SmartCell Sounder and Wall Beacon Installation Guide
- June 8, 2024
- smartcell
Table of Contents
- SmartCell Sounder and Wall Beacon
- Part number
- Product description
- Pre installation
- Components
- Remove mounting plate
- Fix mounting plate
- Fit batteries
- Configuration
- Optional device locking
- Completing the installation
- Device unlocking
- Specification
- Regulatory information
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SmartCell Sounder and Wall Beacon
Part number
SC-32-0110-0001-99 SC-32-0120-0001-99 SC-32-0210-0001-99 SC-32-0220-0001-99
Product description
- SmartCell RED Sounder and Wall Beacon (VAD RED Flash)
- SmartCell RED Sounder and Wall Beacon (VAD WHITE Flash)
- SmartCell WHITE Sounder and Wall Beacon (VAD RED Flash)
- SmartCell WHITE Sounder and Wall Beacon (VAD WHITE Flash)
Pre installation
- Installation must conform to applicable local installation codes and should only be installed by a fully trained competent person.
- The use of a non-metallic spacer should be considered if mounting the device on to a metal surface.
- This device contains electronics that may be susceptible to damage from Electrostatic Discharge (ESD). Take appropriate precautions when handling electronic boards.
- This device is suitable for wall mounting only. Ceiling mounted variants are also available.
- To ensure correct operation, products must be used within the specified environmental operating conditions.
Components
- Sounder and wall beacon
- Mounting plate
- Batteries (not included in some regions*)
When batteries are not supplied, only fit specified batteries.
Remove mounting plate
- Remove the mounting plate by turning the device ANTICLOCKWISE, to release it from the mounting plate.
Fix mounting plate
- When fixing to the wall, all four fixing positions should be used to ensure a firm fixing.
- Where existing electrical mounting boxes are present, two fixing positions may be used.
- Use suitable fasteners and fixings.
- Observe the orientation marking!
Fit batteries
- When fitting / replacing batteries, observe correct polarity, using only specified batteries.
Configuration
The device must now be added (programmed) to the control panel.
- Refer to the programming manual for full programming details.
- SmartCell panel = TSD155
- SmartCell WZM = MK067
Optional device locking
- The device includes an optional locking mechanism.
- Remove the thin section of plastic shown below.
- Once locked, the Allen key will be required to unlock the device.
Completing the installation
- Reassemble the device as shown below.
Device unlocking
- If the device has been locked, an Allen key will be required for unlocking.
- Depress the locking mechanism, by inserting the Allen key, or similar, into the device’s cavity and pushing (A).
- Simultaneously twist the device anti-clockwise to release (B).
IMPORTANT
- The device should be tested upon installation, in accordance with local requirements.
- Testing should only be carried out by a fully trained competent person.
Specification
- Operating temperature -10 to +55 °C
- Storage temperature
- With batteries -10 to +30 °C
- Without batteries -10 to +55 °C
- Humidity 0 to 95% noncondensing
- Location Type B: for indoor/outdoor use
- IP rating IP33
- Supply 3 x ER14505M 3.6 V lithium thionyl chloride batteries (Fanso or Titus)
CAUTION!
-
This is a life safety product. Only use manufacturer-approved battery types. Failure to do so may result in damage to the product.
-
DO NOT mix batteries of different type or age.
-
When replacing batteries; remove all old batteries before fitting replacements.
-
Operating voltage 2.7 to 3.65 VDC
-
Current consumption 0.32 A max.
-
Power consumption 0.8 W max.
-
Operating frequency 868 MHz
-
Output transmitter power 14 dBm / 25 mW
-
Signalling protocol X5
-
Beacon flash rate 0.5 Hz (1 flash, every 2 seconds)
-
Beacon coverage W-2.4-6 (WHITE flash) / W-3-5.11 (RED flash)
-
Sounder output 95 dB(A) at 1m max.
For full sounder output information, refer to the Sounder Data doc (MK103). -
Dimensions (Ø x D) 110 x 77 mm
Regulatory information
References