TRIO2SYS EnOcean 16A DIN Rail Switch Receiver
Installation and operating manual
Modular multifunction switch receiver 1 channel 16A
General
Use
The 1 channel 16A modular multifunction switch receiver TRI02SYS 10020118 is
used to receive radio signals from switch transmitters or sensors
TRI02SYS (see compatibility table §6.1). It is used for switching loads, e.g.
incandescent, halogen, fluorescent tubes, halogen lamps with TBT ferromagnetic
transformer and electronic, power contactor or small motors.
The 10020118 receiver has a “repeater” function (see §6.5).
The Remote Commissioning (ReCom) functions, defined by the EnOcean
Alliance, are compatible with the 10020118 receiver. These allow remote
configuration of the receiver (see §6.7)
Before any use, the transmitters must be allocated to a receiver. Each sensor
or transmitter can control an unlimited number of receivers.
Note: Read the operating manual carefully before initial use.
Guarantee terms
This operating manual is an integral part of the device and our guarantee
terms. It must always be delivered to the user. We reserve the right to modify
the technical design of these devices without warning.
TRI02SYS products are manufactured and their quality checked by making use of
the latest technologies and taking into account the applicable national and
international directives. If nevertheless a fault arises,TRI02SYS undertakes
to remedy the default as follows, without prejudicing the rights of the end
customer that arise from the sales contract with his reseller.
If the event of exercising of a legitimate and regular right, TRI02SYS, may at
its sole discretion, rectify the device fault or supply a fault-free device.
Any claim beyond this and all claims for consequential damages are excluded.
A legitimate fault exists if the device cannot be used at the time of delivery
to the end customer because of a design or manufacturing defect or if its
practical use is severely limited. The guarantee is void in cases of natural
wear and tear, incorrect use, incorrect connection, where the device has been
repaired or external influence. The guarantee period is 24 months (from the
date of invoicing). French law applies to the regulation of guarantee rights.
Safety
WARNING! Risk of electric shocks! (See UTE C18-150) The device contains live internal components. Risk of wounds or injuries if contact occurs! All work on the mains supply network and the device must only be carried out by authorised professional technicians.
- Before carrying out any work, switch-off and isolate the device.
- Secure the device to prevent it being switched back on.
- Check the device is in a zero-volts state.
- Carefully reclose the casing before reconnecting to mains power.
Observe the following points:
- The laws, standards and directives in force.
- Best practice at the time of installation.
- The device operating manual.
- An operating manual can only give general instructions. They must be interpreted in the context of a specific installation.
The device is intended solely for use conforming to its purpose. Any repairs or modifications by the user are forbidden! Do not use with other devices the operation of which could endanger people, animals or property.
Technical characteristics
Remarque: The signal strength between the transmitter and the receiver
decreases as the distance increases. Where there is a line of sight
connection, the range is approximately 30m in corridors and 100 m in large
workshops or halls.
The range can be increased with a TRI02SYS repeater.
Respect a minimum range of 10 cm between transmitter and receiver.
Installation and initial use
Safety instructions
The installation and initial use must only be performed by authorised
qualified electricians. The electrical installation must be placed off-load
before connection it to the mains (230V~/50Hz). Conform to the legislation and
standards in force in the country of use.
Installation
- This product is designed for indoor use. It is maintenance free.
- This product is intended for installation only on horizontal DIN rail, in an electrical panel (mounted on a vertical wall) with compulsory installation of a plastron which will be connected to the ground of the installation if it is metallic.
- For compliance with the standard reference, height of the plastron (compared to the above DIN rail) must not exceed 48mm with a minimum thickness of 1mm.
- NEVER install the receiver in a metal casing or in the immediate vicinity of large metallic objects.
- Installation on the ground or close to the ground is not recommended. Thank you to refer to the installation standards of each country.
- Although NO output is internally connected, to the upper power to 400W it is obligatory to link externally.
- Protect the supply line with a circuit breaker 2A curve C adapted to the installation place.
- For the controlled power over 400W, the output contact must be supplied with the same supply line as the product, but protected separately with a circuit breaker 16A curve C adapted to the installation place.
Connection drawing for a lighting application ≤ 400W:
Connection drawing for a resistive load application ≤ 3500W:
Description of the connection
- Description of the 1-channel 16A modular multifunction switch receiver:
Initial use
- Connect power to the electrical installation after it has been installed.
- Program the transmitter on the receiver (see § 5).
Programming
For programming the receiver must be connected to the mains. The programming
is conserved during a power failure.
A small insulated screwdriver shall be used on the unit to activate the LRN or
CLR buttons.
Programming mode or transmitter deletion mode
N.B.! A transmitter must not be further away than 2 m from receiver in learn mode. The receiver has a limited range!
To enter the programming mode, short press (approximately 0,5s) the LRN button. This mode is confirmed by the regular flashing of the LED.
- a) To associate a transmitter simply press on one of the switches or press the LRN button (see §6.2). The receiver will acknowledge its recording in memory by maintaining the LED on for 4 seconds. As soon as flashing LED starts again, another transmitter can be associated or cleared.
- b) To clear a transmitter simply press on one of the switches or press the LRN button of the desired sensor (see §6.2). The receiver will acknowledge its clearing off the memory by maintaining the LED off for 4 seconds. As soon as flashing LED starts again, another transmitter can be associated or cleared.
- c) The association or deletion of transmitters can also be carried out using the EnOcean UTE1 (Universal TEach-in) protocol: once the relay output has been chosen, send a UTE Query1 type frame. The association or deletion is confirmed by keeping the LED on or off for 4 seconds and by sending a UTE Response1 type frame.
To exit programming mode, short press (approximately 0.5s) the LRN button. The output is confirmed by the stopping of regular flashing of the LED.
Notes:
- No transmitter is programmed in the receiver as supplied state.
- When using BMS products, mono or multi-channel, programming must be performed alone and channel by channel: you must exit the programming mode between each channel, by short press the LRN button and within 5 seconds after the start of LED acquittal.
- Up to 32 switch, transmitters and sensors can be allocated to each channel.
- If the memory is full, the receiver exits programming mode upon an additional association attempt.
- The transmitters are alternatively programmed or cleared in the event of several activations!
- If no button is pressed, learn mode stop automatically after 30 s.
Sensor mode
The TRI02SYS 10020118 receiver, once associated with a BMS product, transmits
an acknowledgment for each change of status on its output. In addition,
advanced functions such as remote polling and remote status change become
available, in accordance with the EEP profile D2-01-011:
- a) Activate the programming mode on the BMS product (refer to its user manual).
- b) Enter the programming mode (see §5.1) on the 10020118 receiver, for the transmission of UTE Query1 type association frames. These transmissions, one every 3 seconds, are indicated by the regular flashing of the LED until the mode is exited.
- c) The association with this BMS product is validated as soon as a positive response of type UTE Response1 is received. This is confirmed on the receiver by the LED remaining lit for 4 seconds and by the sending of a VLD CMD 4 – Actuator Status Response1 type frame.
Clearing off all the programmed transmitters
Press the CLR button for approximately 2s. Clearing is confirmed by the
regular flashing of LED. The receiver returns automatically to programming
mode.
To exit programming mode, short press (approximately 0,5s) the LRN button. The
output is confirmed by the stopping of regular flashing of the LED.
Control and functions
Each receiver can receive up to a maximum of 32 transmitters, switches or
sensors. Upon allocating on the selected output the first transmitter or
sensor, the operating mode is defined. The operating mode cannot be changed
until all the transmitters have been cleared(see §5.3).
Switch mode: For switches (default mode), each press reverses the state of the
receiver: if it is ON it goes OFF and vice versa.
Window contact mode (D5-00-01): If at least one of the window contacts is
open, this activates ON the associated output of the receiver. If all possible
window contacts are closed, the associated output of the receiver is OFF. The
window contacts transmit a signal approximately every 15 minutes. 60 minutes
after receipt of the last signal received, the receiver considers this contact
closed.
Compatible transmitters
The following transmitters can be associated with the receiver TRI02SYS
10020118:
Designation | **Trio2sys reference*** | EEP Profile 1 |
---|---|---|
Emitter | 10020001, 10020019, 10020022 | F6-02-01 |
Emitter bistable | 10040023, 10040024, 10040025 | F6-02-XX (PTM202) |
Key card | 10020067 | F6-04-01 |
Window Handle | 10020011 | F6-10-00 |
Window contact | 10020032, 10020042, 10020075 | D5-00-01 |
Dry contact sensor | 10020047, 10020057 | D5-00-01 |
Occupancy Sensor | 10020051, 10020078 | A5-07-01 A5-07-03 |
Gateway | 10020040 | A5-38-08 |
(*) This list is not exhaustive. To find more compatible products, go to the product section on the website www.trio2sys.fr
Transmitter-associated functions (switch mode)
The functions associated with different sensors are determined during
learning. The learning process
(see § 5.1) is to do before activating the transmitter.
Note: The ON state corresponds to the lighting of the LED (on the front
of the product) and contact closure outputs NO.
Note: The visual acknowledge corresponds to holding the LED on or off for
4 seconds.
Note: The ON state corresponds to the lighting of the LED (on the front of
the product) and contact closure outputs NO.
Note: The visual acknowledge corresponds to holding the LED on or off for
4 seconds.
Inversion of the output contact
This function allows the reversal of the operation of the output contact. In reverse mode, when the LED (product front) is on, then the output contact is open (load off) and vice versa.
To enter the inversion mode:
- a) Power down this receiver
- b) Press the CLR button
- c) Power up this receiver, while maintaining press the CLR button
- d) As soon as the LED is on orange, release the CLR button immediately.
The state of the inversion of the output is shown by the flashing of the LED, long for the non-inverted mode and short for the reverse mode:
- a) To change the inversion mode of the output, short press (approximately 0.5s) the LRN button. This new mode is confirmed by the change of flashing of DEL.
- b) To exit this mode, short press (approximately 0.5s) the CLR button. The output is confirmed by the stopping of regular flashing of the LED.
Notes:
- The output is not inverted (load off) as supplied state.
- The output contact is electrically open (load off), even if a reverse mode is programmed (load on) at power down of the receiver the output contact is open: load off.
- Radio function test (slave)
This RLT function (Radio Link Test, EEP §A5-3F-001) master slave allows, through a diagnostic product (master), to perform a radio test range (slave):
- a) On the diagnostic product, activate the master RLT mode (refer to its manual instruction)
- b) On this receiver, activate the slave RLT mode by a short press (approximately 0,5s) on LRN and CLR simultaneously. This mode is confirmed by the regular flashing (orange) of the LED.
- c) To exit this function, short press (approximately 0,5s) on the LRN button. the output is confirmed by the stopping of regular flashing of the LED. In the absence of test activity, this function stops automatically after 30 seconds.
Repeater 2 levels function
The repeater function of the 10020118 receiver is used to increase the range
between TRI02SYS transmitters and receivers. When the radio signal from a
transmitter is received, it is retransmitted to the associated receiver via a
maximum of two repeaters. Radio signals are received and transmitted
automatically.
-
a) On the receiver, activate the slave RTL mode by a short press (approximately 0,5s) on LRN and
CLR simultaneously. This mode is confirmed by the regular flashing (orange) of the LED; then short press (approximately 0,5s) CLR. This mode is confirmed by the red LED flashing. -
b) The current configuration is displayed by the number of LED flashing:
1. repeater off
2. activated repeater, level 1
3. activated repeater, levels 2
pour plus de détails, voir Communication Profiles – EEP consultable sure : www.enocean-alliance.org/what-is-enocean/specifications/
- c) To change the mode of operation of the repeater, short press CLR the number of times corresponding to the desired mode (b). Each press is acknowledged by maintaining LED on for the time of the press. The new configuration is stored and enabled, after 1,5s without any press. As soon as the flashing restarts, the new configuration is displayed and editable again (back to b).
- d) To exit this function, short press (approximately 0.5s) on the LRN button. The output is confirmed by stopping the flashing of LED. In the absence of activity, this function stops automatically after 30 seconds.
Note:
- This function is disabled on delivery of the receiver.
Factory configuration
With this function, the receiver can be reset to the factory configuration as
it was when the product was delivered:
- a) Switch off the device.
- b) Hold down the CLR button, then switch on the device,
- c) Once the LED is orange, wait for LED to turn red (5s) then release the CLR button.
- d) Press the CLR button again for about 1s, the red LED goes out.
- e) The product is in factory configuration.
Note:
- In the delivery state of the receiver, no transmitter is programmed, the repeater is disactivated and the consumption data is zero.
Remote Commissioning (ReCom)
The 10020118 receiver supports the “Remote Commissioning” features specified
by the EnOcean Alliance.
It can therefore be configured remotely, using a security key (accessible by
reading a QRcode on the side of the 10020118) and a compatible home automation
system or suitable software.
The Device Description File (DDF) required for configuration is available at
the following web address: www.trio2sys.fr
For more details on this function, see “Remote Commissioning” available at:
www.enocean-alliance.org/specifications/
Troubleshooting
New or existing installation
- Check the circuit breaker, the electrical supply and the load connected to the receiver associated with this sensor (qualified electricians).
- Check the connected load and the connecting cables (qualified electricians).
- If the receiver functions at a shorter distance relative to the sensor, it is subject to interference or used outside the transmission range.
- Search the system environment for changes that could cause the interference (for example movement of metallic cabinets, furniture or partitions).
- Use the sensor or receiver in a more suitable location.
- Clear the receiver and perform a new learn process.
Automatic activation of the receiver
- The cause may be the activation of a sensor external to the system which has by chance been programmed on the receiver.
- Clear the receiver and perform a new learn process.
Limitation of the range of the radio signals
Transmitter/receiver used close to metallic objects or close to materials
containing metallic elements.
Observe a distance of at least 10cm.
• Humidity in the materials.
• Device emitting high frequency signals such as: audio and video systems,
computers, electronic ballasts or fluorescent tubes. Observe a distance of at
least 0,5m.
Contacts
E-mail: ………………………. contact@trio2sys.fr
Recycling of the device
In accordance with European Directive 2012/19 / EU on waste electrical and
electronic equipment and its implementation in accordance with national laws,
this logo means that devices must not be thrown away with household waste. The
hazardous substances they are likely to contain can harm health and the
environment. Have these devices taken back by your distributor or use the
selective collection means made available by your municipality.
Declaration of conformity
This product can be marketed and distributed in the countries of the European
Union. Hereby TRI02SYS declares that radio equipment 10020118 is in compliance
with directive 2014/53/EU, known as the RED Directive.
The full text of the EU declaration of conformity is available at the
following internet address: www.trio2sys.fr.