WINKA SYSIT 4 in 1 multi sensor WK-0002 Manual

June 8, 2024
WINKA SYSIT

Table of Contents

WINKA SYSIT

4 in 1 multi sensor

SKU: WK-0002

Quickstart

This is a
secure
Alarm Sensor
for
CEPT (Europe)
.

Please make sure the internal battery is fully charged.

To add this device to your network execute the following action:
First, press the both two tamper buttons on the both side of the device simultaneously and then power thesensor up, which will make it enter the factory testing mode. In this mode, no sensor function works, and theLED light will keep flashing.Exit from factory test mode: Power off and then power the socket on by un-pressing two buttons. And then itwill enter the normal working mode.

Please refer to the
Manufacturers Manual
for more information.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

4 in 1multi sensor,Function includes Motion detected, Door/window detected, Tampering detected, Ambient light intensity /temperature measured.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

a) Ensure that the sensor is powered up correctly.b) Remove the sensor cover on the top, press the tamper button on the top of the sensor three times quickly within 1.5s. Then sensor will erase all data and restore to the defaults and the LED will flash for 10times with an interval of 500ms.Note: This mode can also erase the network information of the sensor and make the device removed from the Z-Wave network that it has included. Please use this procedure only when the network primary controller is missing or otherwise inoperable.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

First, press the both two tamper buttons on the both side of the device simultaneously and then power thesensor up, which will make it enter the factory testing mode. In this mode, no sensor function works, and theLED light will keep flashing.Exit from factory test mode: Power off and then power the socket on by un-pressing two buttons. And then itwill enter the normal working mode.

Exclusion

First, press the both two tamper buttons on the both side of the device simultaneously and then power thesensor up, which will make it enter the factory testing mode. In this mode, no sensor function works, and theLED light will keep flashing.Exit from factory test mode: Power off and then power the socket on by un-pressing two buttons. And then itwill enter the normal working mode.

Communication to a Sleeping device (Wakeup)

This device is battery operated and turned into deep sleep state most of the time
to save battery life time. Communication with the device is limited. In order to
communicate with the device, a static controller C is needed in the network.
This controller will maintain a mailbox for the battery operated devices and store
commands that can not be received during deep sleep state. Without such a controller,
communication may become impossible and/or the battery life time is significantly
decreased.

This device will wakeup regularly and announce the wakeup
state by sending out a so called Wakeup Notification. The controller can then
empty the mailbox. Therefore, the device needs to be configured with the desired
wakeup interval and the node ID of the controller. If the device was included by
a static controller this controller will usually perform all necessary
configurations. The wakeup interval is a tradeoff between maximal battery
life time and the desired responses of the device. To wakeup the device please perform
the following action:

Press the tamper button on the back of the sensor shortly. Then the LED will flash once. If the sensor has addedin a Z-Wave network, the sensor will send WAKE_UP_INFORMATION message to the gateway.If the tamper button is pressed for three times quickly, the sensor will broadcast NODE_INFO messages.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 5| Lifeline group, Support Command List as below:COMMAND_CLASS_NOTIFICATION, NOTIFICATION_REPORTCOMMAND_CLASS_SENSOR_MULTILEVEL, SENSOR_MULTILEVEL_REPORTCOMMAND_CLASS_SENSOR_BINARY, SENSOR_BINARY_REPORTCOMMAND_CLASS_BATTERY, BATTERY_REPORTCOMMAND_CLASS_DEVICE_RESET_LOCALLY, DEVICE_RESET_LOCALLY_NOTIFICATION
---|---|---
2| 5| control group, the preset event is occured, sensor will send BASIC_SET command to the devices that associated in this group. Support Command List as Below:COMMAND_CLASS_BASIC, BASIC_SET
3| 5| This group is for motion event report to devices that associated in this group. Support Command List as Below:COMMAND_CLASS_NOTIFICATION,NOTIFICATION_REPORT (Home Security)
4| 5| This group is for Door/Window Open and close event report to devices that associated in this group. Support Command List as Below:COMMAND_CLASS_NOTIFICATION, NOTIFICATION_REPORT (Access Control)

Special Operations as Z-Wave Controller

As long as this device is not included into a Z-Wave network of a different controller
it is able to manage its own Z-Wave network as primary controller. As a primary controller
the device can include and exclude other devices in its own network, manage associations,
and reorganize the network in case of problems. The following controller functions
are supported:

Inclusion of other devices

Communication between two Z-Wave devices only works if both belong to the same
wireless network. Joining a network is called inclusion and is initiated by a controller.
The controller needs to be turned into the inclusion mode. Once in this inclusion mode
the other device needs to confirm the inclusion – typically by pressing a button.

If current primary controller in your network is in special SIS mode this and
any other secondary controller can also include and exclude devices.

To become
primary a contoller have to be resetted and then include a device.

a) Ensure that the sensor is powered up correctly.b) Set Z-Wave Gateway entered inclusion mode.c) Press the tamper button on the back of the sensor for three times quickly within 1.5 seconds. Then the LEDlight will flash for 10 times with an interval of one second, which means that the sensor has entered themode of networking and it is waiting for the gateway to complete the configuration.

Exclusion of other devices

The primary controller can exclude devices from the Z-Wave network. During exclusion
the relationship between the device and the network of this controller is terminated.
No communication between the device and other devices still in the network can happen
after a successful exclusion. The controller needs to be turned into the exclusion mode.
Once in this exclusion mode the other device needs to confirm the exclusion – typically
by pressing a button.

Attention: Removing a device from the network means that it is turned back
into factory default status. This process can also exclude devices from it’s previous
network.

a) Ensure that the sensor is powered up correctly.b) Set Z-Wave Gateway entered exclusion mode.c) Press the tamper button on the back of the sensor for three times quickly within 1.5 seconds. Then the LEDlight will flash for 10 times with an interval of 500ms, which means that the sensor has entered the modeof removing from the network and it is waiting for the host to complete the configuration.

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: 1)Sensitivity setting

This parameter is to set the detection sensitivity of the motion sensor. The smaller the value is and the higher the detection sensitivity is, the farther the detection range of the sensor is.
Size: 1 Byte, Default Value: 4

SettingDescription

0 – 99 0 is Max Sensitivity, 99 is Min Sensitivity

Parameter 10: Delay time of clear the motion event

_The time set by this parameter refers to: The duration from the time when the sensor detects the motion event to the time when the sensor completes the removal of the motion event alarm. If during this period, the sensor detects the occurrence of another motion event, the timer will start counting again.When the sensor removes the motion event alarm, the sensor will also send BASICSET(0x00) command to all devices in Connection Group 2.
Size: 2 Byte, Default Value: 30

SettingDescription

0 – 4095 Motion event clear time delay

Parameter 11: Setting of light intensity value report

This parameter sets the conditions of the sensor detecting the environment brightness value and reporting it to the host. If the absolute value of the difference between the currently measured environment brightness value and that measured last time is greater than the value set by this parameter, the sensor will report the currently measured environment brightness value to the host, or otherwise the value will not be reported. In theory, the smaller the value is, the shorter the batterys life is.
Size: 2 Byte, Default Value: 50

SettingDescription

0 – 1000 lux, the Differential value for Luminance Report.

Parameter 12: Setting of light intensity threshold in the night

The values set by this parameter should make it clear whether the current time is night or daytime. If the currently measured environment brightness is greater than the set value of this parameter, it means that it is daytime currently; otherwise it is in the evening.
Size: 2 Byte, Default Value: 50

SettingDescription

0 – 1000| If the Light Intensity Value is less than this value, it will be considered to night.
---|---

Parameter 13: Setting of temperature value report

This parameter sets the conditions of reporting the environmental temperature value currently measured by the temperature sensor to the host. If the absolute value of the difference between the currently measured environmental temperature value and that reported last time is greater than the value represented by the setting of this parameter, the sensor will report the currently measured environmental temperature value to the host, or otherwise the value will not be reported. In theory, the smaller the value is, the shorter the batterys life is.Each value represents 0.1 Celsius degree. For example, if the default value is set as ‘5’, then the temperature represented is 5 * 0.1 = 0.5 Celsius degree; It means that when the difference between the current temperature and the temperature reported last time is greater than 0.5 Celsius degree, the current temperature value will be reported to the host.
Size: 1 Byte, Default Value: 5

SettingDescription

0 – 100 The Differential value for Temperature Report. (0.1 Celsius)

Parameter 14: Interval of the sensors measured setting

This parameter sets the measurement interval of the optical sensor. The greater the set value of this parameter is, the longer the battery life is and the less frequently the brightness is reported to the host when Parameter 10 is met; The smaller the set value of the parameter is, the shorter the battery life will be accordingly and the more the brightness data reported to the host with Parameter 10 being met is. Unit: min
Size: 1 Byte, Default Value: 3

SettingDescription

1 – 127 minute. the time interval for Sensor measurment

Parameter 15: Setting of the trigger source for controlled the associated

devices

_This parameter sets to control connected devices in Group 2 by selecting a certain trigger event supported by the device.0 None of the following events will trigger BASIC_SET command to control the connected devices.1 When detecting a motion event (Motion), it will trigger BASIC_SET command to control the connected devices2 When detecting the doors or windows being opened (Open), it will trigger BASIC_SET command to control the connected devices3 When detecting the device being dismantled (Tamper), it will trigger BASIC_SET command to control the connected devices4 When the brightness is lower than the threshold set in 16, it will trigger BASIC_SET command to control the connected devices5 When the brightness is lower than the threshold set in 17, it will trigger BASIC_SET command to control the connected devices6 When the temperature is lower than the threshold set in 18, it will trigger BASIC_SET command to control the connected devices7 When the temperature is lower than the threshold set in 19, it will trigger BASIC_SET command to control the connected devices 8 When Conditions 1 ~ 3 are met, it will trigger BASIC_SET command to control the connected devices 9 When Conditions 4 ~ 5 are met, it will trigger BASIC_SET command to control the connected devices10 When Conditions 6 ~ 7 are met, it will trigger BASICSET command to control the connected devices
Size: 1 Byte, Default Value: 0

SettingDescription

0 – 10 The Trigger source number for BASIC_SET Command

Parameter 16: Low light intensity threshold

_When the environment brightness value is lower than the value set by this parameter, if the trigger source set by Parameter 15 is low brightness threshold alarm, the sensor will trigger BASICSET to control all connected devices in Connection Group 2.
Size: 2 Byte, Default Value: 50

SettingDescription

0 – 1000 Lux. Low threshold value for light intensity

Parameter 17: High light intensity threshold

_When the environment brightness value is higher than the value set by this parameter, if the trigger source set by Parameter 15 is high brightness threshold alarm, the sensor will trigger BASICSET to control all connected devices in Connection Group 2.
Size: 2 Byte, Default Value: 2000

SettingDescription

1 – 32767 Lux. High threshold value for light intensity

Parameter 18: Low temperature threshold

_When the environment temperature value is lower than the value set by this parameter, if the trigger source set by Parameter 15 is low temperature threshold alarm, the sensor will trigger BASICSET to control all connected devices in Connection Group 2.
Size: 1 Byte, Default Value: 0

SettingDescription

-40 – 30 celsius, Low temperature threshold Value

Parameter 19: High temperature threshold

_When the environment temperature value is lower than the value set by this parameter, if the trigger source set by Parameter 15 is low temperature threshold alarm, the sensor will trigger BASICSET to control all connected devices in Connection Group 2.
Size: 1 Byte, Default Value: 25

SettingDescription

0 – 80 celsius. High temperature threshold value

Parameter 2: PIR Window Time Setting

PIR sensor detects the duration of the motion events. Within the scope of the time, if events meeting Parameter 3 occur, the sensor will confirm that it has detected the occurrence of the motion events.In theory, the greater this value is, the higher the sensitivity of the sensor is. Thus, it is not recommended for users to modify the setting of this parameter.Window time = ([setting] + 1)4s, (value range: 4s, 8s, 12s, 16s)
Size: 1 Byte, Default Value: 2

SettingDescription

0 – 3 Window time = (Value + 1)x 4s;

Parameter 20: Binary Sensor Report Enable

When this parameter is set as 1, then the reporting Binary Sensor Report function of the sensor will be open. When the door magnet, motion detection, or tamper event is triggered, in addition to reporting the Notification Report to the host, it will also report the Binary Sensor Report for the purpose of downward compatibility of the sensor.
Size: 1 Byte, Default Value: 0

SettingDescription

0 – 1 0 – Disable, 1 – Enable

Parameter 3: PIR Pulse Counter Settings

Within the window time set by Parameter 2, when the number of pulses detected by the sensor reaches the value set by this parameter, the sensor will determine the occurrence of motion events. In theory, the higher the value is, the lower the sensitivity of the sensor is. It is not recommended for the user to modify the setting of this parameter.Number of pulses = [setting] + 1. So the value range of the parameter is as follows: 1, 2, 3, 4.
Size: 1 Byte, Default Value: 1

SettingDescription

0 – 3 Pulse Counter = Value + 1

Parameter 4: PIR Blind Time Setting

BlindAfter the sensor detects a motion event, it will stop detecting the duration of the motion event. During this period, the sensor will not issue any command even if there is a motion event occurring in front of the PIR sensor. In theory, the higher the value is, the lower the power consumption of the sensor is. The time set by this parameter must be shorter than the time set by Parameter 9.Silence period = ([setting] + 1) x 0.5s.Thus, the value range of this parameter is as follows: 0.5s ~ 8s, with an interval of 0.5s.
Size: 1 Byte, Default Value: 15

SettingDescription

0 – 15 Blind Time = (Value + 1)x 0.5s

Parameter 5: PIR Detected Disable

The detection function of the motion sensor set by this parameter is disabled or not.’1′-motion detected function is enabled; ‘0’-motion detected function is disabled.
Size: 1 Byte, Default Value: 1

SettingDescription

0 – 1 0 – Disable, 1 – Enable

Parameter 6: LED indicator Disable

This parameter is to set whether the sensor will open LED and other indication functions when detecting a motion event. ‘1’-LED indication is open. When the sensor detects a motion event, the LED will flash once; ‘0’-LED indication is closed. When the sensor detects a motion event, the LED will not flash. Setting of this parameter will not affect the LED indication of the sensor in other conditions.
Size: 1 Byte, Default Value: 1

SettingDescription

0 – 1 0 – Disable, 1 – Enable

Parameter 7: Associated Control with Light Sensor Setting

_This parameter sets whether to send the BASIC_SET command to the connected device based on the current brightness when there is a connected device in Connection Group 2.Parameters of BASIC_SET are determined by Parameter 8.’0′-Whether to send BASIC_SET command has nothing to do with the current environment brightness. As long as the sensor detects the occurrence of the motion event, the sensor will send BASIC_SET command to all devices of Connection Group 2 to control the motions of the device.’1′-When the current environment brightness is lower than the brightness value set by Parameter 11 and the sensor detects the occurrence of the motion event, the sensor will send the BASIC_SET command to all devices in Connection Group 2; If the current environment brightness is greater than or equal to the brightness value set by the parameter, the sensor will not send BASICSET command to all devices in Connection Group 2.
Size: 1 Byte, Default Value: 0

SettingDescription

0 – 1 0 – Disable, 1 – Enable

Parameter 8: Setting of BASIC_SET parameter

_This parameter defines the parameter value of BASIC_SET command so as to facilitate the control over different connected devices by the sensor. For example, if the connected device is a light, when the door magnet is detected to be open, this device will issue BASICSET command (the corresponding parameter is the set value of the parameter) to control the switch of the light.
Size: 1 Byte, Default Value: 100

SettingDescription

0 – 100| 0 – Off, 100 – On(Corresponding to 0xFF), 1 ~ 99 is responding to multilevel value
---|---

Parameter 9: Setting of BASIC_SET (0x00) time delay

_This parameter sets the delay time of sending BASIC_SET = 0x00 (closing the connected device) command by the sensor to the connected device, the unit of which is: Seconds. The execution effect of this parameter is affected by Parameter 15.If Parameter 15 is set as ‘1’ or an event related to ‘1’, the setting of this parameter will be invalid. The time controlling the connected device is only associated with the time set by Parameter 10. When the sensor triggers Motion Clear, it will send BASIC_SET=0x00 automatically.If Parameter 15 is set as ‘2’ or ‘3’ or an event related to ‘2’ or ‘3’, then when a Door/Window Close event or a Tamper Clear event occurs, the sensor will send BASIC_SET=0x00 to close the connected device after delaying for an interval set by this parameter.If Parameter 15 is set as 4 ~ 7, 9, 10, when the event meeting the conditions triggers the sensor, it will issue BASIC_SET= (value of Parameter 8) to control the connected device and then send BASIC_SET=0x00 to close the connected device after delaying for an interval set by this parameter. If the delay time has not come but the measured result of the sensor has returned to normal, then it will trigger BASIC_SET = 0x00 to close the connected device automatically.If this parameter is set as ‘0’, it means that the BASIC_SET = 0x00 command is issued immediately when the trigger event is removed.If this parameter is set as ‘32767’, it means that the device does not send BASICSET = 0x00 command.
Size: 2 Byte, Default Value: 30

SettingDescription

0 – 4095 0- No Delay; Other Value is Delay time (Second)
32767 Not Send BASIC_SET = 0x00

Parameter 99: Light Sensor Calibrated

Due to the differences in shell light transmittance and the influences of sensor installation position on the receiving of light by light sensor, there will be errors in the measurement of environment brightness values. This parameter provides correction methods used in different application environments so as to get as exact environment light intensity as possible. This method requires a standard illuminometer as the reference and it will add the sensor to Z-Wave network. The correction steps are as follows: aRestore this parameter to default value by the host.bPut the standard illuminometer and the sensor in the same position and ensure that the light exposed to them is largely equal. Record the reading on the standard illuminometer, namely Vs. The value measured by this sensor, namely Vm, will be sent to the host via Z-Wave network. Record Vm. The calibration coefficient of this sensor is: k = Vm / Vs.cMultiply k, the coefficient having obtained, by 1024, and then get an integer by rounding it.dSet the value obtained in step c in Parameter 13 via the host. Then the calibration is finished.Example: The reading of the illuminometer Vs = 2600, and the data measured by the sensor at the same time Vm = 300; Then, k = Vm / Vs = 300 / 2600 = 0.1153, multiply the result by 1024k = 0.1153 * 1024 = 118.07, Round it, k = 118And then the calibration will be finished after the value 118 is set in Parameter 99 by host.
Size: 2 Byte, Default Value: 1024

SettingDescription

1 – 32767 Light intensity value correct coefficient

Technical Data

Hardware Platform ZM5202
Device Type Notification Sensor
Network Operation Reporting Sleeping Slave
Firmware Version HW: 16 FW: 1.32:01.33
Z-Wave Version 6.51.09
Certification ID ZC10-17105818
Z-Wave Product Id 0x0331.0x0003.0x1D04
Supported Notification Types Home Security
Sensors Luminance
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Association Grp Info
  • Association V2
  • Battery
  • Configuration
  • Device Reset Locally
  • Manufacturer Specific V2
  • Notification V8
  • Powerlevel
  • Security
  • Sensor Binary V2
  • Sensor Multilevel V7
  • Version V2
  • Wake Up V2
  • Zwaveplus Info V2

Controlled Command Classes

  • Basic

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals