SMARTCELL SC-33-0110-0001-99 Sounder and Ceiling Beacon Installation Guide
- June 8, 2024
- smartcell
Table of Contents
- SMARTCELL SC-33-0110-0001-99 Sounder and Ceiling Beacon
- Part number
- Product Description
- Pre-installation
- Components
- Remove mounting plate
- Fix mounting plate
- Fit batteries
- Configuration
- Optional device locking
- Completing the installation
- Device unlocking
- Specification
- Regulatory information
- Documents / Resources
SMARTCELL SC-33-0110-0001-99 Sounder and Ceiling Beacon
Part number
- SC-33-0110-0001-99
- SC-33-0120-0001-99
- SC-33-0210-0001-99
- SC-33-0220-0001-99
Product Description
- SmartCell RED Sounder and Ceiling Beacon (VAD RED Flash)
- SmartCell RED Sounder and Ceiling Beacon (VAD WHITE Flash)
- SmartCell WHITE Sounder and Ceiling Beacon (VAD RED Flash)
- SmartCell WHITE Sounder and Ceiling Beacon (VAD WHITE Flash)
Pre-installation
- Installation must conform to applicable local installation codes and should only be installed by a fully trained competent person.
- This device contains electronics that may be susceptible to damage from Electrostatic Discharge (ESD). Take appropriate precautions when handling electronic boards.
- The use of a non-metallic spacer should be considered if mounting the device on to a metal surface.
- This device is suitable for ceiling mounting only. Wall-mounted variants are also available.
- To ensure correct operation, products must be used within the specified environmental operating conditions.
Components
- Sounder and ceiling beacon
- Mounting plate
- Batteries (not included in some regions*)
- When batteries are not supplied, only fit specified batteries.
Remove mounting plate
- Remove the mounting plate by turning the device ANTICLOCKWISE, to release it from the mounting plate.
Fix mounting plate
- When fixing to the ceiling, all four fixing positions should be used to ensure a firm fixing.
- Where existing electrical mounting boxes are present, two fixing positions may be used.
- Use suitable fasteners and fixings.
Fit batteries
- When fitting/replacing batteries, observe correct polarity, using only specified batteries.
Configuration
- The device must now be added (programmed) to the control panel.
Optional device locking
- The device includes an optional locking mechanism.
- Remove the thin section of plastic shown below.
- Once locked, the Allen key will be required to unlock the device.
Completing the installation
- Reassemble the device as shown below.
Device unlocking
- If the device has been locked, an Allen key will be required for unlocking.
- Depress the locking mechanism, by inserting the Allen key, or similar, into the device’s cavity and pushing (A).
- Simultaneously twist the device anti-clockwise to release (B).
IMPORTANT
- The device should be tested upon installation, in accordance with local requirements.
- Testing should only be carried out by a fully trained competent person.
Specification
- Operating temperature -10 to +55 °C
- Storage temperature
- With batteries -10 to +30 °C
- Without batteries -10 to +55 °C
- Humidity 0 to 95% noncondensing
- Location Type B: for indoor/outdoor use
- IP rating IP33
- Supply 3 x ER14505M 3.6 V lithium thionyl chloride batteries (Fanso or Titus)
CAUTION!
- This is a life safety product. Only use manufacturer approved battery types. Failure to do so may result in damage to the product.
- DO NOT mix batteries of different type or age.
- When replacing batteries; remove all old batteries before fitting replacements.
- Operating voltage 2.7 to 3.65 VDC
- Current consumption 0.32 A max.
- Power consumption 0.8 W max.
- Operating frequency 868 MHz
- Output transmitter power 14 dBm / 25 mW
- Signaling protocol X5
- Flash Rate 0.5 Hz (1 flash, every 2 seconds)
- Beacon coverage C-3-12 (WHITE flash) / C-3-9.5 (RED flash)
- Sounder output 92 dB(A) at 1 m max.
- For full sounder output information, refer to the Sounder Data doc (MK103).
- Dimensions (Ø x D) 110 x 79 mm
Regulatory information
-
Manufacturer Carrier Manufacturing Polska Sp. Z o.o. Ul. Kolejowa 24. 39-100 Ropczyce, Poland
-
Year of manufacture See device serial number label
-
Certification
-
Certification body
-
CPR DoP 0359-CPR-00428
-
Approved to EN54-3: 2001. Incorporating amendments nos. 1 and 2.
-
Fire detection and fire alarm systems.
-
Part 3: fire alarm devices – sounders.
-
EN54-13: 2005. Fire detection and fire alarm systems.
-
Part 13: compatibility assessment of system components.
-
EN54-23: 2010. Fire detection and fire alarm systems.
-
Part 23: fire alarm devices. Visual alarm devices.
-
EN54-25: 2008. Incorporating corrigenda September 2010 and march 2012. Fire detection and fire alarm systems.
-
Part 25: components using radio links.
European Union -
EMS declares that the radio equipment type directives SmartCell Sounder & Ceiling Beacon is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet address: www.mysmartcell.com 2012/19/EC (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see www.recyclethis.info
-
Dispose of your batteries in an environmentally friendly manner according to your local regulations.
-
TSD108-0001-99 (Issue 4) 25/08/2021 AJM
Documents / Resources
|
SMARTCELL SC-33-0110-0001-99 Sounder and Ceiling
Beacon
[pdf] Installation Guide
SC-33-0110-0001-99 Sounder and Ceiling Beacon, SC-33-0110-0001-99, Sounder and
Ceiling Beacon, Ceiling Beacon
---|---