Golden Security Outdoor Strobe Siren GS-ZSS08 Manual

June 8, 2024
Golden Security

Golden Security

Outdoor Strobe Siren

SKU: GS-ZSS08

Quickstart

This is a
secure
Siren
for
CEPT (Europe)
.

To run this device please connect it to your mains power supply.

To add this device to your network execute the following action:
1 Set Z-Wave Controller into inclusion mode,2 Power on the device.3 Press the button 3 times within 1.5s.4 The device will be entered into inclusion mode automatically.

Please refer to the
Manufacturers Manual
for more information.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

This product can be included and operated in any Z-Wave network with other Z-Wave certified devices from other manufacturers and/or other applications. All non-battery operated nodes within the network will act as repeaters regardless of vendor to increase reliability of the network. The siren support 110dB alarm sound and light flashing to threaten burglars/intruders.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

Note: please use the reset procedure only when the primary controller is missing or inoperable.Operation as below:1 Power on the device.2 Keep holding touched the button for 10s until the led turn to red, then release.

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country- specific
installation guidelines/norms may do works with mains power. Prior to the assembly of
the product, the voltage network has to be switched off and ensured against re-switching.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

1 Set Z-Wave Controller into inclusion mode,2 Power on the device.3 Press the button 3 times within 1.5s.4 The device will be entered into inclusion mode automatically.

Exclusion

1 Set Z-Wave Controller into exclusion mode2 Power on the device.3 Press the button 3 times within 1.5s4 The device will be entered into exclusion mode automatically.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 5| Z-Wave Plus Lifeline, all nodes which associated in this group will receive the messages sent by device through lifeline.
---|---|---
2| 5| It is controlling group, all nodes associated in this group will be controlled through BASIC_SET command by the device when device detects a tampering event.

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Alarm Sound Selected

This parameter is to set the sound sent by the alarm when giving an alarm and users can choose five different sound sources through this setting.
Size: 1 Byte, Default Value: 1

SettingDescription

1 default alarm sound
2 – 6 to choose different alarm sound

Parameter 2: Alarm Sound Volume Settings

Users can set through this parameter the sound volume sent when the alarm is activated, and there are 16 levels, with the adjustable scales being 0~15.0 is the minimum volume and 15 is the maximum volume.
Size: 1 Byte, Default Value: 15

SettingDescription

0 no alarm sound
1 – 14 from low to high alarm sound volume setting
15 maximum volume

Parameter 3: Alarm Duration Time

This parameter can set the duration of the alarm function after activation. Unit of time is: seconds.
Size: 2 Byte, Default Value: 300

SettingDescription

0 Alarm Silenced (No Alarm)
1 – 32766 Duration of the alarm in Seconds
32767 The alarm stays on until shut down by the user.

Parameter 4: Led Blink Pattern

There have 3 led pattern mode for user selecting.
Size: 1 Byte, Default Value: 3

SettingDescription

1 LED will not turn on when there is an alarm.
2 The LED will blink slowly when there is an alarm.
3 The LED will blink rapidly when there is an alarm.

Parameter 5: Switch Binary Report Disable

_Set this configuration to 0, siren will not send an SWITCH_BINARYREPORT to controller when an alarm is happed.
Size: 1 Byte, Default Value: 1

SettingDescription

0| siren will not send an SWITCH_BINARY_REPORT to controller when an alarm is happed.
---|---
1| siren will send an SWITCH_BINARY_REPORT to controller when an alarm is happed.

Parameter 6: Alarm Disable

This configuration sets siren alarm is enabled or disabled.
Size: 1 Byte, Default Value: 1

SettingDescription

0 alarm disable, siren will never give an alarm.
1 alarm enable, siren will give an alarm when an alarm event is happened.

Parameter 7: Sensor Report Enable

This configuration sets binary sensor report is enabled or disabled.
Size: 1 Byte, Default Value: 0

SettingDescription

1 enable sensor binary report when device detects a tampering event.
0 disable sensor binary report when device detects a tampering event.

Technical Data

Hardware Platform ZM5202
Device Type Siren
Network Operation Always On Slave
Firmware Version HW: 19 FW: 1.32
Z-Wave Version 6.71.01
Certification ID ZC10-18015964
Z-Wave Product Id 0x033A.0x0003.0x0101
Outdoor Use ok
Supported Notification Types
Security V2 S2_UNAUTHENTICATED
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Association Grp Info
  • Association V2
  • Basic
  • Configuration
  • Device Reset Locally
  • Indicator
  • Manufacturer Specific V2
  • Multi Channel Association V3
  • Notification V8
  • Powerlevel
  • Security
  • Security 2
  • Sensor Binary V2
  • Supervision
  • Switch Binary
  • Transport Service V2
  • Version V2
  • Zwaveplus Info V2

Controlled Command Classes

  • Basic

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals