AD90S2SM3FA Duct Type Air Conditioner
Instruction Manual
AD90S2SM3FA/ AD90S2SM4FA/ AD105S2SM3FA
AD105S2SM4FA/ AD125S2SM3FA/ AD125S2SM4FA
AD125S2SM8FA/ AD140S2SM3FA/ AD140S2SM4FA
AD140S2SM8FA
No.0150535515
AD90S2SM3FA Duct Type Air Conditioner
- This product must only be installed or serviced by qualified personnel.
Please read this manual carefully before installation. This appliance is filled with R32. Keep this manual for future reference.
Original instructions
Read the precautions in this manual carefully before operating the unit.
Service indicator; Read technical manual
This appliance is filled with R32.
Read the operator’s manual
Keep this manual where the user can easily find it.
WARNING
-
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
-
The appliance must be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater).
-
Do not pierce or burn.
-
Be aware that refrigerants may not contain an odour.
-
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
-
This appliance can be used by children aged 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given superivision or instruction concering use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
-
The wiring method should be in line with the local wiring standard.
-
All the cables shall have got the European authentication certificate. During installation, when the connecting cables break off, it must be assured that the grouding wire is the last one to be broken off. The explosion-proof breaker of the air conditioner should be all-pole switch. Distance between its two contacts should not be no less than 3mm. Such means for disconnection must be incorporated in the wiring.
-
Make sure installation is done according to local wiring regulation by professional persons.
-
Make sure ground connection is correct and reliable.
A leakage explosion-proof breaker must be installed. -
Do not use a refrigerant other than the one indicated on the outdoor unit(R32) when installing, moving or repairing. Using other refrigerants may cause trouble or damage to the unit, and personal injury.
-
The installation and service of this product shall be carried out by professional personnel, who have been trainedand certified by national training organizations that areaccredited to teach the relevant national competency standards that may be set in legislation.
-
Mechanical connectors used indoors shall comply with ISO 14903. When mechanicalconnectors are reused indoors, sealing parts shall be renewed. When flared joints arereused indoors, the flare part shall be re-fabricated.
-
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.
-
Disconnect the appliance from its power source during service and when replacing parts
-
A brazed, welded, or mechanical connection shall be made before opening the valves to permit refrigerant to flow between the refrigerating system parts. A vacuum valve shall be provided to evacuate the interconnecting pipe and/or any uncharged refrigerating system part.
-
The maximum working pressure is 4.3 MPa.
-
This maximum working pressure shall be considered when connecting the outdoor unit to indoor unit.
-
The refrigerant suitable for the indoor unit is R32 or R410A. The indoor unit shall only be connected to outdoor unit suitable for the same refrigerant.
-
The unit is a partial unit air conditioner, complying with partial unit requirements of the International Standard, and must only be connected to other units that have been confirmed as complying to corresponding partial unit requirements of the International Standard.
-
The A-weighted sound pressure level is below 70 dB.
-
The maximum refrigerant charge amount (kg), and the minimum floor area (m2) of the room in which the indoor unit will be installed, are specified in the table on the page 8.
-
Pipe-work shall be protected from physical damage and, in the case of flammable refrigerants, shall not be installed in an unventilated space, if the space is smaller than that specified in the table on the page 8
-
The installation of pipe-work shall be kept to a minimum.
-
Compliance with national gas regulations shall be observed.
-
Mechanical connections shall be accessible for maintenance purposes.
-
Handling, installation, cleaning, servicing and disposal of refrigerant shall be carried out as per the specifications on the following pages strictly.
-
Warning: Keep any required ventilation openings clear of obstruction.
-
Notice: Servicing shall be performed only as recommended by this manual instruction.
EUROPEAN REGULATIONS CONFORMITY FOR THE MODELS
CE
All the products are in conformity with the following European provision:
- Low voltage Directive
- Electomagnetic CompatibilitY
ROHS
The products are fulfilled with the requirements in the directive2011/65/EU of
the European parliament and of council on the Restriction of the use of
Certain Hazardous Substances in Electrical and Electronic Equipment(EU RoHS
Directive)
WEEE
In accordance with the directive 2012/19/EU of the European
parliament,herewith we inform the consumer about the dis-posal requirements of
the electrical and electronic products.
DISPOSAL REQUIREMENTS:
** Your air conditioning product is marked with this symbol.This means that
electrical and electronic products shall not be mixed with unsorted household
waste.Do not try to dismantle the system yourself:the dismantling of the air
conditioning system,treatment of the refrigerant,of oil and of other part must
be done by a qualified installer in accordance with relevant local and
national Iegislation.Air conditioners must be treated at a specialized
treatment facility for reuse, recycling and recovery.By ensuring this product
is disposed of correctly,you will help to prevent potential negative cons-
equences for the environment and humen health.Please contact the installer or
local authority for more information. Battery must be removed from the remote
controller and dis-posed of separately in accordance with relevant local and
nationl legislation.
IMPORTANT INFORMATION REGA-RDING THE REFRIGERANT USED**
This product contains fluorinated greenhouse gases covered by the Kyoto
Protocol.Do not vent into the atmosphere.
Refrigerant type:R32
GWP:675
Refrigerant type:R410A
GWP:2088
GWP=global warming potential
Please fill in with indelible ink,
- 1 the factory refrigerant charge of the product
- 2 the additional refrigerant amount charged in the field and
- 1+2 the total refrigerant charge
on the refrigerant charge label supplied with the product. The filled out
label muset be adhered in the proximity of the product charging port(e.g.onto
the inside of the stop value cover).
A contains fluorinated greenhouse gases covered by the Kyoto Protocol
B fatory refrigerant charge of the product:see unit name plate
C additional refrigerant amount charged in the field
D total refrigerant charge
E outdoor unit
F refrigerant cylinder and manifold for charging
WARNING
If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualified persons in order to avoid a hazard.
This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the
appliance.
This appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the hazards involved.
Children shall not play with the appliance. Cleaning and user maintenance
shall not be made by children without supervision.
The appliances are not intended to be operated by means of an external timer
or separate remote-control system.
Keep the appliance and its cord out of reach of children less than 8 years.
WARNING
Do not use means to accelerate the defrosting process or to clean, other
than those recommended by the manufacturer.
The appliance must be stored in a room without continuously operating ignition
sources(for examples: open flames, an operating gas appliance or an operating
electric heater).
Do not pierce or bum.
Be aware that refrigerants may not contain an odour.
If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent or similarty qualified persons in order to avoid a hazard.
This appliance can be used by children aged 8 years and above and persons with
reduced physical,sensory or mental capabilities or lack of experience and
knowledge if they have been given superivision or instruction concering use of
the appliance in a safe way and understand the hazards involved. Children
shall not play with the appliance. Cleaning and user maintenance shall not be
made by children without supervision.
The wiring method should be in line with the local wiring standard.
All the cables shall have got the European authentication certificate. During
installation, wnen the connecting cables break off, it must be assured that
the grouding wire is the last one to be broken off. The explosion-proof
breaker of the air conditioner should be all-pole switch.
Distance between it’s two contacts should not be no less than 3mm. Such means
for disconnection must be incorporated in the wiring.
Make sure installation is done according to local wiring regulation by
professional persons.
Make sure ground connection is correct and reliable. A leakage explosion-proof
breaker must be installed.
The installation and service of this product shall be carried out by
professional personnel, who have been trainedand certified by national
training organizations that areaccredited to teach the relevant national
competency standards that may be set in legislation.
Mechanical connectors used indoors shall comply with ISO 14903. When
mechanical connectors are reused indoors, sealing parts shall be renewed. When
flared joints are reused indoors, the flare part shall be re-fabricated.
This appliance is intended to be used by expert or trained users in shops, in
light industry and on farms, or for commercial use by lay persons.
Disconnect the appliance from its power source during service and when
replacing parts
The maximum working pressure is 4.15 MPa. This maximum working pressure shall
be considered when connecting the outdoor unit to indoor units.
The refrigerant suitable for the indoor unit is R410A. The indoor unit shall
only be connected to outdoor unit suitable for the same refngerant.
The unit isa partial unit air conditioner, complying with partial unit
requirements of the Intemational Standard, and must only be connected to other
units that have been confirmed as complying to corresponding partial unit
requirements of the Intemational Standard.
The A-weighted sound pressure level is below 70 dB.
Cautions
Disposal of the old air conditioner
Before disposing an old air conditioner that goes out of use, please make
sure it’s inoperative and safe. Unplug the air conditioner in order to avoid
the risk of child entrapment.
It must be noticed that air conditioner system contains refrigerants, which
require specialized waste disposal. The valuable materials contained in a air
conditioner can be recycled. Contact your local waste disposal center for
proper disposal of an old air conditioner and contact your local authority or
your dealer if you have any question. Please ensure that the pipework of your
air conditioner does not get damaged prior to being picked up by the relevant
waste disposal center, and contribute to environmental awareness by insisting
on an appropriate, anti-pollution method of disposal.
Disposal of the packaging of your new air conditioner
All the packaging materials employed in the package of your new air
conditioner may be disposed without any danger to the environment.
The cardboard box may be broken or cut into smaller pieces and given to a
waste paper disposal service. The wrapping bag made of polyethylene and the
polyethylene foam pads contain no fluorochloric hydrocarbon.
All these valuable materials may be taken to a waste collecting center and
used again after adequate recycling.
Consult your local authorities for the name and address of the waste materials
collecting centers and waste paper disposal services nearest to your house.
Safety Instructions and Wamings
Before starting the air conditioner, read the information given in the User’s
Guide carefully. The User’s Guide contains very important observations
relating to the assembly, operation and maintenance of the air conditioner.
The manufacturer does not accept responsibility for any damages that may arise
due to non-observation of the following instruction.
- Damaged air conditioners are not to be put into operation. In case of doubt, consult your supplier.
- Use of the air conditioner is to be carried out in strict compliance with the relative instructions set forth in the User’s Guide.
- Installation shall be done by professional people, don’t install unit by yourself.
- For the purpose of safety, the air conditioner must be properly grounded in accordance with specifications.
- Always remember to unplug the air conditioner before opening inlet grill. Never unplug your air conditioner by pulling on the power cord. Always grip plug firmly and pull straight out from the outlet.
- All electrical repairs must be carried out by qualified electricians. Inadequate repairs may result in a major source of danger for the user of the air conditoiner.
- Do not damage any parts of the air conditioner that carry refrigerant by piercing or perforating the air conditioner’s tubes with sharp or pointed items, crushing or twisting any tubes, or scraping the coatings off the surfaces. If the refrigerant spurts out and gets into eyes, it may result in serious eye injuries.
- Do not obstruct or cover the ventilation grille of the air conditioner. Do not put fingers or any other things into the inlet/outlet and swing louver.
- Do not allow children to play with the air conditioner. In no case should children be allowed to sit on the outdoor unit.
- This appliance is not intended for use by persons (including children) with reducedphysical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction conceming use of the appliance by a person responsible for their safety.
- Children should be supervised to ensure that they do not play with the appliance.
Safety Precautions
- Before starting to use the system, read carefully this “SAFETY PRECAUTIONS” to ensure a proper operation of the system.
- Safety precautions described here are classified to “ WARNING” and “ CAUTION”. Precautions which are shown in the column of “ WANING” means that an improper handing could lead to a grave result like a death, serious injury, etc. However, even if precautions are shown in the column of “ CAUTION”, a very serious problem could occur depending on situation. Make sure to observe these safety precautions faithfully because they are very important information to ensure the safety.
- Symbols which appear frequently in the text have following meanings.
| Strictly prohibited.| | Observe instructions faithfully.| | I Provide a positive grounding.
---|---|---|---|---|--- - When you have read through the manual keep it always at hand for read consultation. If the operator is replaced, make sure to hand over this manual to the new operator.
CAUTIONS FOR INSTALLATION
WARNING
The system should be applied to places as office, restaurant, residence and
the like.
Application to inferior environment such as an engineering sho p, could cause
equipment malfunction and serious injury or death.| The system should be
installed by your dealer or a professional installer.
Installation by yourself is not encouraged because it could cause such
problems as water leakage, electrical shock or fire accident by some improper
handing.| When you need some optional devices such as a hurvidif er, electric
heater, etc., be sue to use the products which are recommended by us. These
devices should be attached by a professional installer.
Installationbyyourself is nct encouraged because it could cause such problems
as water leakage, electrical shock or fire accident by some improper handing.
CAUTION
Do not install nearby the place where may have leakage of flammable gas.
If the gas leakes and gathers around, it may cause the fire.
| Depending on the place of installation, a circuit breaker may be necessary.
Unless the circuit breaker is installed, it could cause elecrical shocks.
| Drain pipe should be arranged to provide a positive draining.
If the pipe is arranged improperly, fumiture or the likes may be damaged by leaked water.
Where strong winds may prevail, the system should be fixed securely to prevent
a collapse.
Bodily injury could result by a collapse.| Install on the place where can
endure the weight of air conditioner.
Bodily injury could result by a careless installation.| Make sure the system
is grounded.
Grounding cable should never be connected to a gas pipe, city water pipe, lightning conductor rod or grounding cable of telephone. If the grounding cable is not set properly, it could cause electric shocks.
CAUTIONS FOR TRANSFER OR REPAIR
WARNING
Modification of the system is strictly prohibited. When the system needs a
repair, consult your dealer.
Improper practice of repair could cause water leakage, electric shock or
fire.| When the air conditioner is relocated, contact your dealer or a
professional installer.
Improper practice of installation could cause water leakage, electric shock or
fire.
CAUTION FOR OPERATION
WARNING
You should refrain from exposing your body directiy to cool wind for a long time.
It could affect your physical condition or cause some health problems.
| Do not poke the air inlet or outlet with a bar, etc.
Since the internal fan is operating with a high speed, it could cause an injury.
| When any abnormal condition (scorching smell or others) is found, stop the
operation immediately and turn off the power switch. Then consult your dealer.
If you continue the operation without removing the cause, it could result in a
trouble, electric shock or fire.
CAUTION
The system should never be used for any other purposes than intended such as
for preservation of food, flora and fauna, precision devices or work of art.
It could cause deterioration of food or other problems.| Do not handle
switches with a wet hand. It could cause electric shocks.| Combustion
apparatus should not be placed
allowing a direct exposure to wind of air conditioner. Incomplete combustion
could occur on the apparatus.
Do not wash the air conditioner with water. It could cause electric shocks.|
Do not install the system where the air outlet reaches directly the flora and
fauna.
It will not be good for their health.
| Make sure to use a fuse of proper electric rating.
Use of steel or copper wire in place of a fuse is strictiy prohibited because it could result in a trouble or fire accident.
Neither stand on the air conditioner nor place something on it.
There are risks of falling or injury by collapsed object.| It is strictly
prohibited to place a container of combustible gas or liquid near the air
conditioner or to spray it directly with the gas or liquid.
It could cause a fire accident
| Do not operate the system while the air outlet grill is removed.
There is a risk of injury.
Do not use the power switch to turn on or off the system.
It could cause a fire or water leakage.| Do not touch the air outlet section
while the swing louver is operating.
There is a risk of injury.| Do not use such equipment as a water heater, etc.
around the indoor unit or the wire controller. If the system is operated at
the vicinity of such equipment which generates steam, condensed water may drip
during cooling operation or it could cause a fault current or short-circuit.
When operating the system simultaneously with a combustion apparatus, indoor
air must be ventilated frequently. Insufficient ventilation could cause an
oxygen deficiency accident.| Check occasionally the support structure of the
unit for any damage after a use of long period of time. If the structure is
not repaired immediately, the
unit could topple down to cause a personal injury.| When cleaning the system,
stop the operation and turn off the power switch.
Cleaning should never be done while the internal fans are running with high
speed.
Do not put water containers on the unit such as a flower vase, etc.
If the water enters into the unit and damages the electric insulation
material, it may cause electric shock.
The machine is adaptive in following situation
- Applicable ambient temperature range:
Cooling| Indoor temperature| max. DB/WB
min. DB/WB| 32/23°C
18/14°C
---|---|---|---
Outdoor temperature| max. DB/WB
min. DB/WB| 46/26°C
10/6°C
Heating| Indoor temperature| max. DB/WB
min. DB/WB| 27°C
15°C
Outdoor temperature| max. DB/WB
min. DB/WB| 24/18°C
-15°C - If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.
- If the fuse on the indoor PC board is broken please change it with the type of T 3.15A/250V(For AD125,AD140S2SM3FA,AD125,AD140S2SM4/8FA),or the type T 5A/250V(For AD90,AD105S2SM3FA,AD90,AD105S2SM4FA)
- The wiring method should be in line with the local wiring standard.
- The power cable should be: HO5RN-F 3G 4.0mm2(outdoor unit 1UH071/090/105N1ERG),or HO5RN-F 3G 6.0mm2(outdoor unit 1UH125/140P1ERG), or HO5RN-F 5G 4.0mm2(outdoor unit 1UH125/140P1EK), The connecting cable should be: HO5RN-F 4G 2.5mm2 All the cables shall have got the European authentication certificate. During installation, when the connecting cables break off, it must be assured that the grouding wire is the last one to be broken off.
- The power cable and connect cable should be self-provided.
- The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be no less than 3mm.
- The indoor unit installation height is at least 2.5m.
- A leakage breaker must be installed.
- For AD90S2SM3FA/AD90S2SM4FA/AD105S2SM3FA/AD105S2SM4FA/AD125S2SM3FA/AD125S2SM4FA/ AD140S2SM3FA/AD140S2SM4/AD125S2SM8FA/ AD140S2SM8FAFA,we can get the 10 different ESP through adjust wired controllerYR-E17A,please refer below:
Stactic pressure grade | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 |
---|---|---|---|---|---|---|---|---|---|---|
Stactic pressure | 25Pa | 37Pa | 50Pa | 70 Pa | 90Pa | 100Pa | 110Pa | 120Pa | 130Pa |
150Pa
Adjsutment metchod by wired controller YR-E17A: In the state of ON and non
screen saving state, press Fan+ Set keys for 5 seconds to enter static
pressure grade adjustment state with static pressure icon flashing and current
static pressure grade statically displaying. Press key ↑↓ to change static
pressure grade, then press Set key to confirm. Details please refer to wired
controller operation & installation manual.
Adjsutment metchod by Infrared remote controller+Infrared receiver RE-02:
Step a:set the Infrared remote controller at condition: FAN mode , fan speed
high
Step b:then aim the remote controller at the infrared remote receiver RE-02,
press HEALTH button 4+N times ( 1≤N≤10, integer) within 12 seconds , then the
receiver will beep N+1 times , the static pressure level N is been set
successfully.
Note: For Infrared remote controller YR-HBS01, need press ON/OFF button make
the controller’s at OFF status first, then open the button cover press FRESH
button will enter FAN mode interface.
Parts and Functions
AD90S2SM3FA AD105S2SM3FA AD125S2SM3FA AD125S2SM8FA AD140S2SM4FA
AD90S2SM4FA AD105S2SM4FA AD125S2SM4FA AD 140S2SM3FA AD140S2SM8FA
Installation Manual For Wire Controller
5. Wiring connections of wire controller:
There are three methods to connection wire controller and the indoor units:
A.One wired controller can control max. up to 16 sets of indoor units, and 3
pieces of polar wire must connect the wire controller and the master unit (the
indoor unit connected with wire controller directly), the others connect with
the master unit through 2 pieces of polar wire
B. One wire controller controls one indoor unit, and the indoor unit connects
with the wire controller through 3 pieces of polar wire.
C. Two wired controllers control one indoor unit. The wire controller
connected with indoor unit is called master one, the other is called slave
one. Master wire controller and indoor unit; master and slave wire controllers
are all connected through 3 pieces of polar wire.
6. Communication wiring:
The wire controller is equipped with special communication wiring in the
accessories. 3-core terminal (1-white 2-yellow 3-red) is connected with the
terminal A, B, C of wire controller respectively. The communication wiring is
5 meter long; if the actual length is more than it, please distribute wiring
according to below table:
Communication wiring length(m) | Dimensions of wiring |
---|---|
< 100 | 0.3mm²x3-core shielded wire |
≥100 and <200 | 0.5mm²x3-core shielded wire |
≥200 and <300 | 0.75mm²x3-core shielded wire |
≥300 and <400 | 1.25mm²x3-core shielded wire |
≥400 and <600 | 2mm²x3-core shielded wire |
WIRED CONTROLLER & INDOOR PCB CONNECTION(one for one wiring type):
Note: When do the wired controller & indoor PCB wiring work ,do not connect the shielded wired to the unit’s shell,do not parallel wiring with strong electric lines within 0.3 meters, please keep strong lines and the signal lines separately.
Heating Mode
“HOT KEEP” function
“HOT KEEP’ is operated in the following cases.
-
When heating is started:
In order to prevent blowing out of cool wind, the indoor unit fan stopped according to the room temperature which heating operation is started. Wait for approx. 2 to 3 minute, and the operation will be automatically changed to the ordinary heating mode. -
Defrosting operation (in the heating mode):
When it is liable to frost, the heating operation is stopped automatically for 5 to 12 minutes once per approx. one hour, and defrosting is operated. After defrosting is completed, operation mode is automatically changed to ordinary heating operation. -
When the room thermosiat is actuated:
When room temperature increases and room temperature controller actuates, the fan speed is automatically changed to stop under low temperature condition of indoor heat exchanger. When room temperature decreases, air conditioner automatically changes over to ordinary heating operation. :
Warming operation
-
Heat pump type warming
With the heat pump type warming, the mechanism of heat pump that concentrate heat of outdoor air with the help of refrigerant to warm the indoor space, is utilized. -
Defrosting operation
When a room is warmed with a heat pump type air conditioner, frost accumulates on the heat exchanger of outdoor unit along with the drop of indoor temperature. Since the accumulated frost reduces the effect of warming, it is necessery to automatically switch the operation to the defrosting mode. During the defrosting operation, heating operation is interrupted. -
Atmospheric temperature and warming capacity
Wamming capacity of heat pump type air conditioner decreases along with the drop of outdoor temperature.
When the warming capacity is not sufficient, it is recommended to use another heating implement. -
Period of warm-up
Since the heat pump type air conditioner employs a method to circulate warm winds to warm the entire space of a room, it takes time before the room temperature rises.
It is recommendable to start the operation a little earlier in a very cold moming.
Care and Maintenance
Points to observe Turn off the power supply switch. Do not touch with wet hand. Do not use hot water or volatile liquid.
Points to observe
Turn off the power supply switch.| Do not touch with wet hand.| Do not use hot water or volatile liquid.
CAUTION
- Do not open the inlet grill until fan stops completely.
- Fan will continue rotating for a while by the law of inertia after operation is being stopped.
Cleaning the air filter
- Clean the air filter by lightly tapping it or with the cleaner. It is more effective to clean the air filter with water. If the air filter is very dirty, dissolve neutral detergent in the lukewarm water (approx. 30°C), rinse the air filter in the water, and thoroughly wash the air filter off the detergent in the plain water.
- After drying the air filter, set it up on the air conditioner.
CAUTION
- Do not dry the air filter with fire.
- Do not run the air conditioner without the air filter.
Care and Cleaning of the unit
- Clean with soft and dry cloth.
- If it is very dirty, dissolve neutral detergent in the lukewarm water and make the cloth wet with the water. After wiping, clean off the detergent using clean water.
Post-Season Care
- Operate the unit with FAN mode on a fair day for about half a day to dry the inside of the unit well.
- Stop operation and turn off the power supply switch. Electric power is consumed even the air conditioner is in stop.
- Clean the air filter and set it in the place.
Pre-Season Care
- See that there are no obstacles blocking the air inlet and air outlet of both indoor and outdoor units.
- Make sure that the air filter is not dirty.
- Cut in the power supply switch 12 hours before starting run.
Troubleshooting
Please check the following things about your air conditioner before making a service call.
Unit fails to start
Is the power source switch adjust cut in? Power supply switch is not ON.| Is
city supply power in normal?| Isn’t the signal receiving section exposed to
the direct sunlight or strong illumination?| Isn’t the earth leakage breaker
in action?
It is dangerous. Turn off the power supply switch immediately and contact the
sales dealer.
Cooling or heating is not sufficient
Is the thermostat adjust as required?| Isn’t the air filter dirty?| Isn’t any
doors or windows left open?| Doesn’t any obstacle exist at the air inlet or
outlet?
Cooling is not sufficient
Isn’t sun-shine invading direct?| Isn’t any unexpected heating load
generated?| Isn’t the room much crowded?| The wind does not blow during
heating operation
Isn’t it warming up?
When the air conditioner does not operate properly after you have checked the above mentioned items or when the following phenomenon is observed, stop the operation of the air conditioner and contact your sales dealer.
- The fuse or breaker often shuts down.
- Water drops off during cooling operation.
- There is a irregularity in operation or abnormal sound is audible.
- When the CHECK LED (red) flickers, an irregularity has occurred in the air conditioner.
The followings are not malfunction
Water flowing sound is heard.| When the air conditioner is started, when the
compressor starts or stops during operation or when the air conditioner is
stopped, it sometimes sounds “shuru shuru” or “gobo gobo”. It is the flowing
sound of the refrigerant, and it is not a trouble.
---|---
Cracking sound is heard.| This is caused by heat expansion or contraction of
plastics.
It smells.| Air which blows out from the indoor unit sometimes smells. The
smell results from residents of tobacco smoke or cosmetics stuck inside of
unit.
During operation, white fog comes out of indoor unit.| When the air
conditioner is used at restaurant etc. where dense edible oil fume is always
exists, white fog sometimes blows out of air outlet during operation. In this
case consult sales dealer for cleaning the heat exchanger.
It is switched into the FAN mode during cooling.| To prevent frost from being
accumulated on the indoor unit heat exchanger, it is sometimes automatically
switched to the FAN mode,but it will soon return to the cooling mode.
The air conditioner can not be restarted soon after it stops.| Even if the
operation switch is turned on, cooling, dehumidifying or heating is not
operable for three minutes after the conditioner is stopped. Because the
protecting circuit is activated. (During this time air conditioner operates in
fan mode.)
Air does not blow or the fan speed can not be changed during dehumidifying.|
When it is excessively cooled during dehumidifying, the blower automatically
repeats reducing and lowering the fan speed.
During operation, operation mode has changed over automatically.| Isn’t the
AUTO mode selected?
In the case of AUTO mode, operation mode is changed automatically from cooling
to heating or vise-versa according to the room temperature.
Water or steam generates from the outdoor unit during heating.| This results
when frost accumulated on the outdoor unit is removed (during defrosting
operation).
INDOOR UNIT TROUBLE SHOOTING
AD90/1 05S2SM3FA,AD90/1 05S2SM4FA,AD125S2SM8FA/AD140S2SM8FA
LED flash times of indoor PCB| Wired controller display| Contents
of Malfunction| Possible reasons
---|---|---|---
LED4| LED3
0| 1| 1| Malfunction of indoor unit ambient temperature sensor| Sensor
disconected,or broken,or at wrong position,or short circuit
0| 2| 2| Malfunction of indoor unit piping temperature sensor| Sensor
disconected,or broken,or at wrong position,or short circuit
0| 4| 4| EEPROM wrong of indoor PCB| EEPROM chip disconected or broken or
wrong program-med,or PCB broken
0| 7| 7| Abnormal communication between indo- or and outdoor units| Wrong
connection,or the wires be disconected or wrong adress setting of indoor unit
or faulty power supply or faulty PCB or slave unit malfunction in MAXI system
0| 8| 7
*flashing| Abnormal communication between wired controller and indoor unit| Wrong connection or wired controller broken,or PCB faulty
0| 12| OC| Malfunction of drain system| Pump motor disconnected or at wrong
position,or the float switch,disconnected, or at wrong position,or the short
circuit bridge disconneted
0| 13| OD| Zero cross sigal wrong| Zero cross sigal detected wrong
0| 14| OE| Indoor unit DC fan motor abnormal| DC Fan motor disconnected or DC
Fan broken or circuit broken or motor blocked
Note:
1. The outdoor failure can also be indicated by the indoor unit,the checking
method as follo-ws:If the outdoor error code is M (DECIMAL), the indoor unit’s
wired controller display will show the after converted hexadecimal code of
“M+20″(DECIMAL), for example,if the outdoor error code is 2,the indoor unit
wired controller display will flash the error code 16 (2→2+20=22 → change
decimal 22 to hexadecimal code,get 16 )
2. To get much more details about the out door unit failure,please refer to
the outdoor unit trouble shooting list.
3. For YR-E17A, communication error between I.D. PCB and wired controller, 07
will flash in the main display interface not the check display interface.
INDOOR UNIT TROUBLE SHOOTING
AD125/140S2SM3FA,AD125/140S2SM4FA
LED flash times of indoor PCB| Wired controller display| Contents
of Malfunction| Possible reasons
---|---|---|---
LED4| LED3
0| 1| 1| Malfunction of indoor unit ambient temperature sensor| Sensor
disconected,or broken,or at wrong position,or short circuit
0| 2| 2| Malfunction of indoor unit piping temperature sensor| Sensor
disconected,or broken,or at wrong position,or short circuit
0| 4| 4| EEPROM wrong of indoor PCB| EEPROM chip disconected or broken or
wrong programmed,or PCB broken
0| 7| 7| Abnormal communication between indoor or and outdoor units| Wrong
connection,or the wires be disconected or wrong adress setting of indoor unit
or faulty power supply or PCB hardware malfunction
0| 8| 07
flashing| Abnormal communication between wired controller and indoor unit| Wrong connection or wired controller broken,or PCB hardware malfunction
0| 12| 0C| Malfunction of drain system| Pump motor disconnected or at wrong
position,or the float switch disconnected, or at wrong position,or the short
circuit bridge disconneted
0| 13| 0D| Zero cross sigal wrong| Zero cross sigal detected wrong
0| 14| 0E| Abnormal communication between main control PCB & fan motor driver|
communication wire disconeor wrong conected or PCB hardware malfunction
0| 15| 0F| Fan motor overcurrent| fan motor current too high
0| 17| 11| DC voltage high or low| DC voltage of the fan motor driver too high
or too low
0| 18| 12| F.M.D temperature high| Fan motor driver over 95ºC
0| 19| 13| Fan motor out of step| wrong rotor location detected
M(≥1)| N(≥0)| /| Error of the outdoor unit| See note 1, 2
Note:
1. The outdoor fai ure can also be indicated by the indoor unit,the checking
method as following:outdoor unit error code=(M10+N)-20.LED4 flash M times and
LED3 flash N times .
2. LED4 is a yellow one on the indoor main control PCB,LED3 is a green one.
3. To get much more details about the out door unit failure,please refer to
the outdoor unit trouble shooting list.
4. For YR-E17A,communication error between indoor PCB and wired controller,
07 will flash in the main display interface instead of display at the check
interface.
Precaution for Installation
- Please read these “Safety Precautions” first and then accurately execute the installation work.
- Though the precautionary points indicated herein are divided under two headings, 4 WARNING and 4&4 CAUTION, those points which are related to the strong possibility of an installation done in error resulting in death or serious injury are listed in the 4 WARNING section. However, there is also a possibility of serious consequences in relationship to the points listed in the 4 CAUTION section as well. In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned.
- After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please explain operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner’s manual. Moreover, ask the customer to keep this sheet together with the owner’s manual.
WARNING
- This system should be applied to places as office, restaurant, residence and the like. Application to inferior environment such as engineering shop could cause equipment malfunction.
- Please entrust installation to either the company which sold you the equipment or to a professional contractor. Defects from improper installations can be the cause of water leakage, electric shocks and fires.
- Execute the installation accurately, based on following the installation manual. Again, improper installations can result in water leakage, electric shocks and fires.
- When a large air-conditioning system is installed to a small room, it is necessary to have a prior planned countermeasure for the rare case of a refrigerant leakage, to prevent the exceeding of threshold concentration. In regards to preparing this countermeasure, consult with the company from which you perchased the equipment, and make the installation accordingly. In the rare event that a refrigerant leakage and exceeding of threshold concentration does occur, there is the danger of a resultant oxygen deficiency accident.
- For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insufficient, injury can result from a falling of the unit.
- Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and hurricanes, etc. Improper installations can result in accidents due to a violent falling over of the unit.
- For electrical work, please see that a licensed electrician executes the work while following the safety standards related to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive use circuits are used. Insufficient power source circuit capacity and defective installation execution can be the cause of electric shocks and fires.
- Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to the terminal connection part, through properly securing it. Improper connection or securing can result in heat generation or fire.
- Take care that wiring does not rise upward, and accurately install the lid/service panel. Its improper installation can also result in heat generation or fire.
- When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the designated refrigerant R32 within the refrigeration cycle. Rupture and injury caused by abnormal high pressure can result from such mixing.
- Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this company can result in water leakage, electric shock, fire and refrigerant leakage.
CAUTION
-
Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightning rod or a telephone ground wire. Improper placement of ground wires can result in electric shock.
-
The installation of an earth leakage breaker is necessary depending on the established location of the unit. Not installing an earth leakage breaker may result in electric shock.
-
Do not install the unit where there is a concern about leakage of combustible gas.
The rare event of leaked gas collecting around the unit could result in an outbreak of fire. -
For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.
Is The Unit Installed Correctly
Confirm the following items for safe and comfortable use of air conditioner.
The installation work is to be burden on the sales dealer, and do not conduct
it by yourself.
Installation place
Avoid installing the air conditioner near the place where possibility of
inflammable gas leakage exists. Explosion (Ignition) may occur.| Install the
unit at well ventilated place. If some obstacle exist, it may cause capacity
reduction or noise increase.| Install the air conditioner firmly on the
foundation that can fully support the weight of the unit.If not, it may cause vibration or noise.
Select the place so as not to annoy neighbor with the hot air or noise.| Snow
protection work is necessary where outdoor unit is blocked up by snow.
For details consult your sales dealer.| It is advisable not to install the air
conditioner at the following special place.
It may cause malfunction, consult the sales dealer when you have to install
the unit on such a place.
• The place where corrosive gas generates (Hot spring area etc.)
• The place where salt breeze blows (Seaside etc.)
• The place where dense soot smoke exists
• The place where humidity is extraordinarily high
• The place where near the machine which radiates the electromagnetic wave
• The place where voltage variation is considerably large
Electric work
The electric work must be burden on the authorized engineer with qualification
for electric work and grounding work, and the work must be conducted in
accordance with electric equipment technical standard.
- The power source for the unit is to be of exclusive use.
- An earth leakage breaker should be installed.(This is necessary to prevent electric shock.)
- The unit must be grounded.
When you change your address or the installation place
Special technology is required for removal or reinstallation of air
conditioner, consult the sales dealer. Besides, construction expense is
charged for removal or reinstallation.
For inspection and maintenance
The capacity of air conditioner will decrease by contamination of inside of
unit when it is used for about three years although depending upon the
circumstances under which it is used, and so in addition to the usual
maintenance service, special inspection/maintenance service is necessary. It
is recommended to make a maintenance contract (charged) by consulting your
sales dealer.
Installation Procedure
Indoor Unit
NOTE
All wiring of this installation must comply with NATIONAL, STATE AND LOCAL
REGULATIONS. These instructions do not cover all variations for every kind of
installation circumstance. Should further information be desired or should
particular problems occur, the matter should be referred to your local
distributor.
WARNING
BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH,
EQUIPMENT MALFUNCTION AND/OR PROPERTY DAMAGE.
Preparation of indoor unit
Before or during the installation of the unit, assemble necessary optional
panel etc. depending on the specific type.
Select places for installation satisfying following conditions and at the same
time obtain the consent on the part of your client user.
a. Places where chilled or heated air circulates freely. When the installation
height exceeds 3m warmed air stays close to the ceiling. In such cases,
suggest your client users to install air circulators.
b. Places where perfect drainage can be prepared and sufficient drainage.
c. Places free from air disturbances to the suction port and blowout hole of
the indoor unit, places where the fire alarm may not malfunction or short-
circuit.
d. Places with the environmental dew-point temperature is lower than 28°C and
the relative humidity is less than 80 %. (When installing at a place under a
high humidity environment, pay sufficient attention to the prevention of
dewing such as thermal insulation of the unit. )
e. Ceiling height shall have the following height.
| AD90S2SM3FA AD90S2SM4FA AD105S2SM3FA AD105S2SM4FA AD125S2SM3FA AD125S2SM4FA
AD125S2SM8FA AD140S2SM3FA AD140S2SM4FA AD140S2SM8FA
---|---
Combination with silent panel| 366mm
Installation space
Avoid installation and use at those places listed below.
a. Places exposed to oil splashes or steam (e.g. kitchens and machine plants).
Installation and use at such places incur deteriorations in the performance or
corrosion with the heat exchanger or damage in molded synthetic resin parts.
b. Places where corrosive gas (such as sulfurous acid gas) or inflammable gas
(thinner, gasoline etc.) in generated or remains. Installation and use at such
places cause corrosion in the heat exchanger and damage in molded synthetic
resin parts.
c. Places adjacent to equipment generating electromagnetic waves or high-
frequency waves such as in hospitals. Generated noise may cause malfunctioning
of the controller.
Pipe size
Model | Liquid side | Gas side |
---|
AD90S2SM3FA AD90S2SM4FA AD105S2SM3FA AD105S2SM4FA AD125S2SM3FA AD125S2SM4FA AD125S2SM8FA AD140S2SM3FA AD140S2SM4FA AD140S2SM8FA| Ø 9.52mm| Ø 15.88mm
1. Preparation Por suspending the unit
a. Size oP hole at ceiling and position oP hanging bolts
Dimentions ⇒
Model ⇓| A(mm)| B(mm)| C(mm)| D(mm)| E(mm)| F(mm)
---|---|---|---|---|---|---
AD90S2SM3FA AD90S2SM4FA| 1162| 1612| 1672| 620| 765| 825
AD105S2SM3FA AD105S2SM4FA AD125S2SM3FA AD125S2SM4FA AD125S2SM8FA AD140S2SM3FA
AD140S2SM4FA AD140S2SM8FA| 1562| 2012| 2072| 620| 765| 825
b.Hanger bolts installation
Use care of the piping direction when the unit is installed.
2. Installation of indoor unit
Fix the indoor unit to the hanger bolts.
If required, it is possible to suspend the unit to the beam, etc. Directly by
use of the bolts without using the hanger bolts.
Note
When the dimensions of main unit and ceiling holes does not match, it can be
adjusted with the slot holes of hanging bracket.
Adjusting to the levelness
(a) Adjust the out-of levelness using a level or by the following method. Make
adjustment so that the relation between the lower surface of the unit proper
and water level in the hose becomes as given below.
(b) Unless the adjustment to the levelness is made properly, malfunctioning or
failure of the float switch may occur.
Tap selection on blower unit
(When the high performance filter is used.)
Taps of blower unit are set at the standard selection at the shipping from
factory. Where the static pressure is raised by employing such option as the
high performance filter, etc., change the connection of connectors provided at
the flank of control box as shown below.
Standard tap (at shipping) | High speed tap |
---|
|
Drain Pipe
Drain Piping
(a) Drain piping should always be in a downhill grade (1/50-1/100) and avoid
riding across an elevation or making traps.
Unit model | The size of drain opening |
---|
AD90S2SM3FA AD90S2SM4FA
AD105S2SM3FA AD105S2SM4FA AD125S2SM3FA AD125S2SM4FA AD125S2SM8FA AD140S2SM3FA
AD140S2SM4FA AD140S2SM8FA| 025mm
(b) When connecting the drain pipe to unit, pay suffcient attention not to
apply excess force to the piping on the unit side. Also, fix the piping at a
point as close as possible to the unit.
(c) For unit without water pump,please refer to the digram and select drain
pipe size according to drain opening inner diameter size. The drain pipe shall
be slant downwards (greater than 1/100). The horizontal length of the drain
pipe shall be less than 20 m. In case of long pipe, supports shall be provided
every 1.5-2m to prevent wavy form. Central piping shall be laid out according
to the right figure. Take care not to apply external force onto the drain pipe
connection part.
(d) For unit with water pump drain pipeuse hard PVC general purpose pipe VP
which can be purchased locally. When connecting, insert a PVC pipe end
securely into the drain socket before tightening securely using the attached
drain hose and damp. Adhesive must not be used for connection of the drain
socket and drain hose (accessory).
(e) When constructing drain piping for several units, position the common pipe
about 100 mm below the drain outlet of each unit as shown in the sketch. Use
VP-30(11/4″) or thicker pipe for this purpose.
(f) The hard PVC pipe put indoor side should be heat insulated. Do not ever
provide an air vent.
(g) The height of the drain head can be elevated up to a point 500 mm above
the ceiling, and when an obstacle exists in the ceiling space, elevate the
piping to avoid the obstacle using an elbow or corresponding gadget. When
doing this, if the stretch for the needed height is higher than 500 mm, the
back-flow quantity of drain at the event of interruption of the operation gets
too much and it may cause overflow at the drain pan. Therefore, make the
height of the drain pipe within the distance given in the sketch below.
(h) Avoid positioning the drain piping outlet at a place where generation of
odor may be stimulated. Do not lead the drain piping direct into a sewer from
where sulfur gas may generate.
Drain Pipe
Drainage Test
- Conduct a drainage test after completion of the electrical work.
- During the trial, make sure that drain flows properly through the piping and that no water leaks from connections.
- In case of a new building, conduct the test before it is furnished with the ceiling.
- Be sure to conduct this test even when the unit is installed in the heating season.
Procedures
(a) Supply about 1000 cc of water to the unit through the air outlet using
a feed water pump.
(b) Check the drain while cooling operation.
Before the electrical work has not been completed, connect a convex joint in
the drain pipe connection to provide a water inlet. Then, check if water leaks
from the piping system and that drain flows through the drain pipe normally.
Air Duct
Installation work for air outlet ducts
Calculate the draft and external static pressure and select the length, shape
and blowout.
A. Blowout duct
- 2-spot, 3-spot and 4-spot with 0 200 type duct are the standard specifications.
Note
- Shield the central blowout hole for 2-spot.
- Shield the blowout hole around the center for 3-spot.
- Limit the difference in length between spots at less than 2:1.
- Reduce the length of duct as much as possible.
- Reduce the number of bends as much as possible. (Corner R should be as larger as possible.)
- Use a band. etc. to connect the main unit and the blowout duct flange.
- Conduct the duct installation work before finishing the ceiling.
Connection of suction, exhaust ducts
a. Fresh air inlet
- Inlet can be selected from the side or rear faces depending on the working conditions.
- Use the rear fresh air inlet when the simultaneous intake and exhaust is conducted. (Side inlet cannot be used.)
b. Exhaust (Make sure to use also the suction.)
Use the side exhaust port.
Electrical wiring
WARNING
DANGER OF BODILY INJURY OR DEATH
- TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS.
- GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
Precautions for electrical wiring
- Electrical wiring work should be conducted only by authorized personnel.
- Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated grip on the ends of the wires.
- Use copper conductor only.
Selection of size of power supply and interconnecting wires
Select wire sizes and circuit protection from table below. (This table shows
20 m length wires with less than 2% voltage drop.)
Item⇒
Model ⇓| Phase| Circuit breaker| Power source wire size (minimum) (mm²)| Earth
leakage breaker
---|---|---|---|---
Switch breaker
(A)| Overcurrent
protector rated capacity (A)| Switch breaker (A)| Leak current (mA)
AD90S2SM3FA AD90S2SM4FA
AD105S2SM3FA AD105S2SM4FA AD125S2SM3FA AD125S2SM4FA AD125S2SM8FA AD140S2SM3FA
AD140S2SM4FA AD140S2SM8FA| 1| 40| 30| 60| 40| 30
POWER SUPPLY & INDOOR-OUTDOOR CONNECTION:
Make wiring to supply power to the outdoor unit, so that the power for the
indoor unit is supplied by outdoor unit terminal blocks.
Move and scrap the air conditioning
- When moving, to disassemble and re-install the air conditioning, please contact your dealer for technical support.
- In the composition material of air conditioning, the content of lead, mercury, hexavalent chromium, polybrominated biphenyls and polybrominated diphenyl ethers are not more than 0.1% (mass fraction) and cadmium is not more than 0.01% (mass fraction).
- Please recycle the refrigerant before scrapping, moving, setting and repairing the air conditioning; for the air conditioning scrapping, should be dealt with by the qualified enterprises.
Address:Haier Industrial Park,Qianwangang Road,
Eco-Tech Development Zone,Qingdao 266555,Shandong,P.R.C.
Contacts: TEL +86-532-88936943; FAX +86-532-8893-6999
Website: www.haier.com