Qubino Smart Meter GOAEZMNHTD1 Manual

June 8, 2024
QUBINO

Qubino

Smart Meter

SKU: GOAEZMNHTD1

Quickstart

This is a
secure
Smart Meter
for
Europe
.

To run this device please connect it to your mains power supply.

To add this device to your network execute the following action:
– press service button” S” for more than 2 second

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

This Z-Wave module is used for energy measurements in single-phase electrical power network and can be used in residential, industrial and utility applications. Meters measure energy directly in 2-wire networks according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates energy, power and power factor from the measured signals. The module can be controlled through Z-wave network and it acts as repeater in order to improve range and stability of Z-wave network. It is designed to be mounted on DIN rail.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

– press service button S” for more than 6 second

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country- specific
installation guidelines/norms may do works with mains power. Prior to the assembly of
the product, the voltage network has to be switched off and ensured against re-switching.

Installation

– To prevent electrical shock and/or equipment damage, disconnect electrical power: remove main fuse or put on OFF position a main disconnection switch (or circuit breaker if it is compliant to standard IEC947-2), before installation or any servicing.
– Make sure, that no voltage is present in the installation.
– Prevent the disconnecting device from being switched on accidentally.
– Connect the module according to electrical diagram.
– Locate the antenna far from metal elements (as far as possible).
– Do not shorten the antenna

Notes for the diagram:

LI Live input
NI Neutral input
Lo Live output
No Neutral output
1 Input for IR external relay/Ext. relay
2 Neutral lead for input
4 Live lead for External relay output
5 Output for External relay (max. 3W)
S Service button (used to add or remove module from the Z-Wave network).
LED1 Green – Power on (solid) / no ID (blinking slow 1s) / Inc./Exc. mode (blinking fast 0,5s)
LED2 Yellow on – output on (any) / Yellow off – outputs off (both)
IR Output for IR external relay
1imp/Wh Red – Pulse rate (On – no load indication)”

External relays

It is possible to connect two external relay to Smart Meter module. One controlled by built-in optical (IR) communication port on the side, second controlled by output on terminal 5.”

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

– press service button” S” for more than 2 second

Exclusion

– press service button S for more than 2″ second (not all Parameters are reset)

Auto-Inclusion

Beside the standard inclusion this devices supports the so called auto inclusion.
Right after powering up the device remains in inclusion state and can be included by
(any) gateway without further actions on the device itself. The auto inclusion mode will
time out after some time.

Product Usage

LED SIGNALIZATION FOR INCLUSION/EXCLUSION

LED1 (Green)

– LED is ON = Power ON, module is included

– LED is 1s OFF, 1s ON = Power ON, module is excluded

LED2 (Yellow)

a. External IR relay enabled only

– LED is ON = External IR relay is turned ON

– LED is OFF = External IR relay is turned OFF

– LED is 0.5s OFF, 0.5s ON = IR communication error

b. External TRIAC relay enabled only

– LED is ON = External IR relay is turned ON

– LED is OFF = External IR relay is turned OFF

c. Both TRIAC and IR enabled

– LED is ON = External IR relay is turned ON

– LED is OFF = External IR relay is turned OFF

– LED is 0.5s OFF, 0.5s ON = IR communication error

d. External IR relay disabled

– LED is ON = modbus packet is sent

– LED is OFF = modbus packet is received

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1 1 Lifeline

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 7: Input 1 switch function selection

__
Size: 1 Byte, Default Value: 4

SettingDescription

0 disabled
2 IR external relay control – mono stable push button
3 IR external relay control – bi stable switch
4 External relay control – mono stable push button
5 External relay control – bi stable switch

Parameter 10: Activate / deactivate functions ALL ON / ALL OFF

Only for older Version!
Size: 2 Byte, Default Value: 255

SettingDescription

255 ALL ON active, ALL OFF active.
0 ALL ON is not active, ALL OFF is not active
1 ALL ON is not active, ALL OFF active
2 ALL ON active, ALL OFF is not active DIN Dimmer module responds to commands

ALL ON / ALL OFF that may be sent by the main controller or by other controller belonging to the system.

Parameter 11: Automatic turning off IR external relay output after set

time

When IR external relay is ON it goes automatically OFF after time defined by this Parameter. Timer is reset to zero each time the module receive ON command regardless from where it comes (push button, associated module, controller,..)
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 59 Auto OFF disabled
60 – 32535 Auto OFF enabled with define time, step is 1s

Parameter 12: Automatic turning on IR external relay output after set

time

When IR external relay is OFF it goes automatically ON after time defined by this Parameter. Timer is reset to zero each time the module receive OFF command regardless from where it comes (push button, associated module, controller,..).
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 59 Auto ON disabled
60 – 32535 Auto ON enabled with define time, step is 1s.

Parameter 13: Automatic turning off External relay output after set time

When External relay is ON it goes automatically OFF after time defined by this parameter. Timer is reset to zero each time the module receive ON command regardless from where it comes (push button, associated module, controller,..).
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 59 Auto OFF disabled
60 – 32535 Auto OFF enabled with define time, step is 1s

Parameter 14: Automatic turning on External relay after output set time

When External relay is OFF it goes automatically ON after time defined by this parameter. Timer is reset to zero each time the module receive OFF command regardless from where it comes (push button, associated module, controller,..).
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 59 Auto ON disabled
60 – 32535 Auto ON enabled with define time, step is 1s

Parameter 40: Power reporting in Watts on power change

Set value means percentage, set value from 0 – 100=0% – 100%.” NOTE: if power changed is less than 1W, the report is not send (pushed), independent of percentage set.
Size: 1 Byte, Default Value: 5

SettingDescription

0 reporting disabled
1 – 100 1% – 100% Reporting enabled. Power report is send (push) only when

actual power in Watts in real time changes for more than set percentage comparing to previous actual power in Watts, step is 1%.

Parameter 42: Power reporting in Watts by time interval

Set value means time interval (0 – 32767) in seconds, when power report is send.
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 59 reporting disabled
60 – 32767 Reporting enabled. Power report is send with time interval set by

entered value. Please note, that too fast reporting can cause too much Z-Wave traffic resulting in Z-Wave poor response

Parameter 45: Reset Power counters

__
Size: 1 Byte, Default Value: 0

SettingDescription

0 no function
1 reset counter 1 – KWh
2 reset counter 2 – kVARh
4 reset counter 3 – kVAh
15 reset ALL counters

Parameter 100: Enable / Disable endpoints IR external relay and External

relay

Enabling IR external relay and External relay or both of them, means that endpoint (IR external relay) and endpoint (External relay) or both will be present on UI. Disabling them will result in hiding endpoints according to Parameter set value. Note that hiding endpoint has no impact on its functionality.NOTE1: After parameter change, first exclude module (without setting parameters to default value) and then re include the module.” NOTE2: If you dont have IR BiComm relay module mounted and you enable IR communication (parameter 100 is 2 or 3) there will be no valid IR relay state reported. It will be reported IR COMMUNICATION ERROR and LED2 will BLINK.
Size: 1 Byte, Default Value: 0

SettingDescription

0 Endpoints IR external relay and External relay disabled
1 Endpoints IR external relay disabled, External relay enabled
2 Endpoints IR external relay enabled, External relay disabled
3 Endpoints IR external relay and External relay enabled

Parameter 110: Maximum Power auto off

Set value means Maximum Power Consumption (0 – 15000) in watts (W), when relays are turned off according to parameters no. 111 and 112.
Size: 2 Byte, Default Value: 0

SettingDescription

0 no function
1 – 15000 1 W – 15000 W Maximum Power Consumption.

Parameter 111: – Delay overpower off

Set value means number of second to power off relay (defined by parameters no. 110 and 112) before restart (30 – 32535) in seconds (s)
Size: 2 Byte, Default Value: 30

SettingDescription

30 – 32535 30 s – 32535 s delay

Parameter 112: Relay to power off

Set value selects relay to be powered off when threshold is reached (defined by parameters no. 110 and 111).
Size: 1 Byte, Default Value: 0

SettingDescription

0| switch between the 2 relays (power off relay 1 first, after power on, if power consumption is still over, power off relay 2, ..)
---|---
1| always power off relay 1 (IR external relay)
2| always power off relay 2 (External relay)
3| always power off both relays (relay 1 and relay 2)

Parameter 130: Serial Number (Read Only)

Since Version 7.6
Size: 4 Byte, Default Value:

SettingDescription

Technical Data

Dimensions 36x90x64mm mm
Weight 140 gr
Hardware Platform ZM5202
EAN 3830062070362
IP Class IP 20
Voltage 230 V
Load 65 A
Device Type Smart Meter
Firmware Version 07.06
Z-Wave Version 04.3d
Certification ID ZC10-18086203
Z-Wave Product Id 0x0159.0x0007.0x0052
Frequency Europe – 868,4 Mhz
Maximum transmission power 5 mW

Supported Command Classes

  • Basic
  • Meter
  • Crc 16 Encap
  • Association Grp Info
  • Device Reset Locally
  • Zwaveplus Info
  • Supervision
  • Configuration
  • Manufacturer Specific
  • Powerlevel
  • Firmware Update Md
  • Association
  • Version
  • Multi Channel Association
  • Security
  • Transport Service
  • Security 2

Controlled Command Classes

  • Transport Service
  • Security 2

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals