Schneider Electric Easergy Sepam Series 80 User Guide

June 8, 2024
Schneider Electric

Schneider Electric Easergy Sepam Series 80

Safety instructions

Important notes

Restricted liability

Electrical equipment should be serviced and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this manual. This document is not intended as an instruction manual for untrained persons.

Device operation
The user is responsible for checking that the rated characteristics of the device are suitable for its application. The user is responsible for reading and following the device’s operating and installation instructions before attempting to commission or maintain it. Failure to follow these instructions can affect device operation and constitute a hazard for people and property.

Protective grounding
The user is responsible for compliance with all the existing international and national electrical codes concerning protective grounding of any device.

Safety symbols and messages
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install,  operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

Risk of electric shock

  • ANSI symbol.
  • IEC symbol.

The addition of either symbol to a “Danger” or “Warning” safety label on a device indicates that an electrical hazard exists, which will result in death or personal injury if the instructions are not followed.

Safety alert

This is the safety alert symbol. It is used to alert you to potential personal injury hazards and prompt you to consult the manual. Obey all safety instructions that follow this symbol in the manual to avoid possible injury or death.

Safety messages

  • DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
  • NOTICE is used to address practices not related to physical injury.

Precautions

Storage
Sepam may be stored in its original packaging in a closed sheltered location:

  • ambient temperature: -25 °C to +70 °C (or -13 °F to +160 °F) humidity y 90 %. Periodic checking of the environment and the packaging on a yearly basis is recommended.

Commissioning
Once installed, the Sepam must be energized as soon as possible, especially in a damp location (humidity u 90 %). Storing an unenergized and unpackaged Sepam for a long period may damage the unit.

Documentation

Quick Start

The Quick Start document supplied with each Sepam has two functions:

  • a concise installation and commissioning guide for OEMs
  • a reminder for operators.

It is advisable to keep it near Sepam. The certificate of conformity on the last page may be detached and kept with the installation documents.

Operation manual
Consult the operation manual (reference SEPED303003EN) for detailed information on the installation, use, commissioning and maintenance of Sepam series 80. These documents can be downloaded from www.schneider- electric.com

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • Turn off all power supplying the Sepam and the equipment in which it is installed before working on it.
  • Always use a properly rated voltage sensing device to confim that the power is off.
  • Replace all devices, doors, and covers before turning on the power to this equipment.
  • Before energizing the power equipment, replace all barriers and covers.
  • Apply appropriate personal protective equipment and follow safe electrical work practices. See local regulations.
  • This equipment must only be installed and serviced by qualified electrical personnel.

Failure to observe these instructions will result in death or serious injury.

Identification

Each Sepam is delivered in a separate package containing: b 1 Sepam series 80 base unit, with its memory cartridge and its battery in their locations and two connectors A and E tightened

  • 8 spring clips
  • 1 terminal block identification label
  • 2 keys (mimic-based UMI only)
  • 1 Quick Start and 1 certificate of compliance.

The other optional accessories such as modules, current input connectors and cords are delivered in separate packages. To identify a Sepam, inspect the 4 labels which are visible when the doo047r on the front panel is open:

  • 2 labels stuck on the base unit:
    • 1 label with base unit hardware reference stuck on the back of the door on the front panelSchneider-Electric-Easergy-Sepam-Series-80-fig-1
  • 2 labels stuck on the cartridge:Schneider-Electric-Easergy-Sepam-Series-80-fig-2

Reference of software downloaded in the cartridge:

  • application
  • working language

Dimensions

Base unit dimensions

Schneider-Electric-Easergy-Sepam-Series-80-fig-3

  • Side view of Sepam with MES120, flush-mounted in front panel with spring clips. Front panel: 1.5 mm to 6 mm (0.05 to 0.23 in) thick. Clearance for Sepam assembly and wiring.Schneider-Electric-Easergy-Sepam-Series-80-fig-4

Top view of Sepam with MES120, flush-mounted in front panel with spring clips. Front panel: 1.5 mm to 6 mm (0.05 to 0.23 in) thick.

Assembly with AMT880 mounting plateSchneider-Electric-Easergy-Sepam-
Series-80-fig-5

Top view of Sepam with MES120, flush-mounted in the front panel with spring clips. Mounting plate: 3 mm (0.11 in) thick.

Assembly

Spring clip mounting direction
The direction in which the spring clips are mounted depends on the thickness of the mounting frame. The top clips are mounted in the opposite direction to the bottom clips.

Base unit flush-mounting
Sepam series 80 is mounted on the mounting frame by 8 spring clips. The mounting surface must be flat and stiff to guarantee tightness.

DANGER

HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS

  • Only qualified personnel should install this equipment. Such work should be performed only after reading this entire set of instructions.
  • NEVER work alone.
  • Turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of back feeding.
  • Always use a properly rated voltage-sensing device to confirm that all power is off. Failure to follow these instructions will result in death or serious injury.Schneider-Electric-Easergy-Sepam-Series-80-fig-6

Installation of MES120 modules

Installation of a MES120, MES120G or MES120H module on the base unit

  • Insert the 2 pins on the MES module into the slot 1 on the base unit
  • Push the module flat up against the base unit to plug it into the connector H2
  • Partially tighten the two mounting screws 2 before locking them. MES120 modules must be mounted in the following order:
  • If only one module is required, connect it to connector H1
  • If 2 modules are required, connect them to connectors H1 and H2
  • If 3 modules are required (maximum configuration), the 3 connectors H1, H2, and H3 are used.

Note: the CCT640, CCA630, CCA634 and CCA671 connectors are removable and screw-lockable.

Installing the terminal block identification label
A sticker showing the rear panel of Sepam and terminal assignments is supplied with each base unit to facilitate the installation and connection of Sepam and the MES120 input-output modules. You may stick it in the location of your choice, e.g. on the side of a MES120 module or on the right-hand side panel of Sepam.Schneider-Electric-Easergy-Sepam-Series-80-fig-7 Schneider-Electric-Easergy-Sepam-
Series-80-fig-8

Description

  1. Base unit
  2. 8 fixing points for 4 spring clips
  3. Red LED: Sepam unavailable
  4. Green LED: Sepam on
  5. Gasket
    • 20-pin connector for:
    • 24 V DC to 250 V DC auxiliary supply
    • 5 relay outputs. Connector for 3 phase current I1, I2, I3 inputs
    • Sepam T87, M87, M88, G87, G88: a connector for 3-phase current I’1, I’2, I’3 inputs
    • Sepam B83: a connector for v 3 phase voltage V’1, V’2, V’3 inputs v 1 residual voltage V’0 input.
    • Sepam C86: a connector for capacitor unbalanced current inputs.
  6. Modbus communication port 1
  7. Modbus communication port 2
  8. Remote module connection port 1
  9. Remote module connection port 2 20-pin connector for:
    • 3 phase voltage V1, V2, V3 inputs
    • 1 residual voltage V0 input.
    • 2 residual current I0, I’0 inputs.
  10. Communication port 3 for ACE850 communication interfaces only
  11. Connector for 1st MES120 input/output module
  12. Connector for 2nd MES120 input/output module
  13. Connector for 3rd MES120 input/output module Functional earth

Connection diagrams

Connection of the base unitSchneider-Electric-Easergy-Sepam-
Series-80-fig-10

NOTICE
HAZARD OF IMPROPER OPERATION

  • Do not use a CCA634 on connector B1 and residual current input I0 on connector E (terminals 14 and 15) simultaneously. Even if it is not connected to a sensor, a CCA634 on connector B1 will disturb input I0 on connector E.
  • Do not use a CCA634 on connector B2 and residual current input I’0 on connector E (terminals 17 and 18) simultaneously. Even if it is not connected to a sensor, a CCA634 on connector B2 will disturb input I’0 on connector E.

Failure to follow these instructions can result in equipment damage.

Connection of an MES120 input / ouput moduleSchneider-Electric-Easergy-
Sepam-Series-80-fig-11

Wiring

A connector is required to connect the measurement sensors to and :

  • CCA630 connector to connect the phase CTs
  • CCA634 connector to connect phase CTs and one residual CT
  • CCA671 connector to connect the LPCTs
  • CCT640 connector to connect the VTs.

The table opposite indicates the compatible connectors for each type of Sepam.

Sensor connectors

Schneider-Electric-Easergy-Sepam-Series-80-fig-32

HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC, OR BURNS

DANGER

  • Only qualified personnel should install this equipment. Such work should be performed only after reading this entire set of instructions.
  • NEVER work alone.
  • Turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of back feeding.
  • Always use a properly rated voltage-sensing device to confirm that all power is off.
  • Start by connecting the device to the protective earth and to the functional earth.
  • Screw tight all terminals, even those not in use. Failure to follow these instructions will result in death or serious injury.

| | Wiring instructions
---|---|---
Connector| Type| Wiring
A , E| Screw type CCA620| b wiring with no fittings:

v 1wire with max. cross-section: 0.2 to 2.5 mm² (AWG 24-12) or 2 wires with max. cross-section: 0.2 to 1 mm² (AWG 24-16)

v stripped length: 8 to 10 mm (0.31 to 0.39 in)

b wiring with fittings:

v recommended Telemecanique wiring with fittings: DZ5CE015D: 1 x 1.5 mm² wire (AWG 16)

DZ5CE025D: 1 x 2.5 mm² wire (AWG 12)

AZ5DE010D: 2 x 1 mm² wires (AWG 18)

v tube length: 8.2 mm (0.32 in)

v stripped length: 8 mm (0.31 in)

| 6.35 mm ring lugs CCA622| b 6.35 mm ring or spade lugs (1/4″), 2 lugs maximum per terminal

b wire cross-section: 0.2 to 2.5 mm² (AWG 24-12)

b stripped length: 6 mm (0.24 in)

b use an appropriate tool to crimp the lugs on the wires

b tightening torque: 0.7 to 1 N.m (6.2 to 8.9 lb-in)

B1 , B2| 4 mm ring lugs CCA630 or CCA634

for connection of 1 A or 5 A CTs

| b 4 mm (0.16 in) ring or spade lugs, 2 lugs maximum per terminal

b maximum wire cross-section: 1.5 to 6 mm² (AWG 16-10)

b stripped length: 6 mm (0.24 in)

b use an appropriate tool to crimp the lugs on the wires

b tightening torque: 1.2 N.m (11 lb-in)

| CCA671 RJ45 connector for connection of LPCT sensors| Built into LPCT sensor
| CCT640 for connection of VTs| Same as wiring of CCA620 screw-type connector
Functional earth| Ring lug| Earthing braid, to be connected to cubicle grounding:

b flat copper braid with cross-section u 9 mm² (> AWG 8)

b maximum length: 300 mm (12 in).

MES120| Screw type| Same as wiring of CCA620 screw-type connector

Advanced UMI

Description

  1. Green LED: Sepam on
  2. Red LED: Sepam unavailable
  3. 9 yellow indication LEDs
  4. A label identifying the indication LEDs
  5. Graphical LCD screen
  6. Display of measurements
  7. Display of switchgear, network and machine diagnosis data
  8. Display of alarm messages
  9. Sepam reset (or confirm data entry)
  10. Acknowledgment and clearing of alarms (or moving the cursor up)
  11. LED test (or move the cursor down)
  12. Display and adaptation of activated protection settings
  13. Display of Sepam and Logipam data
  14. Entry of 2 passwords
  15. PC connection port.
  16. Backup battery
  17. Protective battery cover
  18. Memory cartridge
  19. Door

Note: the description of items 1 to 15 also applies to the DSM303 remote advanced UMI module.

NOTICE DAMAGE TO THE MEMORY CARTRIDGE
Do not connect nor disconnect the memory cartridge with the power on. Failure to observe these instructions can result in equipment damage.

Operation

Access to measurements
The measurements are split into 2 categories, accessed via the following keys:

  • key: access to measurements
  • key: access to switchgear, network and machine diagnosis data. The values are presented in a series of screens as shown in the diagram below. Each time the user presses the key, the system moves on to the following screen in the loop.Schneider-Electric-Easergy-Sepam-Series-80-fig-17

Operation After fault tripping of the protection function (e.g. phase overcurrent):

  • the Trip indicator goes on
  • the I>51 indicator goes on
  • the UMI screen displays:
    • v a “Phase fault” message
    • v the date and time of the appearance of the fault
  • the key may be pressed to display the last 16 unacknowledged alarm messages
  • the key may be pressed to erase the message (acknowledgment)
  • the key may be pressed to reset the protection function.

Changing protection settings

The key may be used to change the set point and time delay of most of the protection functions in service in Sepam. It is accessed via a menu that lists the protection functions used. The user selects the protection function to consult or modify the setting of each of the units used for the function.

Mimic-based UMI

Description

  1. Graphical LCD screen
  2. Green LED: Sepam on
  3. Red LED: Sepam unavailable
  4. Local close order
  5. Local open order
  6. A label identifying the indication LEDs
  7. yellow indication LEDs, 1 red LED (I), 1 green LED (O).
  8. Move cursor up
  9. Confirm data entry
  10. Move cursor down
  11. PC connection port
  12. Transparent door
  13. Entry of 2 passwords
  14. Mimic-based UMI display
  15. Sepam reset
  16. Display of alarm messages
  17. Acknowledgment and clearing of alarms
  18. Display of switchgear and network diagnosis data (or LED test)
  19. Display and adaptation of activated protection settings
  20. Display of measurements.
  21. Display of Sepam and Logipam data
  22. Three-position key switch to select Sepam control mode
  23. Backup battery
  24. Protective battery cover
  25. Memory cartridge
  26. DoorSchneider-Electric-Easergy-Sepam-Series-80-fig-18

NOTICE

DAMAGE TO MEMORY CARTRIDGE
Do not connect nor disconnect the memory cartridge with the power on. Failure to observe these instructions can result in equipment damage.

Access to measurements
The measurements are split into 2 categories, accessed via the following keys:

  • : key: access to measurements
  • : key: access to switchgear, network, and machine diagnosis data. The values are presented in a series of screens as shown in the diagram below. Each time the user presses the key, the system moves on to the following screen in the loop.Schneider-Electric-Easergy-Sepam-Series-80-fig-21

Operation
After fault tripping of the protection function (e.g. phase overcurrent):

  • the Trip indicator goes on
  • the I>51 indicator goes on
  • the UMI screen displays:
    • a “Phase fault” message
    • the date and time of the appearance of the fault
  • the key may be pressed to display the last 16 unacknowledged alarm messages
  • the key may be pressed to erase the message (acknowledgment)
  • the key may be pressed to reset the protection function.

Changing protection settings
The key may be used to change the set point and time delay of most of the protection functions in service in Sepam. It is accessed via a menu that lists the protection functions used. The user selects the protection function to consult or modify the setting of each of the units used for the function.

Selecting the control mode
By key-switch on the front of the mimic-based UMI: REMOTE, LOCAL, TEST. Local switchgear control All the devices for which the opening and closing are controlled by Sepam may be controlled locally via the mimic based UMI. The most common interlocking conditions may be defined by logic equations or by Logipam.

Operating procedure:

  • select the LOCAL control mode on the key-switch
  • select the device to be controlled by moving the selection window using the keys Sepam checks whether local control of the selected device is authorized and informs the operator (selection window with a solid line).
  • selection confirmation for the device to be controlled by pressing the key (the selection window flashes). device control by pressing:
    • key : open order
    • or key : close order.

Commissioning

Energizing
The Sepam supply voltage must be between 24 V DC and 250 V DC. After Sepam is switched on, it performs the following initialization sequence, which takes approximately 5 seconds:

  • ON and LEDs switch on, “Sepam” on screen
  • LED switches off
  • watchdog contact picks up

The first screen displayed at the end of the sequence is the phase current metering screen.

Diagnosis
At the end of the initialization sequence, the LED should be off.

  • LED flashing: minor fault detected, Sepam in downgraded operation
  • check the connection of the MET148-2, MSA141 and MCS025 modules.
  • LED steadily on: major fault detected, Sepam in failsafe position
  • check that the CCA630, CCA634 or CCA671 input connectors are plugged in
  • check the connection of the strap between terminals 19 and 20 of connector (DPC, detection of plugged connector function).
    • If the  LED is still not off, refer to the “Maintenance” chapter of the operating manual.
    • If the “LOW BATTERY” message appears, check that the battery is present and in the correct position (check that polarities match).

Parameter setting with SFT2841
The SFT2841 parameter setting and the operating tool is essential to:

  • prepare Sepam parameters
  • to prepare protection and control function settings.
  • transfer the parameters and settings into Sepam.

Passwords
Sepam has two 4-digit passwords:

  • parameter setting password, which allows entry of all general parameters and protection settings
  • protection setting password, which only allows entry of protection settings

Schneider-Electric-Easergy-Sepam-Series-80-fig-31

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals