MOLLET MSD Silo Pressure Detector Instructions

June 8, 2024
MOLLET

MOLLET MSD Silo Pressure Detector

Read and follow these safety instructions first and take notice of the operating instructions.

Safety instructions

  1. The installation, initial operation, and maintenance may be done by a qualified expert with electrical know-how only.
  2. Comply with the local and statutory rules and regulations and/or the VDE 0100.
  3. Take notice of the temperature specifications on the data plate.
  4. A fuse (with max. 4A) has to be connected upstream in series to the signal contact.
  5. Protect the signal contacts from voltage peaks when inductive loads are connected.
  6. The device may be put into operation if it is closed, only.
  7. Switch off the power supply, before opening the device. (touch dangerous voltage)
  8. Attention safety device! Don´t modify anything at the device or at the switching point adjusting!

Operating instructions

Description

Intended use
The pressure detector controls as a limit switch the overpressure in silos and vessels.

Function
If the pressure reaches the switching point SP, the pressure detector will give a signal.

Technical data
  • Manufacturer MOLLET Füllstandtechnik GmbH
  • Address Industriepark RIO 103 74706 Osterburken
  • Name Silo pressure detector
  • Type MSD-070
  • Bulk good temperature -25 °C … +80 °C
  • Ambient temperature -20 °C … +70 °C
  • Signal contact change-over contact, potential free
  • The capacity of the contact 4 A / 250 V AC
    • Switching voltage 24 V … 250 V AC **** or 12 V … 125 V DC
  • Switching point 40 mbar = 0.04 bar = 400 mm WS
  • Overpressure safety up to 0.5 bar
  • Cable connection Screw M4
  • Cable entry Cable gland M20x1.5
  • Type of protection IP65 acc. to DIN EN 60529
  • Weight 1.1 kg
  • Maintenance none
  • Mounting position vertical, ± 5° inclination

Material

  • Housing ABS (high impact plastic), grey
  • Flange Aluminium
    • as an option Stainless steel 1.4571 / 316 Ti
  • Membrane Stainless steel 1.4301 / 304
  • Flange socket Steel
Dimensions

MOLLET-MSD-Silo-Pressure-Detector-fig- \(1\)

Accessory (Option) Flange socket

Installation

Preparation
  • Check the membrane of visual transport damage.
  • Read and follow the safety instructions and the operating instructions, before handling the device!

Mounting in the vessel

  • Weld the flange socket (as an option) vertically (Flange is horizontal) in the silo top.
  • Position the pressure detector (Flange is horizontal) with the gasket at the provided flange or flange socket and fix it with 4 washers and screws M8.
Electrical connection

Circuit diagramMOLLET-MSD-Silo-Pressure-Detector-fig-
\(3\)

Cable gland

  • After the electrical connection, tighten the cable gland.
  • Screw the cap nut, until the cable entry is closed tightly.

Cable run
Run the connection cable in a way that no traction can occur at the pressure detector.MOLLET-MSD-Silo-Pressure-Detector-fig-
\(4\)

Switching point

  • The switching point is adjusted at 40 mbar.
  • A modification may be carried out by the manufacturer only.

Utilization

Commissioning

  • Put the pressure detector into operation only, if the installation in the silo or vessel and the electrical connection has been done correctly.

Normal operation

  • Use the pressure detector in its intended application only.
  • Comply with the specifications on the data plate.
  • Damaged devices have to be put out of operation immediately.
  • The pressure detector must not be modified. If there is any modification, the warranty of the manufacturer will be, canceled.

Inexpert handling

  • Ignoring of the safety instructions and the operating instructions.
  • Not intended use.
  • Modification at the device or of the switching point adjusting.
  • Violation against applicable law and standards.

Maintenance and servicing

Maintenance
  • In case of intended use, the silo pressure detector needs no maintenance.

Servicing

  • The servicing of the pressure detector may be carried out by the manufacturer only.

Storage

  • Store the pressure detector dry and dust-free.
  • Protect the membrane from damage.

Disposal

  • The pressure detector can be recycled.
  • The disposal applies to the valid environmental guidelines according to the location of the carrier and the local manufacturing conditions.

EU-Declaration of Conformity

We

MOLLET Füllstandtechnik GmbH
Industriepark RIO 103
D-74706 Osterburken
Tel. 06291 64400 Fax 06291 9846

declares under our sole responsibility, that the product:

Type

  • MSD-070 … , MSD-A …

conforms with the following European directives:

  • Low voltage directive 2014/35/EU

Applied harmonized standards or normative documents:

  • DIN EN 61010-1:2020
  • DIN EN 60529:2014

And the devices with markings conform additional with the following European directive:

  • ATEX directive 2014/34/EU

Depending on the design applied harmonized standards or normative documents:

  • DIN EN IEC 60079-0:2019
  • DIN EN 60079-31:2014
  • DIN EN 60079-11:2012
  • DIN EN 60079-26:2015

EU-Type Examination Certificate:

  • IBExU06ATEX1069

Issued by:

  • IBExU Institut für Sicherheitstechnik GmbH, 09599 Freiberg (0637)

Quality assurance:

  • TÜV NORD CERT GmbH, 30159 Hannover (0044)

MOLLET-MSD-Silo-Pressure-Detector-fig- \(5\)

This declaration is only allowed to hand out in the unchanged form.