IMI SENSORS 628F01 Precision Quartz Industrial ICP Accelerometer
Repair and Maintenance
PCB guarantees Total Customer Satisfaction through its “Lifetime Warranty
Plus” on all Platinum Stock Products sold by PCB and through its limited
warranties on all other PCB Stock, Standard and Special products.
Due to the sophisticated nature of our sensors and associated instrumentation,
field servicing and repair is not recommended and, if attempted, will void the
factory warranty.
Beyond routine calibration and battery replacements where applicable, our
products require no user maintenance.
Clean electrical connectors, housings, and mounting surfaces with solutions
and techniques that will not harm the material of construction.
Observe caution when using liquids near devices that are not hermetically
sealed. Such devices should only be wiped with a dampened cloth—never
saturated or submerged.
In the event that equipment becomes damaged or ceases to operate, our
Application Engineers are here to support your troubleshooting efforts 24
hours a day, 7 days a week. Call or email with model and serial number as well
as a brief description of the problem.
Calibration
Routine calibration of sensors and associated instrumentation is necessary to
maintain measurement accuracy. We recommend calibrating on an annual basis,
after exposure to any extreme environmental influence, or prior to any
critical test.
PCB Piezotronics is an ISO-9001 certified company whose calibration services
are accredited by A2LA to ISO/IEC 17025, with full traceability to SI through
N.I.S.T. In addition to our standard calibration services, we also offer
specialized tests, including: sensitivity at elevated or cryogenic
temperatures, phase response, extended high or low frequency response,
extended range, leak testing, hydrostatic pressure testing, and others. For
more information, contact your local PCB Piezotronics distributor, sales
representative, or factory customer service representative.
Returning Equipment
If factory repair is required, our representatives will provide you with a Return Material Authorization (RMA) number, which we use to reference any information you have already provided and expedite the repair process. This number should be clearly marked on the outside of all returned package(s) and on any packing list(s) accompanying the shipment.
Contact Information
- PCB Piezotronics, Inc.
- 3425 Walden Ave.
- Depew, NY14043 USA
- Toll-free: 800-828-8840
- 24-hour SensorLine: 716-684-0001
- General inquiries: info@pcb.com
- Repair inquiries: rma@pcb.com
For a complete list of distributors, global offices and sales representatives, visit our website, www.pcb.com.
Safety Considerations
This product is intended for use by qualified personnel who recognize shock hazards and are familiar with the precautions required to avoid injury. While our equipment is designed with user safety in mind, the protection provided by the equipment may be impaired if equipment is used in a manner not specified by this manual.
Discontinue use and contact our 24-Hour Sensorline if:
- Assistance is needed to safely operate equipment
- Damage is visible or suspected
- Equipment fails or malfunctions
For complete equipment ratings, refer to the enclosed specification sheet for your product.
Definition of Terms and Symbols
The following symbols may be used in this manual:
-
DANGER
Indicates an immediate hazardous situation, which, if not avoided, may result in death or serious injury. -
CAUTION
Refers to hazards that could damage the instrument. -
NOTE
Indicates tips, recommendations and important information. The notes simplify processes and contain additional information on particular operating steps.
The following symbols may be found on the equipment described in this manual:
- This symbol on the unit indicates that high voltage may be present. Use standard safety precautions to avoid personal contact with this voltage.
- This symbol on the unit indicates that the user should refer to the operating instructions located in the manual.
- This symbol indicates safety, earth ground.
PCB Industrial Monitoring and Measuring Equipment – China RoHS 2 Disclosure Table
Component Name | Hazardous Substances |
---|---|
Lead (Pb) | Mercury (Hg) |
(Cr(VI))** | Polybrominated Biphenyls (PBB) |
Diphenyl Ethers (PBDE)
Housing| O| O| O| O| O| O
PCB Board| X| O| O| O| O| O
Electrical Connectors| O| O| O| O| O| O
Piezoelectric Crystals| X| O| O| O| O| O
Epoxy| O| O| O| O| O| O
Teflon| O| O| O| O| O| O
Electronics| O| O| O| O| O| O
Thick Film Substrate| O| O| X| O| O| O
Wires| O| O| O| O| O| O
Cables| X| O| O| O| O| O
Plastic| O| O| O| O| O| O
Solder| X| O| O| O| O| O
Copper Alloy/Brass| X| O| O| O| O| O
This table is prepared in accordance with the provisions of SJ/T 11364.
O: Indicates that said hazardous substance contained in all of the homogeneous
materials for this part is below the limit requirement of GB/T 26572.
X: Indicates that said hazardous substance contained in at least one of the
homogeneous materials for this part is above the limit requirement of GB/T
26572.
Lead is present due to allowed exemption in Annex III or Annex IV of the
European RoHS Directive 2011/65/EU.
Piezoelectric ICP® Accelerometers Operating Guide
Operating Guide with Enclosed Warranty Information
- 3424 Walden Avenue, Depew, New York 14043-2495
- Phone 716-684-0003
- Fax 716-684-3823
- Toll Free Line 1-800-959-4IMI
MANUAL NUMBER: 18405
MANUAL REVISION: A
ECN NUMBER: 49766
General
OPERATING GUIDE
for use with
PIEZOELECTRIC ICP® ACCELEROMETERS SPECIFICATION SHEET, INSTALLATION DRAWING
AND CALIBRATION INFORMATION ENCLOSED IMI ASSUMES NO RESPONSIBILITY FOR DAMAGE
CAUSED TO THIS PRODUCT AS A RESULT OF PROCEDURES THAT ARE INCONSISTENT WITH
THIS OPERATING GUIDE
INTRODUCTION
Congratulations on the purchase of a quality ICP® industrial sensor. In order
to ensure the highest level of performance for this product, it is imperative
that you properly familiarize yourself with the correct mounting and
installation techniques before attempting to operate this device. If, after
reading this manual, you have any additional questions concerning this sensor
or its application, feel free to call an Application Engineer at
716-684-0003 or
800-959-4464.
Proper sensor selection requires special attention to three main areas: sensor
design, dynamic expectations, and application environment.
Sensor design encompasses the actual sensing element, the physical material,
and component selection for the sensor. Preferred industrial accelerometers
employ a shear sensing element with either a quartz or ceramic crystal.
Quartz sensing elements are typically used when long-term stability and
minimum output shifts due to temperature changes are desired. Ceramic sensing
elements provide excellent resolution and durability in noisy environments,
and can be designed to supply low-frequency and high-frequency measurements.
Shear-design sensors are preferred because of their inherent insensitivity to
adverse environmental influences, such as case or base strain and thermal
transients. Internal case isolation and shielding is important in avoiding
erroneous signals resulting from ground loops and pick-up of electromagnetic
and radio frequency interference. Other critical material selection criteria
include non-magnetic stainless steel housing, hermetic sealing, and industrial
military connectors. See Figure 1.
Dynamic expectations are application-specific and refer to the frequency range
of measurement and the anticipated amplitudes of vibration. After careful
review of the machinery to be monitored, minimum and maximum measurement
frequency ranges may be established. The minimum measurement frequency is
normally related to any sub-harmonics of running speed or any lower
frequencies where vibration data is to be collected. The maximum measurement
frequency of interest is determined by the maximum number of harmonics of an
event like running speed, bearing frequencies, or gear mesh. This measurement
frequency range should be well within the specified frequency range of the
sensor.
Amplitude range refers to the anticipated levels of vibration to be measured.
These values are related to the alarm levels set for the machine. By carefully
evaluating the idiosyncrasies of the machinery, the predictive maintenance
engineer can estimate the minimum expected vibration levels and ensure that
the electrical noise floor of the accelerometer is less than those levels.
The environment of the application is a critical consideration during program implementation. The sensor chosen must be capable of surviving the wide range of conditions to which it is subjected; therefore, take time to evaluate potential conditions, such as high temperatures and chemical contaminants. The specified temperature range of the sensor must conform to the fluctuations of the environmental temperature. If harsh industrial chemicals are present, the sensor requires hermetic sealing and construction that resists corrosion. Finally, specific location of the sensor within the environment must be sensible, as both cable and sensor may be damaged by imprudent installation in heavily traveled, physically punishing areas.
ICP® ACCELEROMETERS
Enclosed in the back of this guide is a Specification Sheet, which lists the
complete performance characteristics of the particular sensor.
All ICP® sensors require a constant current power source for proper operation.
A typical sensing system includes an ICP® sensor, ordinary two conductor cable
and a basic constant current power supply (as shown in Figure 2).
The signal conditioner consists of a well-regulated 18 to 30 VDC source
(battery or line-powered), a current-regulating diode (or equivalent constant
current circuit), and a capacitor for decoupling (removing the bias voltage)
the signal.
The current-regulating device is used in place of a resistor for several
reasons. The very high dynamic resistance of the diode yields a source
follower gain which is extremely close to unity and independent of input
voltage. Also, the diode can be changed to supply higher currents for driving
long cable lengths. Constant current diodes, as shown in Figure 3, should be
used in ICP® signal conditioners. (The correct orientation of the diode within
the circuit is critical for proper operation.) Except for special models,
standard ICP® sensors require a minimum of 2 mA for proper operation.
The typical limits for this type of diode are to a 4 mA maximum rating;
however, several diodes can be placed in parallel for higher current levels.
All line-powered signal conditioners should use higher capacity (up to 20 mA)
constant current circuits in place of the diodes, particularly when driving
long signal cables (see Section 5).
Decoupling of the data signal occurs at the output stage of the signal
conditioner. A 10 to 30 µF capacitor coupled with a resistor shifts the signal
level to essentially eliminate the sensor bias voltage. The result is a drift-
free AC mode of operation.
OPTIONAL FEATURES
In addition to standard features, a variety of options are also available. When listed before the model number, the following prefix letters indicate that the sensor is manufactured or supplied with optional features:
- CS – Canadian Standards Association Approved Sensor
- D – Dummy, non-working sensor for display purposes EX – Cenelec Approved Sensor
- FM – Factory Mutual Approval Sensor
- HT – High temperature accelerometer (325 ˚F)
- LB – Low Bias electronics
- LC – Limited Calibration (one point calibration)
- LP – Low Pass filter
- M – Metric mounting hardware and cable length
- U – Usable demonstration sensor (does not meet one of more minor specifications)
- VO – Velocity Output Sensors
- MS – Mine Safety Approved Sensors
- TO – Temperature Output Sensor
Note: Not all sensors are available with the optional prefixes. Contact the factory to discuss special features that may be needed.
INSTALLATION OVERVIEW
When choosing a mounting method, consider closely both the advantages and
disadvantages of each technique. Characteristics like location, ruggedness,
amplitude range, accessibility, temperature, and portability are extremely
critical. However, the most important and often overlooked consideration is
the effect the mounting technique has on the high-frequency operating range of
the accelerometer.
Shown in Figure 4 are six possible mounting techniques and their effects on
the performance of a typical piezoelectric accelerometer. (Note: Not all of
the mounting methods may apply to your particular sensor.) The mounting
configurations and corresponding graph demonstrate how the high-frequency
response of the accelerometer may be compromised as mass is added to the
system and/or the mounting stiffness is reduced.
Note: The low-frequency response is unaffected by the mounting technique. This
roll-off behavior is typically fixed by the sensor’s built-in electronics.
However, when operating AC-coupled signal conditioners with readout devices
having an input impedance of less than one megaohm, the low frequency range
may be affected.
STANDARD STUD MOUNT
This mounting technique requires smooth, flat contact surfaces for proper
operation and is recommended for permanent and/or secure installations. Stud
mounting is also recommended when testing at high frequencies.
Note: Do NOT attempt mounting on curved, rough, or uneven surfaces, as
the potential for misalignment and limited contact surface may significantly
reduce the sensor’s upper operating frequency range.
STEP 1: First, prepare a smooth, flat mounting surface and then drill and
tap a mounting hole in the center of this area as shown in Figure 5.
A precision-machined mounting surface with a minimum finish of 63 µin (0.0016
mm) is recommended. (If it is not possible to properly prepare the machine
surface, consider using an adhesive mounting pad as a possible alternative.)
Inspect the area, checking that there are no burrs or other foreign particles
interfering with the contact surface.
STEP 2: Wipe clean the mounting surface and spread on a light film of grease,
oil, or similar coupling fluid prior to installation. See Figure 6.
Adding a coupling fluid improves vibration transmissibility by filling small
voids in the mounting surface and increasing the mounting stiffness. For semi-
permanent mounting, substitute epoxy or another type of adhesive.
STEP 3: Hand-tighten the sensor/mounting stud to the machine, then secure the
sensor with a torque wrench to the mounting surface by applying the
recommended mounting torque. (See enclosed specification data sheet for proper
mounting torque.)
It is important to use a torque wrench during this step. Under-torqueing the
sensor may not adequately couple the device; over-torqueing may result in stud
failure and possibly permanent damage.
ADHESIVE MOUNT
Adhesive mounting is often used for temporary installation or when the machine
surface cannot be adequately prepared for stud mounting. Adhesives like hot
glue or wax work well for temporary mounts; two-part epoxies and quick-bonding
gels provide a more permanent mount.
Note: Adhesively-mounted sensors often exhibit a reduction in high-
frequency range. Generally, smooth surfaces and stiff adhesives provide the
best frequency response. Contact the factory for recommended epoxies.
METHOD 1 – Adhesive mounting base
This method involves attaching a base to the machine surface, then securing
the sensor to the base. This allows for easy removal of the accelerometer.
- STEP 1: Prepare a smooth, flat mounting surface. A minimum surface finish of 63 µin (0.0016 mm) generally works best.
- STEP 2: Stud-mount the sensor to the appropriate adhesive mounting base according to the guidelines set forth in STEPS 2 and 3 of the Stud Mount Procedure.
- STEP 3: Place a small portion of adhesive on the underside of the mounting base. Firmly press down on the assembly to displace any extra adhesive remaining under the base. See Figure 7.
METHOD 2 – Direct Adhesive Mount
For restrictions of space or for convenience, most sensors (with the exception
of integral stud models) can be adhesive-mounted directly to the machine
surface.
- STEP 1: Prepare a smooth, flat mounting surface. A minimum surface finish of 63 µin (0.0016 mm) generally works best.
- STEP 2: Place a small portion of adhesive on the underside of the sensor. Firmly press down on the top of the assembly to displace any adhesive. Be aware that excessive amounts of adhesive can make sensor removal difficult. See Figure 8.
MAGNETIC MOUNT
Magnetic mounting provides a convenient means for making portable measurements
and is commonly used for machinery monitoring and other portable or trending
applications.
Note: The correct magnet choice and an adequately prepared mounting
surface are critical for obtaining reliable measurements, especially at high
frequencies. Poor installations can cause as much as a 50% drop in the sensor
frequency range.
Not every magnet is suitable for all applications. For example, rare earth
magnets are commonly used because of their high strength. Flat magnets work
well on smooth, flat surfaces, while dual-rail magnets are required for curved
surfaces. In the case of non-magnetic or rough surfaces, it is recommended
that the user first weld, epoxy, or otherwise adhere a steel mounting pad to
the test surface. This provides a smooth and repeatable location for mounting.
- STEP 1: After choosing the correct magnet type, inspect the unit, verifying that the mounting surfaces are flat and smooth. See Figure 9.
- STEP 2: Stud-mount the accelerometer to the appropriate magnet according to the guidelines set forth in STEPS 2 and 3 of the Stud Mount Procedure.
- STEP 3: Prepare a smooth, flat mounting surface. A minimum surface finish of 63 µin (0.0016 mm) generally works best. After cleaning the surface and checking for burrs, wipe on a light film of silicone grease, machine oil, or similar-type coupling fluid.
- STEP 4: Mount the magnet/sensor assembly to the prepared test surface by gently “rocking” or “sliding” it into place. See Figure 10.
Note: Magnetically mounting accelerometers carelessly has the potential to generate very high (and very damaging) g levels. To prevent damage, install the assembly gently. If unsure, please contact the factory for assistance.
HANDHELD OR PROVE TIP MOUNT
This method is NOT recommended for most applications. It is generally used where access to machinery may be a safety concern. Both the accuracy and repeatability at low (<5 Hz) and high frequency (>1 kHz) ranges are questionable.
CABLING
The selection of connectors and cables has a direct impact on the ruggedness
and reliability of the sensor installation.
A consideration when dealing with cables is the way in which the cable
conductors are terminated.
ICP® accelerometers are internally amplified, two-wire accelerometers.
Connections to the sensor require two leads: one for the power and signal, and
the other for the common and signal return. Often, coaxial cables are used
since only two conductors are needed. Coaxial cables are less expensive. With
coaxial cables, however, erroneous signals can be introduced into sensor
systems through ground loops, electromagnetic interference, or radio frequency
interference (EMI or RFI). To avoid ground loops, there should only be one
ground in the system.
It is recommended for permanent installations that the sensor be case-isolated and internally shielded with a dual-case design and use a two-conductor shielded cable to insure clean vibration signal transmission. Two-conductor shielded cables allow the signal and the signal return (common) to be fully shielded from the sensor to the readout equipment. To insure that ground loop signals are not induced, the shield should only be terminated at one end. Typically, the shield of a two-conductor shielded cable is left open or not connected at the sensor end and is tied to earth ground at the instrumentation end.
Operation over long cables may affect the frequency response of ICP® accelerometers, and introduce low frequency noise and high frequency distortion when an insufficient current is available to drive cable capacitance.
Unlike charge mode systems, where the system noise is a function of cable length, ICP® sensors provide a high voltage, low impedance output well-suited for driving long cables through harsh environments. While there is virtually no increase in noise with ICP® sensors, the capacitive loading of the longer cable may be distort or filter higher frequency signals depending on the supply current and the output impedance of the sensor.
Generally, this signal distortion is not a problem with lower frequency testing within a range up to 1,000 Hz. However, when monitoring higher frequency vibrations traveling over cables longer than 500ft, the possibility of signal distortion exists.
The maximum frequency that can be transmitted over a given cable length is a function of both the cable capacitance and the ratio of the peak signal voltage to the current available from the signal conditioner according to:
- Where, fmax = maximum frequency (hertz)
- C = cable capacitance (picofarads)
- V = maximum peak output from sensor (volts)
- Lc = constant current from signal conditioner (mA)
- 109 = scaling factor to equate units
Note that in this equation, 1 mA is subtracted from the total current supplied
to sensor (Lc).
This is done to compensate for powering the internal electronics. Also, note
that these are typical values only.
When driving long cables, Equation 1 shows that, as the length of the cable, peak voltage output or maximum frequency of interest increases, a greater constant current will be required to drive the signal.
The nomography on page 12 of this manual provides a simple, graphical method for obtaining the expected maximum frequency capability of an ICP® measurement system. The maximum peak signal voltage amplitude, cable capacitance and supplied constant current must be known or presumed.
For example, when running at 100 ft (30.5 m) cable with a capacitance of 30
pF/ft, the total capacitance is 3,000pF.
This value can be found along the diagonal cable capacitance lines. Assuming
the sensor operates at a maximum output range of 5 volts and the constant
current available from the power supply is 2 mA, the ratio on the vertical
axis can be calculated to equal 5.
The intersection of the total cable capacitance and this ratio result in a
maximum frequency of approximately 10.2 kHz.
The nomography does not indicate whether the frequency amplitude response at a point is flat, rising or falling. For precautionary reasons, it is good general practice to increase the constant current (if possible) to the sensor (within its maximum limit) so that the frequency determined from the nomography is approximately 1.5 to 2 times greater than the maximum frequency of interest.
Note: Higher current levels will deplete battery-powered signal conditioners at a faster rate. Also, any current not used by the cable goes directly to power the internal electronics and will create heat. This may cause the sensor to exceed its maximum temperature specification. For this reason, do not supply excessive current over short cable runs or when testing at elevated temperatures.
CABLE CONNECTOR PROCEDURE
Care and attention to installation is essential, as the reliability and accuracy of your system is no better than that of the output cable.
-
STEP 1: Ascertain that you have ordered the correct cable type.
As with sensors, no cable can satisfy all applications. Special low-noise cabling should be used with high impedance, charge-output devices. ICP® sensors usually operate with any ordinary tow-wire cable. Industrial applications often require twisted/shielded cables to reduce the effects of EMI and RFI. PTFE-jacketed cabling may be necessary to withstand corrosive environments. -
STEP 2: Connect the cable to the accelerometer. A small amount of thread-locking compound placed on the connector prior to attachment helps secure the cable during testing. In harsh environments, the connection can be sealed with silicone rubber, O-rings, and flexible heat-shrink tubing.
-
STEP 3: Plug the connector of the cable into the mating sensor connector. Then, holding the sensor stationary, secure the connector in place by tightening down the attached threaded cable sleeve.
-
STEP 4: Route the cable to the signal conditioner, making certain to stress-relieve the sensor/cable connection and minimize motion by clamping the cable at regular intervals.
Common sense should be used to avoid physical damage and minimize electrical noise. For instance, avoid routing cables near high-voltage wires. Do not route cables along floors or walkways where they be stepped on or become contaminated. Shielded cables should have the shield grounded at one end only, normally at the instrumentation end. -
STEP 5: Finally, connect the remaining cable end to the signal conditioner or readout device. To dissipate charge that may have accumulated in the cable short the signal to ground prior to attachment.
POWERING
All ICP® sensors require constant current excitation for proper operation.
For this reason only use approved constant-current sources. A typical system
schematic is shown in Figure 11.
The power supply consists of a regulated 18 to 30 VDC source. In general,
battery-powered devices offer versatility for portable, low-noise
measurements, whereas line-powered units provide the capability for continuous
monitoring.
This power is regulated by a current-limiting circuit, which provides the
constant-current excitation required for proper operation of sensors with
integral electronics.
Note: Under no circumstances should a voltage be supplied to an ICP® accelerometer without a current-regulating diode or equivalent electrical circuit.
A capacitor at the output stage of the device removes the sensor output bias voltage from the measurement signal. This provides a zero-based, AC-coupled output compatible with most standard readout devices.
Today, many FFT analyzers, data acquisition modules, and data collectors have constant-current excitation for direct use with ICP® sensors. However, before using this feature, check that the supply voltage and constant current are adequate for use with your sensor. Please contact the respective signal conditioner manufacturer or check the product manual for more information.
OPERATING
After completing the system setup, switch on the conditioner, the meter (or
LED) and allow the sensor to power up. If a faulty condition is monitored,
first check all system connections, then check the functionality of the cable
and signal conditioner. If the system still does not operate properly, consult
an IMI Application Engineer.
Note: Always operate the accelerometer within the limitations listed on
the Specification Sheet of your sensor. Operating the device outside of its
parameters can cause temporary or permanent damage to the sensor.
ACCELEROMETER CALIBRATION
Note: It is good measurement practice to verify the performance of each
accelerometer before and after each measurement.
Accelerometers are precision measuring instruments.
They are highly engineered to provide accurate electrical signals
representative of the vibration being monitored.
Each sensor is calibrated by comparison to a known acceleration level.
Some calibrations include frequency response curves, resonant frequency
measurements, transvers sensitivity, and many other valuable tests.
Applications requiring a high degree of accuracy or those in plants requiring
certification and traceability require full calibration test results.
Some applications have much less stringent requirements for calibration certification. Simple sensitivity measurements at a single frequency may be sufficient; operational verification and certificates of conformance to published specifications may satisfy many plants’ calibration needs. Reducing the final calibration requirements reduces the cost of manufacturing the sensor and should lower the price for predictive maintenance users.
Periodic recalibration may be required by plants with strict certification and traceability requirements. It is always recommended that the user has the sensor recalibrated periodically, particularly if the sensor has experienced a very high shock level or extreme temperatures for extended periods of time. Some plants develop in-house calibration capabilities for periodically verifying the performance of accelerometers. Products are available that provide a set 1 g-acceleration level at a fixed frequency for quick sensor checking.
For these reasons, it is recommended that a recalibration cycle be established for each accelerometer. This schedule is unique and is based on a variety of factors, such as extent of use, environmental conditions, accuracy requirements, trend information obtained from previous calibration records, contractual regulations, frequency of “cross-checking” against other equipment, manufacturer recommendation, and any risk associated with incorrect readings. International standards, such as ISO 10012-1, provide insight and suggested methods for determining recalibration intervals for most measuring equipment. With the above information in mind and under “normal” circumstances, a conservative suggestion of 12 to 24 month recalibration cycle for most piezoelectric accelerometers is advised.
SENSOR CALIBRATION
Accelerometer recalibration services are typically performed by IMI’s internal metrology laboratory. (Other international and private laboratories are also available.) The IMI laboratory is certified to ISO 9001, complies with ISO 10012-1 (and former MIL-STD-45662A), and uses equipment directly traceable to NIST. This assures an accurate calibration of relevant specifications.
The following includes a broad overview of the Back-to-Back Calibration technique normally used when calibrating accelerometers. This technique provides a quick and easy method for determining the sensitivity of a test accelerometer over a wide frequency range.
BACK-TO-BACK CALIBRATION THEORY
Back-to-back calibration is perhaps the most common method for determining the sensitivity of piezoelectric accelerometers. This method relies on a simple comparison to a previously calibrated accelerometer, typically referred to as a reference standard, as shown in Figure 12.
Figure 12. Reference Standard Accelerometer
These high-accuracy devices, which are directly traceable to a recognized standards laboratory, are designed for stability, as well as configured to accept a test accelerometer. By mounting a test accelerometer to the reference standard and then connecting this combination to a suitable vibration source, it is possible to vibrate both devices and compare the data as shown in Figure 13. (Test set-ups may be automated and vary, depending on the type and number for accelerometers being calibrated.)
Figure 13. Typical Back-to-Back Calibration System
Because the acceleration is the same on both sensors, the ratio of their
outputs (VT/VR) must also be the ratio of their sensitivities.
With the sensitivity of the reference standard (SR) known, the exact
sensitivity of the test sensor (ST) is easily calculated by using the
following equation:
By varying the frequency of the vibration, the sensor may be calibrated over its entire operating frequency range. The typical response of an unfiltered accelerometer is shown in Figure 14.
Figure 14. Typical Test Accelerometer Response
TROUBLESHOOTING
Piezoelectric sensors are dynamic measuring equipment. They use piezoelectric sensing elements to convert or transduce the mechanical phenomena to an electrical signal. The mechanical parameter may be force, pressure or vibration. The raw electrical signal from a piezoelectric charge element is a high impedance signal. This charge signal is normally converted to a low impedance voltage signal by either an external charge amplifier or an external voltage amplifier. The cables between the charge sensor and the amplifier must be high quality, low noise cable and must be kept as short as possible. Figure 15 shows a typical high impedance system.
Figure 15. High Impedance System Connection
Internally amplified sensors employ miniature amplifiers to convert the high impedance charge signal into a low impedance voltage signal. These amplifiers are internal to the sensor, and therefore, do not require low noise cables or external amplifiers. These amplifiers have set gain so that output sensitivities are standardized.
Figure 16. Sensor with Integral Electronics System Connector
ICP® sensors are two-wire sensors. They are powered with a constant current DC
source. The power supply is typically 18 to 30 volts DC current limited via a
constant current between 2 and 20 mA. Typical battery operated supplies offer
2mA of constant current to extend battery life while continuous monitoring
systems offer more current in order to drive longer cables. Figure 16 shows a
typical system for a sensor with integral electronics.
The signal output of a sensor with integral electronics is a low impedance
voltage signal proportional to the dynamic measurement such as force,
pressure, or vibration. This voltage signal is carried on a DC bias voltage.
The AC dynamic signal is superimposed on the DC bias voltage and is allowed to
swing between the supply voltage and ground as shown in Figure 17. Unlike an
operational amplifier that requires a plus and minus supply and allows the
signal to “ride” on ground and “swing” between the plus and minus “rails,” the
sensor with integral electronics requires the output signal to be DC biased.
Figure 17. Sensor DC Bias Voltage
This DC bias voltage is an excellent diagnostic tool. The voltage provides a
means of verifying that the amplifier is “turned on.” Typical input/output
power supplies will block this DC bias voltage at the output via a blocking
capacitor in order to AC couple the signal to readout devices. By “teeing” off
the input into a DC volt meter, as shown in Figure 18, the bias voltage can be
measured.
While measuring the supply voltage, the bias voltage can be measured agter the
sensor is plugged in. If the meter stays at supply, something in the system is
open or not connected. If the meter reads “0,” something in the system is
shorted. If the meter reads within the bias voltage range of the sensor, then
the sensor and cabling are functioning properly.
Figure 18. DC Bias Voltage Measurement
REPAIR/RETURN PROCEDURE
Because of the nature of most IMI instrumentation, field repair is typically
NOT recommended and may void any warranty. If factory service is required,
contact IMI for a RETURN MATERIAL AUTHORIZATION (RMA) number prior to sending
equipment to the factory. Please have information available, such as model and
serial number. Also, to insure efficient service, be sure to include a written
description of the symptoms and problems with the equipment to a local sales
representative or distributor, or contact IMI if none are located in your
area.
Customers outside the U.S. should consult their local IMI distributor for
information on returning equipment. For exceptions, please contact the
International Sales department at IMI to request shipping instructions and an
RMA. For assistance, please call
716-684-0003, or fax us at
716-684-3823. You may also receive
assistance via e-mail at imi@pcb.com or visit our
website at www.pcb.com.
CUSTOMER SERVICE/WARRANTY
IMI, a division of PCB Piezotronics, guarantees Total Customer Satisfaction.
If, at any time, for any reason, you are not completely satisfied with any IMI
product, IMI will repair, replace or exchange it at no charge. You may also
choose to have your purchase price refunded.
IMI instrumentation is warranted against defective material workmanship for 1
year unless otherwise expressly specified. Damage to instruments caused by
incorrect power or misapplication, is not covered by warranty. If there are
any questions regarding power, intended application, or general usage, please
consult with your local sales contact or distributor. Batteries or expendable
hardware items are not covered by warranty.
IMI offers to all customers, at no charge, 24-hour phone support. This service makes product or application support available to our customers, day or night, seven days a week. When unforeseen problems or emergency situations arise, call the IMI Hot Line at 716-684-0003, and an application specialist will assist you.
Model Number 66102ANZ1| ICP® LOW-PROFILE TO-5
ACCELEROMETER| Revision: B ECN #: 49711
---|---|---
Performance ENGLISH
SI
Sensitivity(± 20 %) 10 mV/g 1.02 mV/(m/s²) [6][1] Measurement
Range ± 500 g ± 5,000 m/s²
Frequency Range(± 3 dB) 0.5 to 10 kHz 0.5 to 10 kHz
[3][7] Resonant Frequency > 25 kHz > 25 kHz [7] Broadband
Resolution 0.0018 g rms 0.017658 m/s² rms [4] Non-Linearity
≤ 1 % ≤ 1 % [2] Transverse Sensitivity ≤ 7 % ≤ 7 %
Environmental
Overload Limit(Shock) 5,000 g pk 49k m/s² pk
Temperature Range(Operating) -65 to +185 °F -54 to +85 °C
Temperature Response See Graph See Graph [4] Electrical
Settling Time(within 1% of bias) ≤ 2 sec ≤ 2 sec
Discharge Time Constant ≥ 0.3 sec ≥ 0.3 secExcitation Voltage
18 to 28 VDC 18 to 28 VDC
Constant Current Excitation 2 to 20 mA 2 to 20 mA
Output Impedance < 100 Ohm < 100 Ohm
Output Bias Voltage 8 to 12 VDC 8 to 12 VDC
Spectral Noise(10 Hz) 19 µg/√Hz 186.4 (µm/sec2)/√Hz [4] Spectral
Noise(100 Hz) 8 µg/√Hz 78.5 (µm/sec2)/√Hz [4] Spectral Noise(1 kHz)
5 µg/√Hz 49.1 (µm/sec2)/√Hz [4] Physical
Size – Lip Diameter 0.36 in 9.1 mm
Size – Height 0.26 in 6.6 mm
Weight 0.08 oz 2.2 gm
Mounting
Adhesive/Solder
Adhesive/Solder Sensing Elemen Ceramic Ceramic
Sensing Geometry Shear Shear Housing Material
Stainless Steel
Stainless Steel
Sealing Welded Hermetic
Welded Hermetic
Electrical Connector Header Pins Header Pins
Electrical Connection Position
Bottom
Bottom Electrical Connections(Pin 1) Signal / Power
Signal / Power
Electrical Connections(Pin 2) Neg (-) Ground
Neg (-) Ground
Electrical Connections(Pin 3) No
Connection No Connection| OPTIONAL VERSIONS
Optional versions have identical specifications and accessories as listed for
the standard model except where noted below. More than one option may be used.
HT – High temperature, extends normal operation temperatures
Temperature Range
-65 to 250 °F
-54 to 121 °C
RH – RoHS Compliant
NOTES: [1] Conversion Factor 1g = 9.81 m/s². [2] Zero-based, least-
squares, straight line method. [3] The high frequency tolerance is accurate
within ±10% of the specified frequency. [4]Typical. [5]See PCB Declaration of
Conformance PS023 or PS060 for details. [6]Negative output along Z-axis (in
upward direction when pin mounted). [7]Performance depends on mounting
| SUPPLIED
ACCESSORIES:
Model ICS-2 NIST-traceable single-point amplitude response calibration at 6000 cpm (100 Hz) for each axis (1)
|
| Entered: LK| Engineer: YHK| Sales: MC| Approved: NJF| Spec Number:
| Date: 07/03/2019| Date: 07/03/2019| Date: 07/03/2019| Date: 07/03/2019|
47360
All specifications are at room temperature unless otherwise specified.
In the interest of constant product improvement, we reserve the right to
change specifications without notice. ICP® is a registered trademark of PCB
Piezotronics, Inc.| 3425 Walden Avenue, Depew, NY 14043| Phone:
800-959-4464
Fax: 716-684-3823
E-M ail:
imi@pcb.com
SIL Declaration of Conformity
Functional safety according to IEC 61508
Manufacturer:
- PCB Piezotronics
- 3425 Walden Avenue
- Depew, NY 14043 USA
PCB Piezotronics declares as manufactmer, that the industrial, qua11z or ceramic shear rep@ accelerometers:
- 621 Series – (XX)62 l yzzz/aaa
- 622 Series – (XX)622yzzz/aaa
- 623 Series – (XX)623yzzz/aaa
- 624 Series – (XX)624yzzz/aaa
- 625 Series – (XX)625yzzz/aaa
- 626 Series – (XX)626yzzz/aaa
- 627 Series – (XX)627yzzz/aaa
- 628 Series – (XX)628yzzz/aaa
(XX) Options include one or more of the following:
- EX – Approved for Hazardous Locations
- M – Metric Mounting Hardware
- TO- Dual Output (Vibration/Temperature)
- HT- High Temperature (325°F, 163°C)
- VO – Velocity Output
Note: “yzzz” completes the model, “aaa” indicates cable length (if applicable)
Is hardware suitable for use in safety-instrumented systems according to IEC 61508, if the safety instructions and the following parameters are observed:
Parameter | **62x Series*** | **EX, HT, TO, VO 62x Series*** |
---|---|---|
SIL | 2 | 2 |
Proof Test Interval (Annual) | 8,760 h | 8,760 h |
Device Type | B | B |
HFT | 0 | 0 |
SFF | 78.18% | 78.18% |
PFDAv1 | 7.99 X 10· 5 | 7.99 X 10″5 |
Adu X 10″6 | 0.018 | 0,018 |
SIL Capability (Low Demand Mode) | 2 | 2 |
SIL Capability (Continuous Demand Mode) | 2 | 2 |
MTTF2 | 75.11 y | 7y |
I. The values comply with SIL2 according to ISA S84.0 I
2. According to Siemens SN29500 and Proven In Use data
*With or without the M (metric) option
The PCB sensor hardware is suitable for inclusion in Safety Instrumented
Systems (SIS) that are designed using IEC 61511 (for the process industry
sector), IEC 62061 (safety of machinery), EN 50129 (railway applications), and
ISO 26262 (automotive industry).
those
Note: in The IEC use of 61508. SIL Hardware in specific safety standard
auRHfwt;,on may apply different number of sequences or definitions to J une 28
, 2019
Carrie Termin
Regulatory Affairs and Product Certification Specialist
PCB PIEZOTRONICS, INC. – CORPORATE HEADQUARTERS
3425 Walden Avenue, Depew, New York 14043-2495 USA _
Phone: 716-684-0001 Fax:
716-684-0987
E-mail: info@pcb.com
Web site: www.pcb.com
AS9100 and ISO9001 Certified
ISO17025 Accredited
INTERTEK ASSURANCE SAFETY INTEGRITY LEVEL SUMMARY REPORT
CLIENT NAME
PCB Piezotronlcs, Inc.
3425 Walden Ave
Depew, NY 14043-2417
REPORT NO
103685042CSLT-002
COMPILED BY
Ashton D. H inge, CFSP, PMP
PROJECT NAME
G103685042
DATE
22 February 2019
PCB FUNCTIONAL SAFETY SIL SUMMARY AND RESULTS
Summary
This report details the results of the reliability analysis performed on the
PCB Piezotronics ICP® Sensor model 62X series. Design changes from this
documentation package would need to be evaluated for the impact on the
reliability characteristics. These results are based on the following PCB
Piezotronics documentation.
- Electrical schematic 65009-NR
- Electrical schematic 65010-NR
- Electrical schematic 65038-NR
- 622801 MTTF Calculation
- 62X Returns FY 2018
Results
The reliability calculations were conducted at the component and circuit level
using the methodology outlined in MIL-HDKB-217F. Product level failure
parameters were then calculated in accordance with the functional safety
approach of IEC 6150? 1:2010, IEC 61508-2:2010, IEC 61508-6:2010, IEC
61508-7:2010. The results from the FMEA are given below for the ICP® Sensor
model 62X:
Type B components: 62X Series
The safety relevant parameter PFDavg Is in compliance with the corresponding
requirements for SIL 2 according to IEC 615081• If this sensor ls fully
defined as type B, then the SIL capability is SIL 1 because the SFF is 78.18
%. However, If this sensor is fully defined as type A, then the SIL capability
is SIL 2. According to IEC 61508-2 section 7.4.4.2.3 if the sensor has both
type A and type B, then SFF may fall below 90 % with HFT of “0” and can pe
considered to have SIL 2 capability. Even though PFDavg has the range of SIL
4, the hardware fault tolerance limits the capability to SIL 2. The user
should consider, that the hardware fault tolerance of all inspected devices is
zero and that a single fault can lead to a dangerous failure.
- Senior Consultant,
- Ashton Halnge, lntertek
- Certified Functional Safety Professional (CFSP)
The assessment results described in this report only refer to the safety-
related parameters PFD avg, HFT, and SFF according to IEC 61508.
This report does not make any statements, that the manufacturer meets all
other requirements of the above cited standards for hardware, software,
documentation, management of functional safety, verification, and validation.
This report does not imply that the examined pressure sensors have been
certified for functional safety by the assessor according to IEC 61508 or any
other standards.
The sensors are only one part of a complete. safety function. It is at the
responsibility of the end-user to prepare and to apply an extensive
reliability model, that brings out the complete safety function and that meets
all requirements of the claimed SIL level according to IEC 61508.
PCB SIL Sensor Rating
Report No: 103685042CSLT-002