Signal Description
1 Not used
2 GND
3 Batteries temperature sensor
4 Battery Detect
5 Not used
6 Not used

Remote Port (RJ-11)

Pin Number Signal Description
1 Reserved
2 GND
3 RXD
4 TXD
5 RMT
6 VCC

Remote Control & Green Terminal

Remote control green terminal may be connected to a Form C relay for “FAULT” indication. When “FAULT” occurs, the relay switches.

Remote control terminal

Item Description Item Description
1 Dry contact (Normal Open) 4 Enable+ (ENB)
2 Common 5 Enable- (ENB)
3 Dry contact (Normal Closed) 6 Ground

Dry contact terminal definition

Remote Control & Green Terminal

Specifications of the Relay

Maximum Voltage|

Load

| Contact Rating| Number of operations| Operating/Storage Temperature
---|---|---|---|---
N.O| N.C
250 VAC| Resistive| 1 A| —| 100,000|

-30℃~75℃

250 VAC| Resistive| —| 1 A| —
24 VDC| Resistive| 1 A| —| —
24 VDC| Resistive| —| 1 A| —

www.ctm-marine.com

Documents / Resources

| CTM SC-1200 series 1200W Pure Sine Wave Inverter / Charger [pdf] Instruction Manual
SC-1200 series 1200W Pure Sine Wave Inverter Charger, SC-1200 series, 1200W Pure Sine Wave Inverter Charger, Wave Inverter Charger, Inverter Charger
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

CTM User Manuals

Related Manuals