Qubino Flush Heat & Cool Thermostat GOAEZMNHKD1 Manual
- June 8, 2024
- QUBINO
Table of Contents
- Qubino
- Flush Heat & Cool Thermostat
- SKU: GOAEZMNHKD1
- Quickstart
- Important safety information
- What is Z-Wave?
- Product Description
- Prepare for Installation / Reset
- Installation
- Inclusion/Exclusion
- Quick trouble shooting
- Association – one device controls an other device
- Configuration Parameters
- Parameter 1: Input I1 switch type
- Parameter 2: Input I2 switch type
- Parameter 4: Input 1 contact type
- Parameter 5: Input 2 contact type
- Parameter 10: Activate / deactivate functions ALL ON / ALL OFF
- Parameter 11: I1 Functionality selection
- Parameter 12: I2 Functionality selection
- Parameter 40: Power reporting in Watts on power change
- Parameter 42: Power reporting in Watts by time interval
- Parameter 43: Hysteresis Heating On
- Parameter 44: Hysteresis Heating Off
- Parameter 45: Hysteresis Cooling On
- Parameter 46: Hysteresis Cooling Off
- Parameter 47: Antifreeze
- Parameter 60: Too low temperature limit
- Parameter 61: Too high temperature limit
- Parameter 64: Output Switch selection Q1
- Parameter 65: Output Switch selection Q2
- Parameter 70: – Input 1 status on delay
- Parameter 71: Input 1 status off delay
- Parameter 72: – Input 2 status on delay
- Parameter 73: Input 2 status off delay
- Parameter 100: Enable / Disable Endpoint I1 or select Notification Type
- Parameter 101: Enable / Disable Endpoint I2 or select Notification Type
- Parameter 110: Temperature sensor offset settings
- Parameter 120: Digital temperature sensor reporting
- Parameter 121: Digital temperature sensor / setpoint selector
- Parameter 122: Node ID of external battery powered room sensor
- Technical Data
- Supported Command Classes
- Controlled Command Classes
- Explanation of Z-Wave specific terms
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Qubino
Flush Heat & Cool Thermostat
SKU: GOAEZMNHKD1
Quickstart
This is a ****
Thermostat
for
Europe.
To run this device please connect it to your mains power supply.
To add this device to your network execute the following action:
- press service button S for more than 2 second or
- press push button I1 three times within 3s (3 times change switch state within 3 seconds).
Important safety information
Please read this manual carefully. Failure to follow the recommendations in
this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any
loss or damage resulting from failure to comply with the instructions in this
manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal
instructions.
Do not dispose of electronic equipment or batteries in a fire or near open heat sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart
Home. This
device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message ( two-
way
communication) and every mains powered node can act as a repeater for other
nodes
( meshed network ) in case the receiver is not in direct wireless range of
the
transmitter.
This device and every other certified Z-Wave device can be used together
with any other
certified Z-Wave device regardless of brand and origin as long as both are
suited for the
same frequency range.
If a device supports secure communication it will communicate with other
devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to
maintain
backward compatibility.
For more information about Z-Wave technology, devices, white papers etc.
please refer
to www.z-wave.info.
Product Description
This Z-Wave module is used to regulate temperature in heating and cooling mode. Module can be controlled either through Z-Wave network or through the wall switch. The module is designed to be mounted inside a “flush mounting box” and is hidden behind a traditional wall switch. Module measures power consumption of connected device. It is designed to act as repeater in order to improve range and stability of Z-wave network.
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory
default
state. Please make sure to reset the device into factory default. You can do
this by
performing an Exclusion operation as described below in the manual. Every
Z-Wave
controller is able to perform this operation however it is recommended to use
the primary
controller of the previous network to make sure the very device is excluded
properly
from this network.
Reset to factory default
This device also allows to be reset without any involvement of a Z-Wave
controller. This
procedure should only be used when the primary controller is inoperable.
- press service button S for more than 6 second or
- press push button I1 five times within 3s ( 5 times change switch state within 3 seconds) in the first 60 seconds after the module is connected to the power supply.
Safety Warning for Mains Powered Devices
ATTENTION: only authorized technicians under consideration of the country-
specific
installation guidelines/norms may do works with mains power. Prior to the
assembly of
the product, the voltage network has to be switched off and ensured against
re-switching.
Installation
– To prevent electrical shock and/or equipment damage, disconnect electrical
power at the main fuse or circuit breaker before installation or any
servicing.
– Make sure, that no voltage is present in the installation.
– Prevent the disconnecting device from being switched on accidentally.
– Connect the module according to electrical diagram.
– Locate the antenna far from metal elements (as far as possible).
– Do not shorten the antenna.
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The
device needs
to be added to an existing wireless network to communicate with the
devices of this network.
This process is called Inclusion.
Devices can also be removed from a network. This process is called
Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network.
This
controller is turned into exclusion respective inclusion mode. Inclusion and
Exclusion is
then performed doing a special manual action right on the device.
Inclusion
- press service button S for more than 2 second or
- press push button I1 three times within 3s (3 times change switch state within 3 seconds).
Exclusion
- press service button S for more than 6 second or
- press push button I1 five times within 3s ( 5 times change switch state within 3 seconds) in the first 60 seconds after the module is connected to the power supply.
Auto-Inclusion
Beside the standard inclusion this devices supports the so called auto
inclusion.
Right after powering up the device remains in inclusion state and can be
included by
(any) gateway without further actions on the device itself. The auto inclusion
mode will
time out after some time.
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
- Make sure a device is in factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Dont poll FLIRS devices.
- Make sure to have enough mains powered device to benefit from the meshing
Association – one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one
device
controlling another device is called association. In order to control a
different
device, the controlling device needs to maintain a list of devices that will
receive
controlling commands. These lists are called association groups and they are
always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’
Command.
Association Groups:
Group NumberMaximum NodesDescription
1 | 1 | Lifeline |
---|---|---|
2 | 16 | Basic on/off (triggered at change of the output Q state and reflecting |
its state)
3| 16| SENSOR_MULTILEVEL_GET (triggered once per minute if Parameter 121 is
not 0)
4| 16| Basic on/off (triggered by Too high temperature limit, it send FF)
5| 16| THERMOSTAT_SETPOINT_GET (triggered once per minute if Parameter 121 is
not 0)
6| 16| Basic on/off (trigged by change of I1 if window sensor functionality is
selected by parameter no. 11)
7| 16| Basic on/off (trigged by change of I2 if condense sensor functionality
is selected by parameter no. 12)
9| 16| Sensor multilevel report (trigged by change of temperature)
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock
further
enhanced features.
IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200âit may be needed to set a value of 200 minus 256 = minus
56.
In case of a two byte value the same logic applies: Values greater than 32768
may
needed to be given as negative values too.
Parameter 1: Input I1 switch type
__
Size: 1 Byte, Default Value: 1
SettingDescription
0 | mono-stable switch type (push button) |
---|---|
1 | bi-stable switch type |
Parameter 2: Input I2 switch type
__
Size: 1 Byte, Default Value: 1
SettingDescription
0 | mono-stable switch type (push button) |
---|---|
1 | bi-stable switch type |
Parameter 4: Input 1 contact type
NOTE: This parameter has influence only when parameter no. 11 is set to the
value “2”. After setting this parameter, switch the window sensor once, so
that the module could determine the input state
Size: 1 Byte, Default Value: 0
SettingDescription
0 | NO (normally open) input type |
---|---|
1 | NC (normally close) input type |
Parameter 5: Input 2 contact type
NOTE: This parameter has influence only when parameter no. 12 is set to the
value “2000”. After setting this parameter, switch the condense sensor once,
so that the module could determine the input state.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | NO (normally open) input type |
---|---|
1 | NC (normally close) input type |
Parameter 10: Activate / deactivate functions ALL ON / ALL OFF
Flush Heat & Cool thermostat module responds to commands ALL ON / ALL OFF
that may be sent by the main controller or by other controller belonging to
the system.
Size: 2 Byte, Default Value: 255
SettingDescription
255 | ALL ON active, ALL OFF active. |
---|---|
0 | ALL ON is not active, ALL OFF is not active |
1 | ALL ON is not active, ALL OFF active |
2 | ALL ON active, ALL OFF is not active |
Parameter 11: I1 Functionality selection
__
Size: 2 Byte, Default Value: 1
SettingDescription
1| input I1 changes the mode of the thermostat between Off and Heat/Cool. In
this case function on window sensor is disabled
---|---
2| input I1 influences on heating/cooling valves according to status of window
sensor. In this case function of Off and Heat/Cool selection by I1 is disabled
32767| input I1 doesn’t influence on the Heat/Cool process
Parameter 12: I2 Functionality selection
__
Size: 2 Byte, Default Value: 32676
SettingDescription
0 – 990| Temperature set point from 0.0 °C to 99.0 °C. When I2 is pressed, it
automatically set temperature setpoint according to value defined here. In
this case function of condense sensor is disabled
---|---
1001 – 1050| Temperature set point from -0.1 °C to -15.0 °C. When I2 is
pressed, it automatically set temperature setpoint according to value defined
here. In this case function of condense sensor is disabled
2000| Input I2 influences on the cooling valve according to status of condense
sensor, In this case function of setpoint selection with I2 is disabled
32767| input I2 does not influence on the Heat/Cool process
Parameter 40: Power reporting in Watts on power change
Set value means percentage, set value from 0 – 100=0% – 100%.
NOTE: if power changed is less than 1W, the report is not send (pushed),
independent of percentage set.
Size: 1 Byte, Default Value: 5
SettingDescription
0 | reporting disabled |
---|---|
1 – 100 | 1% – 100% Reporting enabled. Power report is send (push) only when |
actual power in Watts in real time changes for more than set percentage comparing to previous actual power in Watts, step is 1%.
Parameter 42: Power reporting in Watts by time interval
Set value means time interval (0 – 32767) in seconds, when power report is
send.
Size: 2 Byte, Default Value: 0
SettingDescription
0 | reporting disabled |
---|---|
1 – 32767 | 1 second – 32767 seconds. Reporting enabled. Power report is send |
with time interval set by entered value. Please note, that too fast reporting can cause too much Z-Wave traffic resulting in Z-Wave poor response
Parameter 43: Hysteresis Heating On
This parameter defines temperature min difference between real measured
temperature and set-point temperature to turn device on
Size: 2 Byte, Default Value: 1005
SettingDescription
0 – 127 | 0.0 °C … 12.7 °C |
---|---|
1001 – 1127 | -0.1°C ~ -12.7 °C |
Parameter 44: Hysteresis Heating Off
This parameter defines temperature min difference between real measured
temperature and set-point temperature to turn device off.
Size: 2 Byte, Default Value: 5
SettingDescription
0 – 127 | 0.0 °C – 12.7 °C |
---|---|
1001 – 1127 | -0.1 °C ~ -12.7 °C |
Parameter 45: Hysteresis Cooling On
This parameter defines temperature difference between measured temperature
and set-point temperature to turn cooling on
Size: 2 Byte, Default Value: 5
SettingDescription
0 – 127 | 0.0°C to 12.7 °C |
---|---|
1001 – 1127 | – 0.1°C to – 12.7 °C |
Parameter 46: Hysteresis Cooling Off
This parameter defines temperature difference between measured temperature
and set-point temperature to turn cooling off
Size: 2 Byte, Default Value: 1002
SettingDescription
0 – 127 | 0.0°C to 12.7 °C |
---|---|
1001 – 1127 | – 0.1°C to – 12.7 °C |
Parameter 47: Antifreeze
Set value means at which temperature the device will be turned on even if
the thermostat was manually set to off. NOTE: Antifreeze is activated only in
heating mode and it uses hysteresis from Par.34 and Par.44
Size: 2 Byte, Default Value: 50
SettingDescription
0 – 127 | 0.0 °C – 12.7 °C |
---|---|
1001 – 1127 | -0.1°C ~ -12.6 °C |
255 | Antifreeze functionality disabled |
Parameter 60: Too low temperature limit
Too low temperature limit is set by entered value. In case is set value out
of this range, module is changing set value automatically to default value
Size: 2 Byte, Default Value: 50
SettingDescription
1 – 1000 | 0.1°C to 100.0°C, step is 0.1°C |
---|---|
1001 – 1150 | -0.1°C to -15.0°C |
Parameter 61: Too high temperature limit
Too high temperature limit is set by entered value. In case the set value is
out of this range, module is changing automatically set value to default
value.
Size: 2 Byte, Default Value: 700
SettingDescription
1 – 1000 | 0.1°C – 100.0°C, step is 0.1°C. |
---|
Parameter 64: Output Switch selection Q1
Set value means the type of the device that is connected to the Q1 output.
The device type can be normally open (NO) or normally close (NC)
Size: 1 Byte, Default Value: 0
SettingDescription
0 | When system is turned off the output is 0 V |
---|---|
1 | When system is turned off the output is 230 V |
Parameter 65: Output Switch selection Q2
Set value means the type of the device that is connected to the Q2 output.
The device type can be normally open (NO) or normally close (NC)
Size: 1 Byte, Default Value: 0
SettingDescription
0 | When system is turned off the output is 0 V |
---|---|
1 | When system is turned off the output is 230 V |
Parameter 70: – Input 1 status on delay
If the value of parameter is different to 0, means that the Influence of
this input to heating or cooling will react after inserted time. This
parameter has influence only when the window sensor functionality is selected
by the parameter no. 11.
NOTE: Device status on UI change immediately
Size: 2 Byte, Default Value: 0
SettingDescription
1 – 32000 | seconds |
---|
Parameter 71: Input 1 status off delay
If the value of parameter is different to 0, means that the Influence of
this input to heating or cooling will react after inserted time. This
parameter has influence only when the window sensor functionality is selected
by the parameter no. 11.
NOTE: Device status on UI change immediately
Size: 2 Byte, Default Value: 0
SettingDescription
1 – 32000 | seconds |
---|
Parameter 72: – Input 2 status on delay
If the value of parameter is different to 0, means that the Influence of
this input to heating or cooling will react after inserted time. This
parameter has influence only when the window sensor functionality is selected
by the parameter no. 12.
NOTE: Device status on UI change immediately
Size: 2 Byte, Default Value: 0
SettingDescription
1 – 32000 | seconds |
---|
Parameter 73: Input 2 status off delay
If the value of parameter is different to 0, means that the Influence of
this input to heating or cooling will react after inserted time. This
parameter has influence only when the window sensor functionality is selected
by the parameter no. 12.
NOTE: Device status on UI change immediately
Size: 2 Byte, Default Value: 0
SettingDescription
1 – 32000 | seconds |
---|
Parameter 100: Enable / Disable Endpoint I1 or select Notification Type
and Event
Enabling I1 means that Endpoint (I1) will be present on UI. Disabling it
will result in hiding the endpoint according to the parameter set value.
Additionally, a Notification Type and Event can be selected for the endpoint.
Available configuration parameters (data type is 1 Byte DEC): Endpoint device
type selection: – notification sensor (1 – 6):
NOTE1: After parameter change, first exclude module (without setting
parameters to default value) and then re include the module!
NOTE2: When the parameter is set to value 9 the notifications are send for
Home Security.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Endpoint, I1 disabled |
---|---|
1 | Home Security; Motion Detection, unknown location. |
2 | CO; Carbon Monoxide detected, unknown location. |
3 | CO2; Carbon Dioxide detected, unknown location. |
4 | Water Alarm; Water Leak detected, unknown location. |
5 | Heat Alarm; Overheat detected, unknown location |
6 | Smoke Alarm; Smoke detected, unknown location. |
9 | Sensor binary |
Parameter 101: Enable / Disable Endpoint I2 or select Notification Type
and Event
Enabling I2 means that Endpoint (I2) will be present on UI. Disabling it
will result in hiding the endpoint according to the parameter set value.
Additionally, a Notification Type and Event can be selected for the endpoint.
Available configuration parameters (data type is 1 Byte DEC): Endpoint device
type selection: – notification sensor (1 – 6):
NOTE1: After parameter change, first exclude module (without setting
parameters to default value) and then re include the module!
NOTE2: When the parameter is set to value 9 the notifications are send for
Home Security.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Endpoint, I1 disabled |
---|---|
1 | Home Security; Motion Detection, unknown location. |
2 | CO; Carbon Monoxide detected, unknown location. |
3 | CO2; Carbon Dioxide detected, unknown location. |
4 | Water Alarm; Water Leak detected, unknown location. |
5 | Heat Alarm; Overheat detected, unknown location |
6 | Smoke Alarm; Smoke detected, unknown location. |
9 | Sensor binary |
Parameter 110: Temperature sensor offset settings
Set value is added or subtracted to actual measured value by sensor.
Size: 2 Byte, Default Value: 32536
SettingDescription
1 – 100 | value from 0.1 °C to 10.0 °C is added to actual measured temperature. |
---|---|
1001 – 1100 | value from -0.1 °C to -10.0 °C is subtracted to actual measured |
temperature.
Parameter 120: Digital temperature sensor reporting
If digital temperature sensor is connected, module reports measured
temperature on temperature change defined by this parameter.
Size: 1 Byte, Default Value: 5
SettingDescription
0 | reporting disabled |
---|---|
1 – 127 | 0,1°C – 12,7°C, step is 0,1°C |
Parameter 121: Digital temperature sensor / setpoint selector
If digital temperature sensor is not connected, module can grab measured
temperature from external secondary module.
Size: 1 Byte, Default Value: 0
SettingDescription
0| internal digital temperature sensor is mounted, setpoint is set by
controller
---|---
1| (bit 0) temperature is grabbed from external always on sensor with
sensor_multilevel_get sent by association 3
2| (bit 1) temperature is grabbed from external battery powered room sensor
declared in parameter 122
3| (bit 2) setpoint is grabbed from external always on module with
thermostat_setpoint_get sent by association 5
8| (bit 3) setpoint is grabbed from external battery powered room sensor
declared in parameter 122.
10| (bit 1 and bit 3) temperature AND setpoint are grabbed from external
battery powered room sensor declared in parameter 122
Parameter 122: Node ID of external battery powered room sensor
_If digital temperature sensor is not connected, module can grab measured
temperature from external battery powered room sensor defined by this
parameter.
NOTE: Get sensor nodeid from controller and set parameter 122 immediately
after sensor weak up (after button press on it etc.)
Size: 1 Byte, Default Value: 0
SettingDescription
0 | external battery powered room sensor not in function |
---|---|
1 – 254 | Node ID of external battery powered room sensor |
Technical Data
Dimensions | 42mm x 37mm x 17mm mm |
---|---|
Weight | 46.91 gr |
Hardware Platform | ZM5202 |
EAN | 3830062070140 |
IP Class | IP 20 |
Voltage | 230 V |
Load | 920 Watt |
Device Type | Thermostat |
Firmware Version | 03.01 |
Z-Wave Version | 04.05 |
Z-Wave Product Id | 0x0159.0x0005.0x0052 |
Frequency | Europe – 868,4 Mhz |
Maximum transmission power | 5 mW |
Supported Command Classes
- Basic
- Switch All
- Sensor Multilevel
- Meter
- Thermostat Mode
- Thermostat Setpoint
- Association Grp Info
- Device Reset Locally
- Zwaveplus Info
- Configuration
- Manufacturer Specific
- Powerlevel
- Association
- Version
- Multi Channel Association
Controlled Command Classes
- Basic
Explanation of Z-Wave specific terms
-
Controller — is a Z-Wave device with capabilities to manage the network.
Controllers are typically Gateways,Remote Controls or battery operated wall controllers. -
Slave — is a Z-Wave device without capabilities to manage the network.
Slaves can be sensors, actuators and even remote controls. -
Primary Controller — is the central organizer of the network. It must be
a controller. There can be only one primary controller in a Z-Wave network. -
Inclusion — is the process of adding new Z-Wave devices into a network.
-
Exclusion — is the process of removing Z-Wave devices from the network.
-
Association — is a control relationship between a controlling device and
a controlled device. -
Wakeup Notification — is a special wireless message issued by a Z-Wave
device to announces that is able to communicate. -
Node Information Frame — is a special wireless message issued by a
Z-Wave device to announce its capabilities and functions.