Nice Door/Window-Control FGDW-002 Manual

June 8, 2024
Nice

Nice

Door/Window-Control

SKU: FGDW-002

Quickstart

This is a
secure
Alarm Sensor
for
.

Please make sure the internal battery is fully charged.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

Door/Window-Control is a wireless, battery powered Hall effect contact sensor, compatible with the Z-Wave Plus standard. Changing the devices status will automatically send signal to the Z-Wave controller and associated devices. Sensor can be used to trigger scenes and wherever there is a need for information about opening or closing of doors, windows, garage doors, etc. Opening is detected by separating the sensors body and the magnet.In addition, Door/Window-Control is equipped with a built-in temperature sensor.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 1| u0022Lifelineu0022 reports the device status and allows for assigning single device only (main controller by default).
---|---|---
2| 5| On/Off is assigned to the device status – contact sensor (sends Basic Set command frames).
3| 5| Tamper is assigned to the TMP switch (sends alarm command frames).

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Door/window state

This parameter allows to set in what state is door/window when the magnet is close to the sensor.
Size: 1 Byte, Default Value: 0

SettingDescription

0 – 1 Door/window state

Parameter 10: Tamper – reporting alarm cancellation

Reporting cancellation of tamper alarm to the controller and 3rd association group.
Size: 1 Byte, Default Value: 1

SettingDescription

0 – 1 Tamper – reporting alarm cancellation

Parameter 11: Interval of temperature measurements

This parameter defines how often the temperature will be measured. The shorter the time, the more frequently the temperature will be measured, but the battery life will shorten.
Size: 2 Byte, Default Value: 300

SettingDescription

0 – 32400 Interval of temperature measurements

Parameter 12: Temperature reports threshold

This parameter defines the change of temperature in comparison with last reported, resulting in temperature report being sent to the main controller.
Size: 2 Byte, Default Value: 10

SettingDescription

0 – 300 Temperature reports threshold

Parameter 13: Interval of temperature reports

This parameter determines how often the temperature reports will be sent to the main controller (regardless of parameters 50 and 51).
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 32400 Interval of temperature reports

Parameter 14: Temperature offset

The value to be added to the actual temperature, measured by the sensor (temperature compensation).
Size: 2 Byte, Default Value: 0

SettingDescription

-1000 – 1000 Temperature offset

Parameter 15: Temperature alarm reports

Temperature alarms reported to the Z-Wave controller. Thresholds are set in parameters 55 and 56.
Size: 1 Byte, Default Value: 0

SettingDescription

0 – 3 Temperature alarm reports

Parameter 16: High temperature alarm threshold

If temperature is higher than set value, overheat notification will be sent and high temperature alarm will be triggered (if activated).Value set in parameter 55 must be higher than value set in parameter 56.
Size: 2 Byte, Default Value: 350

SettingDescription

1 – 600 High temperature alarm threshold

Parameter 17: Low temperature alarm threshold

If temperature is lower than the set value, underheat notification will be sent and low temperature alarm will be triggered (if activated).
Size: 2 Byte, Default Value: 100

SettingDescription

0 – 599 Low temperature alarm threshold

Parameter 2: Visual LED indications

This parameter defines events indicated by the visual LED indicator. Disabling events might extend battery life.
Size: 1 Byte, Default Value: 6

SettingDescription

1 – 6 Visual LED indications

Parameter 3: Associations in Z-Wave network Security Mode

This parameter defines how commands are sent in specified association groups: as secure or non-secure. Parameter is active only in Z-Wave network Security Mode. It does not apply to 1st group Lifeline
Size: 1 Byte, Default Value: 3

SettingDescription

0 – 3 Associations in Z-Wave network Security Mode

Parameter 4: 2nd association group triggers

Parameter defines events which result in sending on/off commands to devices added to the 2nd association group. These commands are sent alternately to switch the devices on and off.
Size: 1 Byte, Default Value: 0

SettingDescription

0 – 2 2nd association group triggers

Parameter 5: Association for opening – value sent

Value sent to devices in 2nd association group when opening is detectedThe value of 0 turns OFF the device, 255 turns it ON. In case of associating devices allowing smooth control, values 1-99 allow to set an associated device to a specified level.
Size: 2 Byte, Default Value: 255

SettingDescription

0 – 255 Association for opening – value sent

Parameter 6: Association for closing – value sent

Value sent to devices in 2nd association group when closing is detectedThe value of 0 turns OFF the device, 255 turns it ON. In case of associating devices allowing smooth control, values 1-99 allow to set an associated device to a specified level.
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 255 Association for closing – value sent

Parameter 7: Association for opening – time delay

Time that must elapse from opening to send the command frame to to devices in 2nd association group.
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 32400 Association for opening – time delay

Parameter 8: Association for closing – time delay

Time that must elapse from closing to send the command frame to devices in 2nd association group.
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 32400 Association for closing – time delay

Parameter 9: Tamper – alarm cancellation delay

Time period after which a tamper alarm will be cancelled.
Size: 2 Byte, Default Value: 5

SettingDescription

0 – 32400 Tamper – alarm cancellation delay

Technical Data

Hardware Platform ZM5101
Device Type Notification Sensor
Network Operation Reporting Sleeping Slave
Firmware Version HW: 2 FW: 3.02
Z-Wave Version 6.51.09
Certification ID ZC10-22037075
Z-Wave Product Id 0x010F.0x0702.0x1000
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Application Status
  • Association Grp Info
  • Association V2
  • Basic
  • Battery
  • Configuration
  • Crc 16 Encap
  • Device Reset Locally
  • Firmware Update Md V4
  • Manufacturer Specific V2
  • Multi Channel Association V3
  • Notification V5
  • Powerlevel
  • Security
  • Sensor Multilevel V5
  • Version V2
  • Wake Up V2
  • Zwaveplus Info V2

Controlled Command Classes

  • Basic
  • Notification V5

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals