Aeotec MultiSensor 6 ZW100-A Manual
- June 8, 2024
- Aeotec
Table of Contents
- Aeotec
- MultiSensor 6
- SKU: ZW100-A
- Quickstart
- Important safety information
- What is Z-Wave?
- Product Description
- Prepare for Installation / Reset
- Inclusion/Exclusion
- Communication to a Sleeping device (Wakeup)
- Quick trouble shooting
- Association – one device controls an other device
- Configuration Parameters
- Parameter 100: Set the parameter 101-103 to default values.
- Parameter 101: To set which report would be sent in Report group 1
- Parameter 102: To set which report would be sent in Report group 2
- Parameter 103: To set which report would be sent in Report group 3
- Parameter 111: To set the interval time of sending reports in Report
- Parameter 112: To set the interval time of sending reports in Report
- Parameter 113: To set the interval time of sending reports in Report
- Parameter 2: Enable/Disable waking up for 10 minutes when re-power on
- Parameter 201: Temperature sensor calibration
- Parameter 202: Humidity sensor calibration
- Parameter 203: Luminance sensor calibration
- Parameter 204: Ultraviolet sensor calibration
- Parameter 252: Enable/disable all configuration parameters to be locked
- Parameter 255: Reset to factory defaults.
- Parameter 3: Set the PIR time.
- Parameter 39: Configure the default low battery value.
- Parameter 4: Set the sensitivity of the motion sensor.
- Parameter 40: Enable/disable the selective reporting only when
- Parameter 41: Threshold change in temperature to induce an automatic
- Parameter 42: Threshold change in humidity to induce an automatic report
- Parameter 43: Threshold change in luminance to induce an automatic
- Parameter 44: Threshold change in battery level to induce an automatic
- Parameter 45: Threshold change in ultraviolet to induce an automatic
- Parameter 46: Enable/disable to send the alarm report of low temperature
- Parameter 48: Enable/disable to send a report when the measurement is
- Parameter 49: Set the upper limit value of temperature sensor.
- Parameter 5: Which command would be sent when the motion sensor
- Parameter 50: Set the lower limit value of temperature sensor.
- Parameter 51: Set the upper limit value of humidity sensor.
- Parameter 52: Set the lower limit value of humidity sensor.
- Parameter 53: Set the upper limit value of Lighting sensor
- Parameter 54: Set the lower limit value of Lighting sensor.
- Parameter 55: Set the upper limit value of ultraviolet sensor.
- Parameter 56: Set the lower limit value of ultraviolet sensor.
- Parameter 57: Set the recover limit value of temperature sensor.
- Parameter 58: Set the recover limit value of humidity sensor.
- Parameter 59: Set the recover limit value of Lighting sensor.
- Parameter 60: Set the recover limit value of Ultraviolet sensor.
- Parameter 61: Get the out-of-limit state of the Sensors.
- Parameter 64: Set the default unit of the automatic temperature report in
- Parameter 8: Set the timeout of awake after the Wake Up CC is sent out..
- Parameter 81: Enable/disable the LED blinking when the PIR is triggered.
- Parameter 9: Report the current power mode and the product state for
- Technical Data
- Supported Command Classes
- Controlled Command Classes
- Explanation of Z-Wave specific terms
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Aeotec
MultiSensor 6
SKU: ZW100-A
Quickstart
This is a
secure
Alarm Sensor
for
U.S. / Canada / Mexico.
Please make sure the internal battery is fully charged.
To add this device to your network execute the following action:
Turn the primary controller of Z-Wave network into inclusion mode, short press
the products Z-Wave button that you can find in the back of the product.
Please refer to the
Manufacturers
Manual
for more information.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in
this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any
loss or damage resulting from failure to comply with the instructions in this
manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal
instructions.
Do not dispose of electronic equipment or batteries in a fire or near open heat sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart
Home. This
device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message ( two-
way
communication) and every mains powered node can act as a repeater for other
nodes
( meshed network ) in case the receiver is not in direct wireless range of
the
transmitter.
This device and every other certified Z-Wave device can be used together
with any other
certified Z-Wave device regardless of brand and origin as long as both are
suited for the
same frequency range.
If a device supports secure communication it will communicate with other
devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to
maintain
backward compatibility.
For more information about Z-Wave technology, devices, white papers etc.
please refer
to www.z-wave.info.
Product Description
Aeotec MultiSensor 6 looks like a motion sensor and it acts like one too. But its also so much more. Installing this 1 piece of Z-Wave technology is the same as installing 6 pieces of Z-Wave technology. Your home control network will immediately understand motion, temperature, humidity, light, Ultraviolet and Vibration readings wherever MultiSensor installed. Those intelligent readings will equate to intelligence automation. And intelligent automation will give you the perfect, smart home.
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory
default
state. Please make sure to reset the device into factory default. You can do
this by
performing an Exclusion operation as described below in the manual. Every
Z-Wave
controller is able to perform this operation however it is recommended to use
the primary
controller of the previous network to make sure the very device is excluded
properly
from this network.
Reset to factory default
This device also allows to be reset without any involvement of a Z-Wave
controller. This
procedure should only be used when the primary controller is inoperable.
Press and hold the Z-Wave button that you can find in back of the product for 20 seconds and then release. This procedure should only be used when the primary controller is inoperable.
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The
device needs
to be added to an existing wireless network to communicate with the
devices of this network.
This process is called Inclusion.
Devices can also be removed from a network. This process is called
Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network.
This
controller is turned into exclusion respective inclusion mode. Inclusion and
Exclusion is
then performed doing a special manual action right on the device.
Inclusion
Turn the primary controller of Z-Wave network into inclusion mode, short press the products Z-Wave button that you can find in the back of the product.
Exclusion
Turn the primary controller of Z-Wave network into exclusion mode, short press the products Z-Wave button that you can find in back of the product.
Communication to a Sleeping device (Wakeup)
This device is battery operated and turned into deep sleep state most of the
time
to save battery life time. Communication with the device is limited. In order
to
communicate with the device, a static controller C is needed in the
network.
This controller will maintain a mailbox for the battery operated devices and
store
commands that can not be received during deep sleep state. Without such a
controller,
communication may become impossible and/or the battery life time is
significantly
decreased.
This device will wakeup regularly and announce the wakeup
state by sending out a so called Wakeup Notification. The controller can then
empty the mailbox. Therefore, the device needs to be configured with the
desired
wakeup interval and the node ID of the controller. If the device was included
by
a static controller this controller will usually perform all necessary
configurations. The wakeup interval is a tradeoff between maximal battery
life time and the desired responses of the device. To wakeup the device please
perform
the following action:
Pressing the Z-Wave button once will trigger sending the Wake up notification command. If press and hold the Z-Wave button for 3 seconds, the MultiSensor will wake up for 10 minutes.
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
- Make sure a device is in factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Dont poll FLIRS devices.
- Make sure to have enough mains powered device to benefit from the meshing
Association – one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one
device
controlling another device is called association. In order to control a
different
device, the controlling device needs to maintain a list of devices that will
receive
controlling commands. These lists are called association groups and they are
always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’
Command.
Association Groups:
Group NumberMaximum NodesDescription
1| 5| The MultiSensor supports 1 association group. Group 1 is assigned to the
Lifeline association group and can add max 5 association nodes.When the PIR
motion sensor is triggered, the MultiSensor will send Basic Set (0xFF) to the
associated nodes. If no PIR motion is triggered after the PIR interval time
(configurable), the MultiSensor will send Basic Set (0x00) to the associated
nodes.The automatically reports of temperature, humidity, luminance and
ultraviolet (configurable) also can be sent to the associated nodes.
---|---|---
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock
further
enhanced features.
IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus
56.
In case of a two byte value the same logic applies: Values greater than 32768
may
needed to be given as negative values too.
Parameter 100: Set the parameter 101-103 to default values.
Set the parameter 101-103 to default values.
Size: 1 Byte, Default Value: 0
SettingDescription
1 | Set the parameter 101-103 to default values. |
---|
Parameter 101: To set which report would be sent in Report group 1
To set which report would be sent in Report group 1.Note:You can also set
all sensor reports to be sent out at the same time. E.g. If you want the
batter report and temperature report to be sent out at the same time, you just
need to set the configuration value to 33 (1+32).
Size: 4 Byte, Default Value: 241
SettingDescription
1 | Battery Report is enabled. |
---|---|
16 | Ultraviolet Report is enabled. |
32 | Temperature Report is enabled. |
64 | Humidity Report is enabled. |
128 | Luminance Report is enabled. |
Parameter 102: To set which report would be sent in Report group 2
To set which report would be sent in Report group 2.Note:You can also set
all sensor reports to be sent out at the same time. E.g. If you want the
batter report and temperature report to be sent out at the same time, you just
need to set the configuration value to 33 (1+32).
Size: 4 Byte, Default Value: 0
SettingDescription
1 | Battery Report is enabled. |
---|---|
16 | Ultraviolet Report is enabled. |
32 | Temperature Report is enabled. |
64 | Humidity Report is enabled. |
128 | Luminance Report is enabled. |
Parameter 103: To set which report would be sent in Report group 3
To set which report would be sent in Report group 3.Note:You can also set
all sensor reports to be sent out at the same time. E.g. If you want the
batter report and temperature report to be sent out at the same time, you just
need to set the configuration value to 33 (1+32).
Size: 4 Byte, Default Value: 0
SettingDescription
1 | Battery Report is enabled. |
---|---|
16 | Ultraviolet Report is enabled. |
32 | Temperature Report is enabled. |
64 | Humidity Report is enabled. |
128 | Luminance Report is enabled. |
Parameter 111: To set the interval time of sending reports in Report
group 1
To set the interval time of sending reports in Report group 1
Size: 4 Byte, Default Value: 3600
SettingDescription
5 – 2678400 | Available rang is 5 to 2678400 seconds. |
---|
Parameter 112: To set the interval time of sending reports in Report
group 2
To set the interval time of sending reports in Report group 2
Size: 4 Byte, Default Value: 3600
SettingDescription
5 – 2678400 | Available rang is 5 to 2678400 seconds. |
---|
Parameter 113: To set the interval time of sending reports in Report
group 3
To set the interval time of sending reports in Report group 3
Size: 4 Byte, Default Value: 3600
SettingDescription
5 – 2678400 | Available rang is 5 to 2678400 seconds. |
---|
Parameter 2: Enable/Disable waking up for 10 minutes when re-power on
(battery mode) the MultiSensor.
Enable/Disable waking up for 10 minutes when re-power on (battery mode) the
MultiSensor.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Disable |
---|---|
1 | Enable. |
Parameter 201: Temperature sensor calibration
Temperature sensor calibration.Note:1.High byte is the calibration value.
Low byte is the unit (0x01=Celsius, 0x02=Fahrenheit)2.The calibration value
(high byte) contains one decimal point. E.g. if the value is set to 20
(0x1401), the calibration value is 2.0(EU/AU version) or if the value is set
to 20 (0x1402), the calibration value is 2.0 (US version)3.The calibration
value (high byte) = standard value – measure value.E.g.If measure value =25.3
and the standard value = 23.2, so the calibration value= 23.2 – 25.3= -2.1
(0xEB).If the measure value =30.1 and the standard value = 33.2, so the
calibration value= 33.2 – 30.1=3.1 (0x1F).
Size: 2 Byte, Default Value: 0
SettingDescription
-128 – 127 | Available rang is -12.8 to 12.7. |
---|
Parameter 202: Humidity sensor calibration
Humidity sensor calibration.The calibration value = standard value – measure
value.E.g.If measure value =80RH and the standard value = 75RH, so the
calibration value= 75RH80RH= -5RH (0xFB).If the measure value =85RH and the
standard value = 90RH, so the calibration value= 90RH85RH=5RH (0x05).
Size: 1 Byte, Default Value: 0
SettingDescription
-50 – 50 | Available rang is -50RH to 50RH. |
---|
Parameter 203: Luminance sensor calibration
Luminance sensor calibration.The calibration value = standard value –
measure value.E.g.If measure value =800Lux and the standard value = 750Lux, so
the calibration value= 750800= -50 (0xFFCE).If the measure value =850Lux and
the standard value = 900Lux, so the calibration value= 900850=50 (0x0032)
Size: 2 Byte, Default Value: 0
SettingDescription
-1000 – 1000 | Available rang is -1000Lux to 1000Lux. |
---|
Parameter 204: Ultraviolet sensor calibration
Ultraviolet sensor calibration.The calibration value = standard value –
measure value.E.g.If measure value =9 and the standard value = 8, so the
calibration value= 89= -1 (0xFE).If the measure value =7 and the standard
value = 9, so the calibration value= 97=2 (0x02).
Size: 1 Byte, Default Value: 0
SettingDescription
-10 – 10 | Available rang is -10 to 10. |
---|
Parameter 252: Enable/disable all configuration parameters to be locked
Enable/disable all configuration parameters to be locked.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Disable |
---|---|
1 | Enable. |
Parameter 255: Reset to factory defaults.
Reset to factory defaults.
Size: 4 Byte, Default Value: 0
SettingDescription
1 | Reset all configuration parameters to factory defaults. |
---|---|
1431655765 | Reset the product to factory defaults. |
Parameter 3: Set the PIR time.
The default PIR time is 4 minutes. The Multisensor will send BASIC SET CC
(0x00) to the associated nodes if no motion is triggered again in 4 minutes.
Size: 2 Byte, Default Value: 240
SettingDescription
10 – 3600 | The range of PIR time is 10 to 3600. |
---|
Parameter 39: Configure the default low battery value.
Configure the default low battery value. When the current battery level is
lower than this value, it will send out the low battery alarm.
Size: 1 Byte, Default Value: 20
SettingDescription
10 – 50 | Available rang is 10% to 50%. |
---|
Parameter 4: Set the sensitivity of the motion sensor.
This parameter changes the sensitivity level of the motion detector.
Size: 1 Byte, Default Value: 5
SettingDescription
0 | Minimum Sensitivity |
---|---|
1 | Sensitivity Level 1 of 6 |
2 | Sensitivity Level 2 of 6 |
3 | Sensitivity Level 3 of 6 |
4 | Sensitivity Level 5 of 6 |
5 | Maximum Sensitivity |
Parameter 40: Enable/disable the selective reporting only when
measurements reach a certain threshold or percentage
Enable/disable the selective reporting only when measurements reach a
certain threshold or percentage. This is used to reduce network traffic.Note:
If USB power, the Sensor will check the threshold every 10 seconds. If battery
power, the Sensor will check the threshold when it is waken up.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Disable |
---|---|
1 | Enable. |
Parameter 41: Threshold change in temperature to induce an automatic
report.
Threshold change in temperature to induce an automatic report. Note:1.The
unit is Fahrenheit for US version, Celsius for EU/AU version.2.High byte is
the threshold value. Low byte is the unit (0x01=Celsius,
0x02=Fahrenheit).3.The threshold value (high byte) contains one decimal point.
E.g. if the value is set to 20 (0x001401), the threshold value =2.0(EU/AU
version) or if the value is set to 20 (0x001402), the threshold value= 2.0(US
version). When the current temperature gap is more then 2.0, which will induce
a temperature report to be sent out.
Size: 4 Byte, Default Value: 20
SettingDescription
10 – 2120 | Available rang of threshold is 1 to 212. |
---|
Parameter 42: Threshold change in humidity to induce an automatic report
Threshold change in humidity to induce an automatic report.Note:1.The unit
is %.2.The default value is 10, which means that if the current humidity gap
is more than 10%, it will send out a humidity report.
Size: 1 Byte, Default Value: 10
SettingDescription
1 – 100 | Available rang is 1% to 100%. |
---|
Parameter 43: Threshold change in luminance to induce an automatic
report.
Threshold change in luminance to induce an automatic report.
Size: 2 Byte, Default Value: 100
SettingDescription
1 – 30000 | Available rang is 1 LUX to 30000 LUX. |
---|
Parameter 44: Threshold change in battery level to induce an automatic
report.
Threshold change in battery level to induce an automatic report.Note:1.The
unit is %.2.The default value is 10, which means that if the current battery
level gap is more than 10%, it will send out a battery report.
Size: 1 Byte, Default Value: 10
SettingDescription
1 – 100 | Available rang is 1% to 100%. |
---|
Parameter 45: Threshold change in ultraviolet to induce an automatic
report.
Threshold change in ultraviolet to induce an automatic report.
Size: 1 Byte, Default Value: 2
SettingDescription
1 – 11 | Available rang is 1 to 11. |
---|
Parameter 46: Enable/disable to send the alarm report of low temperature
Enable/disable to send the alarm report of low temperature( <-15).Note:If it
is enabled, the MultiSensor will send a report of Multi Level Temperature CC
to controller when the current temperature is less than -15).
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Disable |
---|---|
1 | Enable. |
1 – 30000 | Available rang is 1LUX to 30000LUX. |
Parameter 48: Enable/disable to send a report when the measurement is
more than the upper limit value or less than the lower limit value.
Enable/disable to send a report when the measurement is more than the upper
limit value or less than the lower limit value.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Disable |
---|---|
1 | Enable. |
Parameter 49: Set the upper limit value of temperature sensor.
Set the upper limit value of temperature sensor.When the measurement is more
than this upper limit, which will trigger to sent out a sensor report.
Size: 4 Byte, Default Value: 824
SettingDescription
-400 – 2120 | Available rang is -40.0 to 212.0. |
---|
Parameter 5: Which command would be sent when the motion sensor
triggered.
To set which command would be sent when the motion sensor triggered.
Size: 1 Byte, Default Value: 1
SettingDescription
1 | Send Basic Set CC |
---|---|
2 | Send Sensor Binary Report CC |
Parameter 50: Set the lower limit value of temperature sensor.
Set the lower limit value of temperature sensor. When the measurement is
less than this lower limit, which will trigger to sent out a sensor
report.High byte is the lower limit value.
Size: 4 Byte, Default Value: 320
SettingDescription
-400 – 2120 | Available rang is -40.0 to 212.0. |
---|
Parameter 51: Set the upper limit value of humidity sensor.
Set the upper limit value of humidity sensor. when the measurement is more
than this upper limit, which will trigger to sent out a sensor report.
Size: 1 Byte, Default Value: 60
SettingDescription
0 – 100 | Available rang is 0% to 100%. |
---|
Parameter 52: Set the lower limit value of humidity sensor.
Set the lower limit value of humidity sensor. When the measurement is less
than this lower limit, which will trigger to sent out a sensor report.
Size: 1 Byte, Default Value: 50
SettingDescription
0 – 100 | Available rang is 0% to 100%. |
---|
Parameter 53: Set the upper limit value of Lighting sensor
Set the upper limit value of Lighting sensor. When the measurement is more
than this upper limit, which will trigger to sent out a sensor report.
Size: 1 Byte, Default Value: 1000
SettingDescription
0 – 30000 | Available rang is 0 to 30000LUX. |
---|
Parameter 54: Set the lower limit value of Lighting sensor.
Set the lower limit value of Lighting sensor. When the measurement is less
than this lower limit, which will trigger to sent out a sensor report.
Size: 1 Byte, Default Value: 100
SettingDescription
0 – 30000 | Available rang is 0 to 30000LUX. |
---|
Parameter 55: Set the upper limit value of ultraviolet sensor.
Set the upper limit value of ultraviolet sensor. When the measurement is
more than this upper limit, which will trigger to sent out a sensor report.
Size: 1 Byte, Default Value: 8
SettingDescription
1 – 11 | Available rang is 1 to 11. |
---|
Parameter 56: Set the lower limit value of ultraviolet sensor.
Set the lower limit value of ultraviolet sensor. When the measurement is
less than this upper limit, which will trigger to sent out a sensor report.
Size: 1 Byte, Default Value: 4
SettingDescription
1 – 11 | Available rang is 1 to 11. |
---|
Parameter 57: Set the recover limit value of temperature sensor.
Note:1.When the current measurement <= (Upper limitRecover limit), the upper
limit report is enabled and then it would send out a sensor report when the
next measurement is more than the upper limit. After that the upper limit
report would be disabled again until the measurement = (Lower limit + Recover
limit), the lower limit report is enabled and then it would send out a sensor
report when the next measurement is less than the lower limit. After that the
lower limit report would be disabled again until the measurement >= (Lower
limit + Recover limit).3.High byte is the recover limit value. Low byte is the
unit (0x01=Celsius, 0x02=Fahrenheit).
Size: 2 Byte, Default Value: 20
SettingDescription
10 – 255 | Available rang is 1.0 to 25.5 |
---|
Parameter 58: Set the recover limit value of humidity sensor.
Set the recover limit value of humidity sensor.Note:1.When the current
measurement <= (Upper limitRecover limit), the upper limit report is enabled
and then it would send out a sensor report when the next measurement is more
than the upper limit. After that the upper limit report would be disabled
again until the measurement = (Lower limit + Recover limit), the lower limit
report is enabled and then it would send out a sensor report when the next
measurement is less than the lower limit. After that the lower limit report
would be disabled again until the measurement >= (Lower limit + Recover
limit).
Size: 1 Byte, Default Value: 5
SettingDescription
1 – 50 | Available rang is 1 to 50% |
---|
Parameter 59: Set the recover limit value of Lighting sensor.
Set the recover limit value of Lighting sensor.Note:1.When the current
measurement <= (Upper limitRecover limit), the upper limit report is enabled
and then it would send out a sensor report when the next measurement is more
than the upper limit. After that the upper limit report would be disabled
again until the measurement = (Lower limit + Recover limit), the lower limit
report is enabled and then it would send out a sensor report when the next
measurement is less than the lower limit. After that the lower limit report
would be disabled again until the measurement >= (Lower limit + Recover
limit).3.Unit = 10Recover limit (Lux)
Size: 1 Byte, Default Value: 100
SettingDescription
1 – 127 | Available rang is 10Lux to 1270Lux |
---|
Parameter 60: Set the recover limit value of Ultraviolet sensor.
Set the recover limit value of Ultraviolet sensor.Note:1.When the current
measurement <= (Upper limitRecover limit), the upper limit report is enabled
and then it would send out a sensor report when the next measurement is more
than the upper limit. After that the upper limit report would be disabled
again until the measurement = (Lower limit + Recover limit), the lower limit
report is enabled and then it would send out a sensor report when the next
measurement is less than the lower limit. After that the lower limit report
would be disabled again until the measurement >= (Lower limit + Recover
limit).
Size: 1 Byte, Default Value: 2
SettingDescription
0 | USB power mode |
---|---|
1 – 5 | Available rang is 1 to 5. |
256 | Keep sleep state for Battery power mode |
257 | Keep awake for 10 minutes for battery power mode. |
Parameter 61: Get the out-of-limit state of the Sensors.
Get the out-of-limit state of the Sensors.
Size: 2 Byte, Default Value: 0
SettingDescription
1 | Temperature sensor is out of the lower limit |
---|---|
2 | Humidity sensor is out of the lower limit |
4 | Luminance sensor is out of the lower limit |
8 | Ultraviolet sensor is out of the lower limit |
16 | Temperature sensor is out of the upper limit |
32 | Humidity sensor is out of the upper limit |
64 | Luminance sensor is out of the upper limit |
128 | Ultraviolet sensor is out of the upper limit |
Parameter 64: Set the default unit of the automatic temperature report in
parameter 101-103.
Set the default unit of the automatic temperature report in parameter
101-103.
Size: 1 Byte, Default Value: 2
SettingDescription
1 | The unit is Celsius. |
---|---|
2 | The unit is Fahrenheit. |
Parameter 8: Set the timeout of awake after the Wake Up CC is sent out..
Set the timeout of awake after the Wake Up CC is sent out..
Size: 1 Byte, Default Value: 30
SettingDescription
8 – 127 | Available rang is 8 to 127 seconds. |
---|
Parameter 81: Enable/disable the LED blinking when the PIR is triggered.
Enable/disable the LED blinking when the PIR is triggered.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Enable. |
---|---|
1 | Disable |
Parameter 9: Report the current power mode and the product state for
battery power mode
Report the current power mode and the product state for battery power
mode.Note: this parameter cannot be used as Set usage.
Size: 2 Byte, Default Value: 0
SettingDescription
0 | USB power mode |
---|---|
256 | Keep sleep state for Battery power mode |
257 | Keep awake for 10 minutes for battery power mode. |
Technical Data
Hardware Platform | ZM5101 |
---|---|
Device Type | Notification Sensor |
Network Operation | Reporting Sleeping Slave |
Firmware Version | HW: 100 FW: 1.10 |
Z-Wave Version | 6.51.10 |
Certification ID | ZC10-17115845 |
Z-Wave Product Id | 0x0086.0x0102.0x0064 |
Sensors | Air TemperatureHumidityLuminanceMotion/No Motion (Binary)Ultraviolet |
IndexVibration/Shock (Binary)
Supported Notification Types| Home Security
IP (Ingress Protection) Rated| ok
Firmware Updatable| Updatable by Consumer by RF
Frequency| XXfrequency
Maximum transmission power| XXantenna
Supported Command Classes
- Association Grp Info
- Association V2
- Basic
- Battery
- Configuration
- Device Reset Locally
- Firmware Update Md V2
- Manufacturer Specific V2
- Notification V3
- Powerlevel
- Security
- Sensor Binary
- Sensor Multilevel V5
- Version V2
- Wake Up V2
- Zwaveplus Info V2
Controlled Command Classes
- Basic
Explanation of Z-Wave specific terms
-
Controller — is a Z-Wave device with capabilities to manage the network.
Controllers are typically Gateways,Remote Controls or battery operated wall controllers. -
Slave — is a Z-Wave device without capabilities to manage the network.
Slaves can be sensors, actuators and even remote controls. -
Primary Controller — is the central organizer of the network. It must be
a controller. There can be only one primary controller in a Z-Wave network. -
Inclusion — is the process of adding new Z-Wave devices into a network.
-
Exclusion — is the process of removing Z-Wave devices from the network.
-
Association — is a control relationship between a controlling device and
a controlled device. -
Wakeup Notification — is a special wireless message issued by a Z-Wave
device to announces that is able to communicate. -
Node Information Frame — is a special wireless message issued by a
Z-Wave device to announce its capabilities and functions.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>