Puravent 19546 KD 450 XL1 CIRC. Duct Fan User Manual

June 2, 2024
puravent

Puravent 19546 KD 450 XL1 CIRC. Duct Fan

Description

  • High efficiency – low noise
  • Speed-controllable
  • Integral thermal contacts
  • Can be installed in any position
  • Maintenance-free and reliable

The KD series have external rotor motors with a new type of mixed flow impeller which reduces the external dimensions of the fans. These fans have a high capacity in relation to their compact design. Brackets are supplied with the fans to make installation easier. The FK mounting clamp facilitates easy installation and removal and prevents the transfer of vibrations to the duct. To protect the motor from overheating the fan has integral thermal contacts with leads to a motor protection device. The casing is manufactured from galvanised sheet steel.

Technical parameters

Nominal data|
---|---
Voltage| 230| V
Frequency| 50| Hz
Phase| 1| ~
Input power (P1)| 1392| W
Current| 6,16| A
Max. airflow| 2,35| m³/s
R.p.m.| 1289| r.p.m.
Capacitor| 30| µF
Weight| 37| kg
 |  |
Temperature data|  |
Max. temperature of transported air| 60| °C
Max. temperature of transported air when speed-controlled| 60| °C
 |  |
Sound data|  |
Sound pressure level at 3 m| 60,9| dB(A)
 |  |
Protection / Classification|  |
Insulation class| F|
Enclosure class, motor| IP54|

Diagrams

Puravent-19546 KD 450-XL1-CIRC-Duct-Fan-FIG-
\(3\)

Max efficiency

Hydraulic data|
---|---
Working air flow|  |  |  |  |  |  |  | 1,18| m³/s|
Working static pressure|  |  |  |  |  |  |  | 372| Pa|
Power|  |  |  |  |  |  |  | 1310| W|
Speed|  |  |  |  |  |  |  | 1315| r.p.m.|
Current|  |  |  |  |  |  |  | 5,75| A|
SFP|  |  |  |  |  |  |  | 1,12| W/(l/s)|
Voltage|  |  |  |  |  |  |  | 230| V|
Sound power level|  | 63| 125| 250| 500| 1k| 2k| 4k| 8k| Tot
Inlet| dB(A)| 69| 76| 75| 75| 74| 73| 66| 59| 82
Outlet| dB(A)| 69| 76| 73| 76| 76| 72| 67| 61| 82
Surrounding| dB(A)| 35| 54| 60| 65| 61| 59| 46| 40| 68

Dimensions

Puravent-19546 KD 450-XL1-CIRC-Duct-Fan-FIG-
\(4\)

  øA B     C øD (x4) E  F  G  øH øI øJ K L
KD 400 M 400 40 480 10 38 59 38 355 400 503 590 11
KD 400 XL 400 44 602 12 33 61 37 400 450 560 662 18,5
KD 450 M 450 44 559 12 33 61 37 400 450 560 662 18,5
KD 450 XL 450 46 686 12 45 76 50 450 500 660 812 18,5
KD 500 M 500 46 643 12 45 76 50 450 500 660 812 18,5

|  |  |  |  |  |  |  |

Wiring

Accessories

Electric accessories

  • REU 7 Speed control (5007)
  • RTRE 7 Speed control (5011)
  • S-ET 10 Motor Protection (5154)
  • STL 10 Speed controller (84272)
  • REV-5POL/05 ON/OFF (33979)

Accessories

  • FK 450 Fast clamp (1616)
  • SG 450 Protection guard (5614)
  • VK-45 Louvre shutter (5645)
  • RSK-450 Back draft dmp. (9768)

Documentation

  • 132780_Fans_Instructions_Outside_EU_A002.pdf (1 006,63kB)

Name: KD 450 XL1 CIRC. DUCT FAN
Item no.: 19546
Document type : Product card
Document date: 2019-07-16
Generated by: Online catalogue

Get In Touch
Call: 0845 6880112
Email: info@adremit.co.uk

Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals