STELPRO SB/SB SERIES Dual Energy Duct Heater Installation Guide
- June 8, 2024
- StelPro
Table of Contents
ASB/SB SERIES
DUAL ENERGY DUCT HEATER
REPLACEMENT COMPONENT LIST INCLUDED
INSTALLATION GUIDE E322241
SB/SB SERIES Dual Energy Duct Heater
If you are viewing this guide online, please note that this product has been
modified since its introduction. To obtain the guide corresponding to your
model (manufactured before October 2015), please contact customer service.
WARNING
Before installing and operating this product, the user and/or installer must
read, understand and follow these instructions and keep them handy for future
reference. If these instructions are not followed, the warranty will be
considered null and void and the manufacturer deems no further responsibility
for this product.
This product must be installed by a qualified person and connected by a
certified electrician, according to the electrical and building codes
effective in your region.
The following instructions must be adhered to in order to avoid personal
injuries or property damages, serious injuries and potentially fatal electric
shocks.
Make sure that all screws and electrical terminal connections are tightly
secured before operating the unit in case they would have loosened during
transportation.
Protect the heating unit with the appropriate circuit breaker or fuse, in
accordance with the nameplate.
Make sure the line voltage (volt) is consistent with that indicated on the
unit’s nameplate.
This unit must be grounded.
Switch off the power at the circuit breaker/fuse before installing, repairing
and cleaning the unit.
Make sure the unit is appropriate for the intended use (if needed, refer to
the product catalog or a representative).
If the unit’s capacity is insufficient for the size of the house, it will be
in operation continuously, and may become defective earlier.
Respect distances and positions indicated in the installation section.
If the installer or the user modifies the unit, they will be held responsible
for any damage resulting from this modification, and the UL certification
could be void.
This unit must not come into contact with a water source and must be protected
from splashes (e.g. a wet mop). Do not use it if any part has been immersed.
Moreover, do not turn it on or off when standing in water or if your hands are
wet.
When cutting a piece of steel for the installation of the return duct, do not
damage electrical wiring of the unit.
Because this unit is hot when in use, it may pose risks even in normal
operation. Therefore, be careful and responsible when using it. To avoid
burns, do not let bare skin touch hot surfaces. Let the unit cool down for a
few minutes before handling it (it stays warm for some time after shut-down).
Never block air vents. This obstruction could lead to overheating, which could
result in a fire.
Do not insert or allow foreign objects to enter any air vent as this may cause
electric shocks, fires, or damages to the unit.
This unit has hot and arcing or sparking parts inside. It is not designed to
be used or stored in wet areas or areas containing flammable liquids,
combustible materials or corrosive, abrasive, chemical, explosive and
flammable substances such as, but not limited to, gasoline, paint, chlorine
and cleaning products.
Some areas are dustier than others. Thus, it is the user’s responsibility to
evaluate if the filter must be changed based on it. Accumulated dirt can lead
to a component malfunction or discoloration (yellowing). It may cause a fire
hazard if not installed and maintained in accordance with these instructions.
Thermal protection activation indicates that the unit has been subjected to
abnormal operating conditions. If the thermal protection remains activated or
activates and deactivates repeatedly, it is recommended that a qualified
electrician or a certified repair centre examine the unit in order to make
sure it is not damaged. (Refer to the limited warranty).
If the unit is damaged or defective, cut off power supply at circuit
breaker/fuse and call a certified repair centre. (Refer to the limited
warranty).
Label all wires prior to disconnection when servicing controls. Wiring errors
can cause improper and dangerous operation.
Note: When a part of the product specification must be changed to improve
operability or other functions, priority is given to the product specification
itself. In such instances, the instruction manual may not entirely match all
the functions of the actual product. Therefore, the actual product and
packaging, as well as the name and illustration, may differ from the manual.
SPECIFICATIONS
ASB/SB DUAL ENERGY DUCT HEATER
TYPE| VOLTS| KW| AMPS| HEIGHT (IN)| WIDTH (IN)|
DEPTH (IN)| LB| KG
---|---|---|---|---|---|---|---|---
ASB/SB05| 240/208| 5.0/3.8| 20.8/18.1| 12 9/16| 20 1/8| 20 9/16 – 23 9/16|
33.4| 15.5
ASB/SB10| 240/208| 10.0/7.5| 41.7/36.1| 12 9/16| 20 1/8| 20 9/16 – 23 9/16|
33.4| 15.5
ASB/SB15| 240/208| 15.0/11.3| 62.5/54.2| 12 9/16| 20 1/8| 20 9/16 – 23 9/16|
33.4| 15.5
ASB/SB18| 240/208| 18.0/13.5| 75.0/65.0| 12 9/16| 20 1/8| 20 9/16 – 23 9/16|
33.4| 15.5
ASB/SB20| 240/208| 20.0/15.0| 83.3/72.2| 12 9/16| 20 1/8| 20 9/16 – 23 9/16|
33.4| 15.5
ASB/SB23| 240/208| 23.0/17.3| 95.8/83.1| 12 9/16| 20 1/8| 20 9/16 – 23 9/16|
33.4| 15.5
ASB/SB27| 240/208| 27.0/20.3| 112.5/97.5| 12 9/16| 20 1/8| 20 9/16 – 23 9/16|
33.4| 15.5
ASB/SB30| 240/208| 30.0/22.5| 125.0/108.3| 12 9/16| 20 1/8| 20 9/16 – 23
9/16| 33.4| 15.5
*For the ASB05 and ASB10 models, no breakers are needed.
TECHNICAL DRAWINGS
MODEL | A | B |
---|---|---|
16×181 | 18” | 16” |
19×19 | 19” | 19” |
INSTALLATION
N.B. Cut off power supply at circuit breaker/fuse before proceeding to
the installation.
Please note that each ASB/SB duct heater is factory inspected before shipping
in order to ensure that every component is operating efficiently.
The ASB/SB series dual energy duct heater is available in several models of
various heating capacity (from 5 to 30 kW). All these models are designed to
be installed downstream of the furnace, this is to say, on the supply side.
INSTALLATION CLEARANCES
When performing the installation, respect clearances given by the following
daigrams 2A or 2B.
A 28” front panel clearance is required to facilitate servicing.
DUCT HEATER ORIENTATION
The ASB/SB duct heater can only be installed in a vertical conduit with an
upflow orientation (see figure 3). An improper installation will affect the
safe and reliable operation of the unit.
DUCT CUT-OUT
Installer must cut an opening in the duct in order to install the duct heater
unit. Consult the following diagram for the dimensions of that opening. If the
baffles are to be used, the installer must cut a slot on each side of the
opening. These slots have to be wide enough to avoid interference with the
baffles at the insertion of the unit into the duct.
N.B : The duct cut-out must be positioned accordingly to figures 2A & 2B.
BAFFLE INSTALLATION
Baffles have to be installed by matching the clips on the baffles to the holes
on the heat body and by securing them with self-tapping screws. Then, they
have to be cut in order to fit in the duct with a gap of 1/8” between the duct
lining and the baffle edge.
N.B. : If the clips are too tight to slide, they can be opened with a
flat screwdriver.
HEATER INSTALLATION
Insert heat body through the opening in the duct and secure it with six self-
tapping screws in the pre-drilled holes inside the electrical enclosure. Seal
the baffles slots and the enclosure perimeter in order to avoid air leaks.
POSITIONING THE DUCT TEMPERATURE SENSOR
The temperature-sensor of the duct must be placed on the supply side at a good
distance from the duct heater in order to avoid as much exposure as possible
from the radiation of the elements.
ELECTRICAL CONNECTIONS
ELECTRICAL POWER SUPPLY
Note that a qualified electrician must wire this product according to the
electrical and building codes effective in your region.
The duct heater must be connected to a of 240/208VAC power supply source. Note
that the nominal power values calculated are based on a supply voltage of
240VAC.
The connection of the unit itself is made to a power block installed inside
the control panel. Knockouts are punched on both sides of the unit to allow
power entry.
Please refer to the national and local electrical codes for selecting the
proper cable size as well as the appropriate circuit breakers or fuses.
Before installing the unit, the installer must make sure the distribution
panel is adequate to permit the connection of the duct heater .The available
power must be verified to ensure that it is sufficient to support the
additional load.
The installer must make sure the heating power of the duct heater does not
exceed the nominal power of the furnace burner.
OPERATION
The ASB/SB series dual-energy air heater duct heater is designed to drive
activate, when the thermostat calls for heat, external heating equipment or
its own heating elements. Depending on the selected mode and the external
temperature, one of these two heating modes will be activated.
The call for heat from the thermostat is redirected relayed to the air heater
duct heater through the “W” and “R” connectors while the SHQ probe sensor
provides the external temperature information signal.
*The SHQ external probe is provided and installed by Hydro-Québec.
The three push buttons located on the air heater duct heater allow to select
the selection between the 3 available modes: dual-energy mode, electric mode
and fuel mode. The selected mode is signaled by the LEDs “FOSSIL-FUEL”,
“ELECTRIC” or “DUAL-ENERGY”.
For the dual-energy mode, one of the two LEDs will indicate the operating
heating mode.
One The orange LED indicate indicates a call for heat.
The selected heating mode is kept in memory in case of a power failure.
In electric mode, the plenum temperature can be adjusted using the
potentiometer located on the board, the setting is from 35°C to 60°C.
NOTE : the name term Fossil-Fuel refers to natural gas and fuel oil.
DUAL ENERGY MODE
In this operating mode the duct heater will decide to activate either its own
heating assembly or the furnace heat output in accordance with the outdoor
temperature sensor’s signal.
More specifically, while the thermostat calls for heat, as the outdoor
temperature drops to –12ºC or –15ºC (depending on the climatic zone in which
you live) the outdoor sensor’s signal will trigger the duct heater to
deactivate its heating assembly and trigger the furnace burner. Conversely,
while the thermostat calls for heat, as the outdoor temperature rises to –12ºC
or –15ºC (depending on the climatic zone), the outdoor sensor’s signal will
trigger the duct heater to deactivate the furnace burner and subsequently,
following a 5 minute delay, trigger simultaneously its heating assembly and
the furnace blower.
ELECTRIC MODE
In this operating mode, regardless of the outdoor temperature sensor’s signal,
the duct heater triggers its own heating assembly in response to the
thermostat signal.
FUEL MODE (OR GAS)
In this operating mode, irregardless of the outdoor temperature sensor’s
signal, the duct heater redirects the thermostat call for heat to the furnace.
AUTO-TRANSFER OVERRIDE
THIS SECTION ONLY APPLIES IN DUAL-ENERGY MODE
If a bad behavior malfunction is detected in the active heating mode while the
air-heater duct heater is in dual-energy mode, the air-heater duct heater will
bypass the active mode and activate the other heating mode as backup.
The bad behavior malfunction is detected using the plenum temperature sensor
provided with the ASB/SB series dual-energy air-heater.
Based on this information, the duct heater Using this information, the air-
heater is able to detect that the heating system (electric or fossil-fuel) is
defective. When the thermostat calls for heat, the air-heater duct heater
starts heating using one of the two available heating modes depending on the
external temperature signal provided by the SHQ probe sensor. Each time a new
heating cycle is initiated, a 15 minutes minute countdown is started.
Once this countdown has expired, if the plenum temperature did not reach the
auto-transfer override temperature (see Auto-transfer override temperature
section) and the call for heat is still present, the active heating mode will
be deactivated and the other mode will be activated. I.e. if the Electric mode
was activated when the call for heat was received, the auto-transfer override
will activate the Fossil-Fuel mode and vice-versa.
While the auto-transfer override is active, the blinking LED is showing the
defective heating mode.
The user may cancel the auto-transfer override at any time by pressing one of
the 3 buttons and select the desired heating mode.
Once the auto-transfer override is activated, the bypass duration is fixed to
1 hour for the first two fix attempts. The subsequent auto-transfer override
duration is then set to 12 hours for all other fix attempts.
After each bypass period, the auto-transfer override is deactivated to verify
if the defective mode has been fixed.
If both heating modes are defective, the auto-transfer override will be
activated every 15 minutes until one of the two heating mode has been fixed.
CONTROL PANEL
LEGEND
- DUAL ENERGY button: Allows the selection of the Electric or Fossil Fuel mode.
- ELECTRIC LED: Indicates the Electric mode of the Dual Energy mode is activated.
- FOSSIL FUEL LED: Indicates the Fossil Fuel mode of the Dual Energy mode is activated.
- THERMOSTAT orange LED: indicates a heating demand from the thermostat.
- FOSSIL FUEL button: Allows the selection of the Fossil Fuel mode.
- FOSSIL FUEL – ON LED: Indicates the Fossil Fuel mode is activated.
- ELECTRIC LED: Allows the selection of the Electric mode.
- ELECTRIC – ON LED: Indicates the Electric mode is activated.
AUTO-TRANSFER TEMPERATURE
The auto-transfer override temperature is defined as the minimum air
temperature in the plenum under which the auto-transfer override function will
be activated (after a 15 minute minute delay). The installer may adjust it
with the potentiometer located on the board.
The installer must determine the proper value by performing a plenum
temperature reading with the electric elements on, not the furnace burner. He
must then adjust the potentiometer to a lesser temperature than the one from
the plenum.
The following table describes the control board operation:
CONTROL BOARD OPERATION
MODE | INPUTS | BURNER | ELEMENTS | FAN |
---|---|---|---|---|
ELECTRIC | FOSSIL-FUEL | DUAL-ENERGY | W1 | G |
0 | 0 | 1 | 1 | 0 |
0 | 0 | 1 | 1 | 1 |
0 | 0 | 1 | 1 | X |
0 | 1 | 0 | 1 | 0 |
0 | 1 | 0 | 1 | 1 |
0 | 1 | 0 | 0 | 1 |
1 | 0 | 0 | 1 | X |
X | X | X | 0 | 1 |
X | X | X | 0 | 0 |
THERMOSTAT AND FURNACE CONTROL SIGNALS
The existing thermostat may be used to control the ASB/SB dual energy duct
heater. The duct heater includes a control terminal block connection located
directly on the circuit board. This makes it possible to connect the
thermostat and the furnace control wires (R, W and G). Please refer to the
following wiring diagrams to connect the thermostat and the furnace to the
duct heater.
SAFETY FEATURES
The ASB/SB duct heater is designed with several safety features to guarantee
safe operation. The following paragraphs describe these safety features.
DUCT OVERHEATING DETECTION
The ASB/SB duct heater control board is able to detect if the temperature of
the duct exceeds a certain critical point at which the operation could lead to
premature wear of the elements and an overheating of the unit. For instance a
dirty air filter could reduce the circulation of air in the conduits to the
point where it becomes insufficient to dissipate all the heat generated by the
elements or the burner of the furnace.
If the burner is on and the plenum temperature exceeds 71 °C (160 °F) for more
than two minutes, then the electric mode will be forced, and the temperature
will be set by the potentiometer.
In this situation the control board will only indicate the event by means of
an orange pilot light. The pilot light will blink 4 times in two seconds,
followed by a two second pause.
If the ASB/SB is on dual energy mode (fuel mode) and the temperature on the
duct exceeds 71°C (160°F) for two minutes, the furnace burner will be
deactivated and the electric mode will be forced until temperature of the duct
is below 54°C (129°F). When the electric mode is forced, the orange indicator
flashes 4 times in 2 seconds and then is off for the following two seconds.
THERMAL PROTECTION
The ASB/SB dual energy duct heater is equipped with a thermo-mechanical
protection, which provides the ultimate line of defence against any possible
overheating. Each element has its own automatic reset thermal protection,
which protects it from overheating. Moreover, a manual reset thermal
protection has been installed in the duct heater in case the elements
automatic protection should fail. The automatic thermal protection of the
element activates at 71°C (140°F) where as the manual thermal protection
activates at 60°C (165°F). For the new ASB/SB series (manufactured since
October 2015) the manual protection is rated for 85°C (185°F).
The thermal protection provide a 93°C (199°F) maximum temperature limitation
on the air output.
HEATING DEMAND INTERLOCK
The demand for heat received by the control board can only operate one heating
mode at a time even if the microcontroller is damaged. Indeed, an
electromechanical interlock built into the control board, prevents the two
heating modes from operating at the same time as a result of a damaged
microcontroller requesting erratic demands.
MAINTENANCE
The ASB/SB dual energy duct heater itself does not require any particular
maintenance. However, it is important to carry out regular maintenance on the
ventilation system overall. The air filter should be replaced when it is dirty
and the ventilation shafts cleaned out when necessary. During the cleaning of
the conduits, the ventilator of the furnace must be inspected and cleaned if
necessary. A faulty maintenance of the ventilation system will reduce the
performance of the duct heater.
N.B. Never activate the duct heater if the ventilation system is not
equipped with an air filter.
AIRFLOW CALCULATIONS
The airflow in the ASB/SB dual energy duct heater is bidirectional and the minimum air velocity is 300 FPM. It is possible to calculate the airflow of the ventilation system using the following two formulas:
TROUBLESHOOTING
PROBLEM | DEFECTIVE PART OR PART TO CHECK |
---|---|
The unit does not work | •Defective thermostat, wrong thermostat setting, |
positioning or wiring
•Open circuit breaker or fuse
•Faulty power supply connections
•Defective transformer
The unit has power but the elements do not work
•Defective relay| •Tripped manual reset thermal cut-out
The unit runs continuously| •Defective thermostat, wrong thermostat setting,
positioning or wiring
•Heat losses greater than the heating capacity of the unit
Element operating and/or cycling continuously| •Defective 24V relay (contact
probably welded)
All the element operating and/or cycling when there is a heating demand|
•Defective furnace fan
•Obstructed Return and/or supply air
Unit is overheating| •Defective furnace fan
•Obstructed Return and/or supply air
The breaker trips when the heater is turned on| •Faulty power supply
connections
•Voltage higher than that indicated on the nameplate
Unable to attain desired room temperature| •One or more defective elements
•Defective thermostat, wrong thermostat setting, positioning or wiring
•Voltage lower than that indicated on the nameplate
•Heat losses greater than the heating capacity of the unit
•Defective 24V relay
•Tripped manual reset thermal cut-out
The orange pilot light blinks| •The duct’s temperature-sensor is defective or
wrongly connected
The orange pilot light blinks four times every two seconds and pause for two
seconds| •The air temperature of the plenum exceeds 71°C (160°F) – Dirty
filter or worn fan belt
•Mode forced to electric
N.B.: If you do not solve the problem after checking these points, cut off the power supply at the main electrical panel and contact our customer service (see the “LIMITED WARRANTY” section to obtain the phone numbers).
REPLACEMENT COMPONENTS LIST
REF. # | PART # | DESCRIPTION |
---|---|---|
1 | ELF-SB160521 | SB ASSEMBLED ELEMENT, 16” LONG., 5 KW, 240 V |
1 | ELF-SB160421 | SB ASSEMBLED ELEMENT, 16” LONG., 4 KW, 240 V |
1 | ELF-SB160321 | SB ASSEMBLED ELEMENT,16” LONG., 3.5 KW, 240 V |
1 | ELF-SB190521 | SB ASSEMBLED ELEMENT, 19” LONG., 5 KW, 240 V |
1 | ELF-SB190421 | SB ASSEMBLED ELEMENT, 19” LONG., 4 KW, 240 V |
1 | ELF-SB190321 | SB ASSEMBLED ELEMENT, 19” LONG., 3.5 KW, 240 V |
2 | PROT-065 | THERMAL PROTECTION, 165°F, MANUAL RESET |
2 | PROT-017 | THERMAL PROTECTION, 185°F, MANUAL RESET |
3 | PROT-019 | THERMAL PROTECTION, 140°F, AUTOMATIC RESET |
4 | CIR-023 SB | ELECTRONIC BOARD FOR SB DUCT HEATER WITH PROGRAM |
5 | TRF200040D | TRANSFORMER, 208-240/24/40VA, CL.2 CL.B |
6 | REL-006 | RELAY, SINGLE POLE 30A/250VAC 24VDC |
7 | BREA-001 | CIRCUIT BREAKER 120/240V 30A 2P |
7 | BREA-002 | CIRCUIT BREAKER 120/240V 40A 2P |
7 | BREA-003 | CIRCUIT BREAKER 120/240V 50A 2P |
LIMITED WARRANTY
This limited warranty is offered by Stelpro Design inc. (“Stelpro”) and
applies to the following product made by Stelpro: ASB/SB model. Please read
this limited warranty carefully. Subject to the terms of this warranty,
Stelpro warrants its products and their components against defects in
workmanship and/or materials for the following period from the date of
purchase: 3 years. This warranty applies only to the original purchaser; it is
non-transferable and cannot be extended.
CLAIM PROCEDURE
If at any time during the warranty period the unit becomes defective, you must
cut off the power supply at the main electrical panel and contact 1) your
installer or distributor, 2) your service center or 3) Stelpro’s customer
service department. In all cases, you must have a copy of the invoice and
provide the information written on the product nameplate. Stelpro reserves the
right to examine or to ask one of its representatives to examine the product
itself or any part of it before honoring the warranty. Stelpro reserves the
right to replace the entire unit, refund its purchase price or repair a
defective part. Please note that repairs made within the warranty period must
be authorized in advance in writing by Stelpro and carried out by persons
authorized by Stelpro.
Before returning a product to Stelpro, you must have a Stelpro authorization
number (RMA). To obtain it, call the customer service department at:
1-800-363-3414 (electricians and
distributors – French), 1-800-343-1022
(electricians and distributors – English), or
1-866-766-6020 (consumers). The
authorization number must be clearly written on the parcel or it will be
refused.
CONDITIONS, EXCLUSIONS AND DISCLAIMER OF LIABILITY
This warranty is exclusive and in lieu of all other representations and
warranties (except of title), expressed or implied, and Stelpro expressly
disclaims and excludes any implied warranty of merchantability or implied
warranty of fitness for a particular purpose.
Stelpro’s liability with respect to products is limited as provided above.
Stelpro shall not be subject to any other obligations or liabilities
whatsoever, whether based on contract, tort or other theories of law, with
respect to goods or services furnished by it, or any undertakings, acts or
omissions relating thereto. Without limiting the generality of the foregoing,
Stelpro expressly disclaims any liability for property or personal injury
damages, penalties, special or punitive damages, damages for lost profits,
loss of use of equipment, cost of capital, cost of substitute products,
facilities or services, shutdowns, slowdowns, or for other types of economic
loss or for claims of a dealer’s customers or any third party for such
damages. Stelpro specifically disclaims all consequential, incidental and
contingent damages whatsoever.
This warranty does not cover any damages or failures resulting from: 1) a
faulty installation or improper storage; 2) an abusive or abnormal use, lack
of maintenance, improper maintenance (other than that prescribed by Stelpro)
or a use other than that for which the unit was designed; 3) a natural
disaster or an event out of Stelpro’s control, including, but not limited to,
hurricanes, tornadoes, earthquakes, terrorist attacks, wars, overvoltage,
flooding, water damages, etc. This warranty does not cover any accidental or
intentional losses or damages, nor does it cover damages caused by negligence
of the user or owner of the product. Moreover, it does not cover the cost of
disconnection, transport, and installation.
The warranty is limited to the repair or the replacement of the unit or the
refund of its purchase price, at the discretion of Stelpro. Any parts replaced
or repaired within the warranty period with the written authorization of
Stelpro will be warranted for the remainder of the original warranty period.
This warranty will be considered null and void and Stelpro will have the right
to refuse any claims if products have been altered without the written
authorization of Stelpro and if the nameplate numbers have been removed or
modified. This warranty does not cover scratches, dents, corrosion or
discoloration caused by excessive heat, chemical cleaning products and
abrasive agents. It does not cover any damage that occurred during the
shipping.
Some states and provinces do not allow the exclusion or limitation of
incidental or consequential damages and some of them do not allow limitations
on how long an implied warranty lasts, so these exclusions or limitations may
not apply to you. This warranty gives you specific legal rights and you may
have other rights which vary from state to state or from province to province.
For further information or to consult this guide online, please visit our
website at www.stelpro.com
INS_ASB_SB_I_0622
Documents / Resources
|
STELPRO SB/SB SERIES Dual Energy Duct
Heater
[pdf] Installation Guide
SB SB SERIES Dual Energy Duct Heater, SB SB SERIES, Dual Energy Duct Heater,
Energy Duct Heater, Duct Heater
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>