NOVUS NP620 Pressure Transmitters User Guide
- June 9, 2024
- Novus
Table of Contents
NOVUS NP620 Pressure Transmitters
PRESENTATION
NP620 positive relative pressure transmitter are robust and reliable devices suitable for industrial applications. Its great differential lies in the fact that it is possible to set its operating range easily and quickly. With the aid of software, you have access to various information about the transmitter and can define the most suitable configuration for your process.
PRECAUTION
Before operating the transmitter, you should carefully read the specifications
and instructions for use. In case of damage caused by incorrect operation or
misuse, the warranty becomes null and void. The installation must be carried
out by a specialized professional.
The power supply to the electronic instruments must come from a proper
instrumentation network.
UNPACKING
After unpacking, besides the transmitter, you should find:
- An installation and operation guide.
- A sealed electrical connector.
- A screw to attach the connector to the transmitter.
IDENTIFICATION
The identification label is attached to the body of the transmitter. On this
label, you will find information that allows you to recognize the device.
The figure below shows the identification label and details its information:
Figure 1 – Transmitter identification
MADE IN BRAZIL
www.novusautomation.com
SPECIFICATIONS
Reference Conditions:
Environment 23 °C ± 3 °C, 24 V supply, 250 Ω load. Vertical position (pressure connection down). Atmospheric pressure: 1015 ± 30 mbar.
Measure Type:
≤ 10 bar: Positive relative pressure.
≥ 16 bar: Sealed relative pressure with 1 bar reference pressure
*Maximum Range (Max. Range) ():**
Table 1 – Maximum measurement ranges
Measurement Ranges | Over Pressure | Burst Pressure |
---|---|---|
0.1 MPa (1 bar / 14.50 psi) | 2 times the value of the maximum measurement | |
range | 5 times the upper value of the measurement range |
0.4 MPa (4 bar / 58.02 psi)
1 MPa (10 bar / 145.04 psi)
1.6 MPa (16 bar/ 232.06 psi)
2.5 MPa (25 bar / 362.59 psi)
4 MPa (40 bar / 580.15 psi)| 4 times the upper value of the measurement range
6 MPa (60 bar / 870.20 psi )
10 MPa (100 bar / 1450.38 psi)
16 MPa (160 bar / 2320.60 psi)
25 MPa (250 bar / 3625.94 psi)| 1.5 times the value of the maximum measurement
range| 3 times the upper value of the measurement range
40 MPa (400 bar / 5801.51 psi)
(*) Information available on the product identification label.
Rangeability:
3:1, set by software.
Measurement Accuracy:
< ±0.25 % of the maximum range (Max. Range)
Including linearity, hysteresis, and repeatability under reference conditions.
Attention: For ranges with sealed relative measurement, errors proportional to the ambient pressure may occur when the altitude is different from sea level. You can easily compensate for these errors by using the Zero Offset function.
Long-term Stability: < ± 0,3 % of the maximum range / year
Durability: > 10 million cycles
Thermal Maximum Deviation: < ±0.05 % Max. Range / °C
Including zero deviations and span.
Mounting Position Influence: < 0.001% of the maximum range / °C
Output Signal (Output):
Electric current, 4-20 mA, 2 wires.
Meets NAMUR NE-43 recommendation.
Maximum current: < 21.5 mA.
Resolution: < 0.02 % of the maximum range
Power Supply (Power): 11 to 33 Vdc
Internal protection against reversal polarity of voltage supply.
Maximum Load (RL): RL = (Vcc – 11) / 20 mA (Ω)
Where: Vcc = Voltage supply
Protection Degree: IP65
Electrical Connection: Connector for Type A valves (DIN EN 175301-803), IP65. Conductor 1.5 mm² (max.) and cables between 6 and 8 mm in diameter.
Operating temperature: -20 to 70 °C / -4 to 158 °F
Medium Temperature: -20 to 100 °C / -4 to 212 °F
Storage Temperature: -40 to 100 °C / -40 to 212 °F
Dynamic Response: < 30 ms
Process Conection (Thread): ¼ NPT; ½ NPT; ½ BSP, G ¼ (*)
Sensor features: Polysilicon Piezoresistive (silicone oil filled)
Metal housing of the transmitter: Stainless 316
Wetted parts: Sensor, stainless steel 316
Sealing ring, FKM
Metal connection, stainless steel 316
Compatibility: Any gas or liquid compatible with the constituent materials of the wetted parts.
Certifications: CE, UKCA
ELECTRICAL CONNECTIONS
Figure 2 – Electrical Connections
Installation Recommendations
- Input signal conductors should run through the plant separately from output and supply conductors. If possible, in grounded conduits.
- The electronic instruments power supply must come from a proper instrumentation network.
- It is mandatory the use of RC FILTERS (electrical noise suppressors) in contactor coils, solenoids, etc.
- To improve the stability, immunity, and safety of the measurement, it is recommended to use the system grounding.
CONFIGURATION
To configure it, use the Transmitter Configuration Kit. This kit includes the TxConfig-II software, distributed free of charge on NOVUS website, and the TxConfig-USB-DIN43650 interface, which can be purchased in our distribution and reseller network. To install the TxConfig-II software, run the setup file TxConfigIISetup.exe and follow the installer instructions. The TxConfig interface must be connected to the transmitter, as shown in the figure below. The interface provides the power supply necessary for the transmitter configuration operation.
Figure 3 – TxConfig-USB connection
SOFTWARE CONFIGURATION
Figure 4 – TxConfig II software main screen
When you run the TxConfig-II software, it will automatically recognize the transmitter and will display the following fields:
-
General Information:
This field contains data that identifies the transmitter. For consultation, this information should be submitted to the manufacturer. -
Unit:
Definition of the pressure unit adopted in the measurement range definition fields. -
Measurement Range:
Definition of the measurement range adopted by the transmitter.
Lower Limit: Target pressure value for 4 mA current.
Upper Limit : Target pressure value for 20 mA current.
Minimum Range: is not possible to set a span lower than the Minimum Range value indicated below in this same field. -
Sensor Failure : Establishes the behavior of the current output when the transmitter malfunctions:
Minimum: Output current goes to < 4 mA.
Maximum: Output current goes to > 20 mA. -
Zero Offset: When no pressure is applied, corrects for small deviations in the transmitter output current.
-
Send Configuration: Sends the configuration made. Once sent, the configuration will be immediately adopted by the transmitter.
-
Read Configuration: Reads the transmitter setup. The screen will display the current setting, which you can change.
DIMENSIONS
Figure 5 – Transmitter dimensions ()
**
Table 2 – Dimensions
THREAD | A (mm) | B (mm) | WEIGHT (g) |
---|---|---|---|
NPT ¼ | 15.5 | 58.7 | 132 |
NPT ½ | 20.0 | 63.2 | 166 |
BSP ½ | 14.0 | 57.2 | 145 |
G ¼ | 14.0 | 57.2 | 129 |
(**) Previous versions (2020) have other measurements.