WINKA SYSIT Outlet WK-0003 Manual

June 8, 2024
WINKA SYSIT

WINKA SYSIT

Outlet

SKU: WK-0003

Quickstart

This is a
secure
On/Off Power Switch
for
CEPT (Europe)
.

To run this device please connect it to your mains power supply.

To add this device to your network execute the following action:
Keep pressing the button of the outlet, and then power up the outlet. The outlet will enter the factory test mode,in which all the operations of the outlet will not work and the green LED light will keep flashing.Exit from factory test mode: Power off, and then power the outlet on by un-pressing the button. And then itwill enter the normal working mode.

Please refer to the
Manufacturers Manual
for more information.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

This is a smart power plug, function includes Switch, Electrical parameters measure, Over-current protection & timing. Lets you wirelessly control whatever device is plugged into it remotely, from a schedule, or from the outlet iteself. This smart switch has electrical parameters measure,you can see the electricity which your device are using in real time from APP.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

a) Ensure that the outlet is powered up correctly.b) Press the button and maintain this action for 10 seconds, then release it after the green and red LEDs bothlight on. Then the outlet will restore all data to the factory defaults.Note: This mode can also delete the network information of the outlet and make the device exclude from the Z-Wave network that it has joined.Please use this procedure only when the network primary controller is missing or otherwise inoperable.

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country- specific
installation guidelines/norms may do works with mains power. Prior to the assembly of
the product, the voltage network has to be switched off and ensured against re-switching.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

Keep pressing the button of the outlet, and then power up the outlet. The outlet will enter the factory test mode,in which all the operations of the outlet will not work and the green LED light will keep flashing.Exit from factory test mode: Power off, and then power the outlet on by un-pressing the button. And then itwill enter the normal working mode.

Exclusion

Keep pressing the button of the outlet, and then power up the outlet. The outlet will enter the factory test mode,in which all the operations of the outlet will not work and the green LED light will keep flashing.Exit from factory test mode: Power off, and then power the outlet on by un-pressing the button. And then itwill enter the normal working mode.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 5| Lifeline Group, Support Command List as below:COMMAND_CLASS_SWITCH_BINARY, SWITCH_BINARY_REPORTCOMMAND_CLASS_METER, METER_REPORTCOMMAND_CLASS_NOTIFICATION, NOTIFICATION_REPORTCOMMAND_CLASS_DEVICE_RESET_LOCALLY, DEVICE_RESET_LOCALLY_NOTIFICATION
---|---|---
2| 5| Control Group, If over-load is occured, the device will send BASIC_SET to nodes associated in group 2. Support Command List as Below:COMMAND_CLASS_BASIC, BASIC_SET
3| 5| Power Manager Group. If Over-load is occured, device will send notification report to nodes associated in group 3. Support List as Below:COMMAND_CLASS_NOTIFICATION, POWERMANAGEMENT STATUS (OVER LOAD)

Special Operations as Z-Wave Controller

As long as this device is not included into a Z-Wave network of a different controller
it is able to manage its own Z-Wave network as primary controller. As a primary controller
the device can include and exclude other devices in its own network, manage associations,
and reorganize the network in case of problems. The following controller functions
are supported:

Inclusion of other devices

Communication between two Z-Wave devices only works if both belong to the same
wireless network. Joining a network is called inclusion and is initiated by a controller.
The controller needs to be turned into the inclusion mode. Once in this inclusion mode
the other device needs to confirm the inclusion – typically by pressing a button.

If current primary controller in your network is in special SIS mode this and
any other secondary controller can also include and exclude devices.

To become
primary a contoller have to be resetted and then include a device.

a) Ensure that the outlet is powered up correctly.b) Set Z-Wave Gateway entered inclusion mode.c) Press the button on the outlet for three times quickly within 1.5 seconds. Then the LED light will flash for5 times with an interval of 500ms, which means that the outlet has entered the inclusion mode and it iswaiting for the gateway to complete the configuration.

Exclusion of other devices

The primary controller can exclude devices from the Z-Wave network. During exclusion
the relationship between the device and the network of this controller is terminated.
No communication between the device and other devices still in the network can happen
after a successful exclusion. The controller needs to be turned into the exclusion mode.
Once in this exclusion mode the other device needs to confirm the exclusion – typically
by pressing a button.

Attention: Removing a device from the network means that it is turned back
into factory default status. This process can also exclude devices from it’s previous
network.

a) Ensure that the outlet is powered up correctly.b) Set Z-Wave Gateway entered exclusion mode.c) Press the button on the outlet for three times quickly within 1.5 seconds. Then the LED light will flash for5 times with an interval of 500ms, which means that the outlet has entered the mode of excluding from thenetwork and it is waiting for the gateway to complete the configuration.

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Outlet On/Off state Saved Disable

This parameter is set as ‘1’. The switch will save the current switch state, and after the outlet is powered down and restarted, it will automatically recover to the switch state before power-down.
Size: 1 Byte, Default Value: 1

SettingDescription

0 – 1 0 – Disable, 1 – Enable

Parameter 2: Button Switch Function Disable

Setting this parameter as ‘0’ will make it invalid to operate the outlet switch with the button
Size: 1 Byte, Default Value: 1

SettingDescription

0 – 1 0 – Disable, 1 – Enable

Parameter 3: Outlet LED indication Disable

Setting this parameter as ‘0’ will forbid the LED of the outlet from being on; Parameter ‘0’ is invalid to the LED indication in the power-up state.
Size: 1 Byte, Default Value: 1

SettingDescription

0 – 1 0 – Disable, 1 – Enable

Parameter 4: Timer Enable

Setting this parameter as ‘1’ will start the timing function of the outlet,and the length of time is determined by the setting of Parameter 5.This function can only provide the timed closing control function when the outlet is open.
Size: 1 Byte, Default Value: 0

SettingDescription

0 – 1 0 – Disable, 1 – Enable

Parameter 5: Time cycle setting

This parameter sets the time length of closing the outlet at a fixed time,the unit of which is minute,which is only valid when Parameter 4 is set as ‘1’.
Size: 2 Byte, Default Value: 150

SettingDescription

1 – 32767 minute. the time interval for Timer

Parameter 6: Meter reporting function Disable

Setting this parameter as ‘0’ will close the timed report function of the outlet, with no influence on the current change reporting function. The interval of reporting electric quantity detection result is controlled by the time set by Parameter 7.
Size: 1 Byte, Default Value: 1

SettingDescription

0 – 1 0 – Disable, 1 – Enable

Parameter 7: Interval of meter reporting setting

This parameter is to set the interval of reporting electric quantity detection result, the unit of which is: Seconds. This parameter is only valid when Parameter 6 is set as ‘1’.
Size: 1 Byte, Default Value: 300

SettingDescription

30 – 32767 second. The timer interval for meter report

Parameter 8: Maximum output current setting

This parameter sets the maximum output current that the outlet can provide,the unit of which is: Ampere (A).When the current consumed by the load is greater than the set value, the outlet will automatically cut off the power of the load and send out alarm information.
Size: 1 Byte, Default Value: 16

SettingDescription

1 – 16 The max output current value. (Ampere)

Parameter 9: Current changes setting

This parameter sets the change volume of the load current (volatility). When the differences between two measurements of current consumed by the load exceed the value set by this parameter, the outlet will report the last electric quantity detection result automatically to the host, the unit of which is 0.01A.For example, when this parameter is set as 10, then 100.01A = 0.1A, which means that all results currently measured will be reported to the outlet automatically (voltage, current, instant power and cumulative power) when the difference between the current measured currently and the current reported last time is greater than 0.1A.
Size: 2 Byte, Default Value: 50

SettingDescription

1 – 1600 The current changed value for meter report. (0.01A)

Technical Data

Hardware Platform ZM5202
Device Type On/Off Power Switch
Network Operation Always On Slave
Firmware Version HW: 16 FW: 1.36
Z-Wave Version 6.51.09
Certification ID ZC10-17105819
Z-Wave Product Id 0x0331.0x0003.0x1D61
Switch Type Toggle
Supported Notification Types Power Management
Supported Meter Type Electric Energy
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Association Grp Info
  • Association V2
  • Basic
  • Configuration
  • Device Reset Locally
  • Manufacturer Specific V2
  • Meter V4
  • Notification V8
  • Powerlevel
  • Security
  • Switch All
  • Switch Binary
  • Version V2
  • Zwaveplus Info V2

Controlled Command Classes

  • Basic

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals