ElectriFLEX LD 40759 Light Duty Commercial Electric Water Heater Instruction Manual
- June 2, 2024
- ElectriFLEX LD
Table of Contents
ElectriFLEX LD 40759 Light Duty Commercial Electric Water Heater
INSTALLATION & OPERATING INSTRUCTION
A Spanish language version of these instructions is available by contacting
the company listed on the rating plate.
THE WARRANTY ON THIS WATER HEATER IS IN EFFECT ONLY WHEN THE WATER HEATER IS
INSTALLED AND OPERATED IN ACCORDANCE WITH LOCAL CODES AND THESE INSTRUCTIONS.
THE MANUFACTURER OF THIS HEATER WILL NOT BE LIABLE FOR ANY DAMAGE RESULTING
FROM FAILURE TO COMPLY WITH THESE INSTRUCTIONS. READ THESE INSTRUCTIONS
THOROUGHLY BEFORE STARTING.
For your comfort, safety and convenience, it is recommended that this water
heater be installed and serviced by a plumbing professional.
CONGRATULATIONS!
You have just purchased one of the finest water heaters on the market today!
This installation, operation and instruction manual will explain in detail the
installation and maintenance of your new Light Duty Commercial Electric Water
Heater. We strongly recommend that you contact a plumbing professional for the
installation of this water heater.
We require that you carefully read this manual, as well as the enclosed
warranty, and refer to it when questions arise. If you have any specific
questions concerning your warranty, please consult the plumbing professional
from whom your water heater was purchased. For your records we recommend that
you write the model, serial number and installation date of your water heater
in the maintenance section in the back of this manual. This manual should be
kept with the water heater.
GENERAL INFORMATION
This electric water heater’s design is certified by INTERTEK (ETL) and listed
in accordance with UL 1453. CETL listed in accordance with Canadian National
Standard C22.2, No. 110.
This water heater must be installed in accordance with local codes. In the
absence of local codes, install this water heater in accordance with the
N.E.C. Reference Book (latest edition).
The warranty for this water heater is in effect only when the water heater is
installed, adjusted, and operated in accordance with these Installation and
Operating Instructions. The manufacturer will not be held liable for damage
resulting from alteration and/or failure to comply with these instructions.
To comply with NSF requirements this water heater is to be:
- Sealed to the floor with sealant, in a smooth and easily cleanable way, or
- Installed with an optional leg kit that includes legs and/or extensions that provide a minimum clearance of 6” beneath the water heater.
This water heater has been designed and certified for the purpose of heating potable water. The installation and use of this water heater for any purpose other than the heating of potable water, may cause damage to the water heater and create a hazardous condition and nullify the warranty.
CAUTION Incorrect operation of this appliance may create a hazard to life
and property and will nullify the warranty.
Do not use this appliance if any part has been submerged in water. The
plumbing professional responsible for the installation of this water heater
should be contacted to inspect the appliance and to replace any part of the
control system, including thermostat, which has been submerged in water.
Make sure that the rating plate on the water heater is referenced for
certainty that the correct voltage is being supplied to the water heater.
DANGER Do not store or use gasoline or other flammable, combustible, or
corrosive vapors and liquids in the vicinity of this or any other appliance. A
sacrificial anode(s) is used to extend tank life. Removal of any anode, except
for inspection and/or replacement, will nullify the warranty. In areas where
water is unusually active, an odor may occur at the hot water faucet due to a
reaction between the sacrificial anode and impurities in the water. If this
should happen, an alternative anode(s) may be purchased from the supplier that
installed this water heater. This will minimize the odor while protecting the
tank. Additionally, the water heater should be flushed with appropriate
dissolvers to eliminate any bacteria.
IMPORTANT
Before proceeding, please inspect the water heater and it’s components for
possible damage. DO NOT install any damaged components. If damage is evident,
please contact the supplier where the water heater was purchased or the
manufacturer listed on the rating plate for replacement parts.
INSTALLATION
Locating The Water Heater
WARNING Water heaters are heat producing appliances. To avoid damage or
injury, there shall be no materials stored against the water heater and proper
care shall be taken to avoid unnecessary contact (especially by children) with
the water heater. UNDER NO CIRCUMSTANCES SHALL FLAMMABLE MATERIALS, SUCH AS
GASOLINE OR PAINT THINNER BE USED OR STORED IN THE VICINITY OF THIS WATER
HEATER OR ANY LOCATION FROM WHICH FUMES COULD REACH THE WATER HEATER.
This water heater MUST be installed indoors out of the wind and weather. This
water heater shall NOT be installed in any location where gasoline or
flammable vapors are likely to be present, unless the installation is such to
eliminate the probable ignition of gasoline or flammable vapors.
The location this water heater is to be installed is of utmost importance.
Before installing this water heater, consult the installation section of these
instructions. After reading these installation and operating instructions,
select a location for the water heater where the floor is level and is easily
accessible to a power supply and water connections. It is recommended that the
water heater be located near the center of greatest hot water usage to prevent
heat loss through the pipes. DO NOT locate the water heater where water lines
could be subjected to freezing temperatures. Locate the water heater so that
access panels and drain valves are accessible. Some models are not equipped
with a drain valve. For those models, install a drain tee in the cold water
inlet as close as practical to the water heater.
Water heater corrosion and component failure can be caused by the heating and
breakdown of airborne chemical vapors. Examples of some typical compounds that
are potentially corrosive are: spray can propellants, cleaning solvents,
refrigerator and air conditioning refrigerants, swimming pool chemicals,
calcium or sodium chloride, waxes and process chemicals. These materials are
corrosive at very low concentration levels with little or no odor to reveal
their presence. NOTE: DAMAGE TO THE WATER HEATER CAUSED BY EXPOSURE TO
CORROSIVE VAPORS IS NOT COVERED BY THE WARRANTY. DO NOT OPERATE THE WATER
HEATER IF EXPOSURE HAS OR WILL OCCUR. DO NOT STORE ANY POTENTIALLY CORROSIVE
COMPOUNDS IN THE VICINITY OF THE WATER HEATER.
This water heater must be located in an area where leakage of the tank or
water line connections and the combination temperature and pressure relief
valve will not result in damage to the area adjacent to the water heater or to
lower floors of the structure. When such locations cannot be avoided, a
suitable drain pan must be installed under the water heater. The drain pan
must have a minimum length and width of at least 4 in. (10.2 cm) greater than
the diameter of the water heater. The drain pan, as described above, can be
purchased from your plumbing professional. The drain pan must be piped to an
adequate drain. The piping must be pitched for proper drainage.
CLEARANCES
- Minimum clearance to combustible material is 0 inches for the Top, Sides, Front, and Rear of this water heater. However, it is recommended that at least 18 inches (45.7 cm) from the Top, and 24 inches (61 cm) from the Front. Clearance for servicing may be reduced down to minimum clearance to combustible material, but service time and effort may be greatly increased.
- Increase distances to provide clearances for servicing.
Note: For California installation this water heater must be braced, anchored, or strapped to avoid falling or moving during an earthquake. See instructions for correct installation procedures. Instructions may be obtained from the DSA Headquarters Office, 1102 Q Street, Suite 5100, Sacramento, CA 95811.
Water Connections
NOTE: BEFORE PROCEEDING WITH THE INSTALLATION, CLOSE THE MAIN WATER
SUPPLY VALVE.
After shutting the main water supply valve, open a faucet to relieve the water
line pressure to prevent any water from leaking out of the pipes while making
the water connections to the water heater. After the pressure has been
relieved, close the faucet. The COLD water inlet and HOT water outlet are
identified on top of the water heater. The fittings at the cold water inlet
and hot water outlet are dielectric waterway fittings with 3/4” NPT tapered
male threads. Make the proper plumbing connections between the water heater
and the plumbing system in the building. Install a shut-off valve in the cold
water supply line.
CAUTION If sweat fittings are to be used, DO NOT apply heat to the
nipples on top of the water heater. Sweat the tubing to the adapter before
fitting the adapter to the water connections. It is imperative that heat is
not applied to the nipples containing a plastic liner.
IMPORTANT FAILURE TO INSTALL AND MAINTAIN A NEW, LISTED 3/4” X 3/4”
TEMPERATURE-PRESSURE RELIEF VALVE WILL RELEASE THE MANUFACTURER FROM ANY CLAIM
WHICH MIGHT RESULT FROM EXCESSIVE TEMPERATURE AND PRESSURES.
If this water heater is installed in a closed water supply system, such as the
one having a back-flow preventer in the cold water supply, provisions shall be
made to control thermal expansion. DO NOT operate this water heater in a
closed system without provisions for controlling thermal expansion. Your water
supplier or local plumbing inspector should be contacted on how to control
this situation.
After installation of the water lines, open the main water supply valve and
fill the water heater. While the water heater is filling, open several hot
water faucets to allow air to escape from the water system. When a steady
stream of water flows through the faucets, close them and check all water
connections for possible leaks. NEVER OPERATE THE WATER HEATER WITHOUT FIRST
BEING CERTAIN IT IS FILLED WITH WATER.
WARNING Hydrogen gas can be produced in a hot water system served by this water heater that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable. To reduce the risk of injury under these conditions, it is recommended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance connected to the hot water system. If hydrogen is present, there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow. There should be no smoking or open flame near the faucet at the time it is open.
WARNING For protection against excessive temperatures and pressure, install temperature and pressure protective equipment required by local codes, but not less than a combination temperature and pressure relief valve certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment or materials, as meeting the Requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22, and the Standard CAN1-4.4 Temperature, Pressure, Temperature and Pressure Relief Valves and Vacuum Relief Valves. The combination temperature and pressure relief valve shall be marked with a maximum set pressure, not to exceed the maximum working pressure of the water heater. The combination temperature and pressure relief valve shall also have an hourly rated temperature steam BTU discharge capacity not less than the hourly input rating of the water heater. Install the combination temperature and pressure relief valve into the opening provided and marked for this purpose on the water heater
Note: Some models may already be equipped or supplied with a combination
temperature and pressure relief valve. Verify that the combination temperature
and pressure relief valve complies with local codes. If the combination
temperature and pressure relief valve does not comply with local codes,
replace it with one that does. Follow the installation instructions above on
this page. Install a discharge line so that water discharged from the
combination temperature and pressure relief valve will exit within six (6)
inches (15.3 cm) above, or any distance below the structural floor and cannot
contact any live electrical part. The discharge line is to be installed to
allow for complete drainage of both the temperature and pressure relief valve
and the discharge line. The discharge opening must not be subjected to
blockage or freezing. DO NOT thread, plug or cap the discharge line. It is
recommended that a minimum of four (4) inches
(10.2 cm) be provided on the side of the water heater for servicing and
maintenance of the combination temperature and pressure relief valve.
Do not place a valve between the combination temperature and pressure relief
valve and the tank.
CAUTION INCREASING THE THERMOSTAT SETTING ABOVE THE PRESET TEMPERATURE
MAY CAUSE SEVERE BURNS AND CONSUME EXCESSIVE ENERGY. HOTTER WATER INCREASES
THE RISK OF SCALD INJURY.
This water heater can deliver scalding temperature water at any faucet in the
system. Be careful whenever using hot water to avoid scalding injury. Certain
appliances, such as dishwashers and automatic clothes washers, may require
increased temperature water. By setting the thermostat on this water heater to
obtain increased temperature water required by these appliances, you may
create the potential for scald injury. To protect against injury, you should
install an ASSE approved mixing valve in the water system. This valve will
reduce point of discharge temperature by mixing cold and hot water in branch
supply lines. Such valves are available from the manufacturer listed on the
rating plate or from your local plumbing supplier. Please consult with a
plumbing professional. Water temperature over 125°F (52°C) can cause severe
burns instantly or death from scalds. Children, disabled and elderly are at
highest risk of being scalded.
Review this instruction manual before setting tatem watpeerratu heater. Feel
water before bathing or showering. Temperature limiting valves are available.
APPROXIMATE TIME/TEMPERATURE RELATIONSHIPS IN SCALDS
120°F (49°C)| More than 5 minutes
125°F (52°C)| 1½ to 2 minutes
130°F (54°C)| About 30 seconds
135°F (57°C)| About 10 seconds
140°F (60°C)| Less than 5 seconds
145°F ( 63°C )| Less than 3 seconds
150°F (66°C)| About 1½ seconds
155°F (68°C)| About 1 second
Upright Models (See Figure 1A & 1B)
The hot and cold water connections are identified on the top of the water
heater (See figure 1A). For bottom inlet models (-503 models), the cold water
inlet is located on the side of the drain valve (see figure 1B). Connect the
hot and cold water lines to the installed nipples using unions. Install a
listed temperature-pressure relief valve in the remaining fitting
.
Utility Models (See Figure 2)
Utility models are supplied with inlet and outlet nipples located in a plastic
bag attached to the side of the water heater. The hot and cold water
connections are identified on the side of the water heater. Apply appropriate
amount of thread sealant to the provided nipples and install them into the
side of the tank. For 20 gallon utility models, install the supplied
anode/nipple combination at the HOT outlet location. Connect the hot and cold
water lines to the installed nipples using unions. Install a listed
temperature-pressure relief valve in the opening on the side of the water
heater. Install a vacuum relief anti-siphon device in the cold water inlet
line.
Electrical Connections
Before any electrical connections are made, be sure that the water heater is
full of water and that the manual shut-off valve in the cold water supply line
is open. Check the rating plate and wiring diagram before proceeding. This
electric water heater was built and wired in accordance with the INTERTEK
testing approvals requirements. The temperature limiting device is of the
manual reset, trip-free type and has been factory installed to interrupt all
ungrounded power supply conductors in the event of thermostat failure.
Thermostats are factory set and wired in accordance with the wiring diagram
fastened to the inside of the top access panel. The plumbing supplier in your
area ordered this heater wired at the factory to comply with existing area
codes, but local utility codes may require or allow other circuitry. The
thermostats are factory set and wired in accordance with the wiring diagram
affixed to the water heater next to the thermostat/element access cover.
Consult your local power company to determine the correct electrical hook-up
in order to meet local utility and building codes and in order to obtain the
most economical rates. Also check to find out if you are required to obtain a
permit before starting the installation.
The water heater must be well grounded. The green ground wire from the power
supply shall be attached to the terminal marked for this purpose on the
terminal block for all water heaters except 10 and 15 gallon utility models.
For 10 and 15 gallon utility models, the ground wire shall be attached to the
green ground screw located under the element access cover.
Upright and lowboy models are wired for “unbalanced” three phase delta branch
circuit operation. Upright and lowboy models (only) may be converted to single
phase and/or simultaneous operation as shown on the wiring diagram (see figure
3A and 3B). To ensure proper electrical connection, check the voltage and
wiring configuration on the rating plate located on the front of the water
heater.
Run the power leads from an adequately fused disconnect switch (not supplied)
and connect the wires to the water heater according to the wiring diagram
found in these installation and operation instructions (see figures 3A, 3B, 4
and 4A for correct wiring diagram) and located on the front of the water
heater. Where longer runs are needed or local codes and ordinances require, an
increase in wire size may be necessary. Consult local codes and/or your local
power company for any specific requirements which may apply. In the absence of
local codes and ordinances, refer to the National Electrical Code
.
The following tables show the recommended fuse size for the maximum wattage supplied to the water heater. The maximum wattage and rate voltage are shown on the water heater data plate.
BRANCH CIRCUIT SIZING GUIDE
Watt Load| Recommended over current protection rating| Copper wire size – AWG
Based on N.E.C. Table 310-16| Approximate Recovery Gal./Hr. @100°F Rise
120V| 208V| 240V| 120V| 208V| 240V
1500| 15| 15| 15| 12| 14| 14| 6.1
2000| 20| 15| 15| 10| 14| 14| 8.2
2500| 30| 15| 15| 10| 14| 14| 10.2
3000| 30| 20| 15| 8| 12| 12| 12.3
3500| | 20| 20| | 10| 12| 14.3
4000| | 25| 20| | 10| 10| 16.4
4500| | 30| 25| | 10| 10| 18.4
5000| | 30| 30| | 10| 10| 20.5
5500| | 35| 30| | 8| 10| 22.5
6000| | 35| 30| | 8| 8| 24.8
9000| | 50| 45| | 8| 6| 36.9
10000| | 60| 55| | 4| 4| 41.0
11000| | | 30| | | 4| 45.1
FOR YOUR SAFETY
Increasing the wattage and/or voltage from the factory original equipment can
require changes to the water heater and/or the electric service. Unauthorized
modification of the water heater may create a hazard to life and property and
will nullify the warranty. Contact your dealer or utility company before
making any changes.
SINGLE PHASE FULL LOAD CURRENT DRAW
(NON-SIMULTANEOUS OPERATION)
Element Wattage| 120V| 208V| 240V| 277V| 380V| 415V| 480V
1500/1500| 12.5| 7.2| 6.3| 5.4| 3.9| 3.6| 3.1
2000/2000| 16.7| 9.6| 8.3| 7.2| 5.3| 4.8| 4.2
2500/2500| 20.8| 12.0| 10.4| 9.0| 6.6| 6.0| 5.2
3000/3000| 25.0| 14.4| 12.5| 10.8| 7.9| 7.2| 6.3
3500/3500| N/A| 16.8| 14.6| 12.6| 9.2| 8.4| 7.3
4000/4000| N/A| 19.2| 16.7| 14.4| 10.5| 9.6| 8.3
4500/4500| N/A| 21.6| 18.8| 16.2| 11.8| 10.8| 9.4
5000/5000| N/A| 24.0| 20.8| 18.8| 13.2| 12.0| 10.4
5500/5500| N/A| N/A| 22.9| 19.9| 14.5| 13.3| 11.5
6000/6000| N/A| N/A| N/A| 21.7| 15.8| 14.5| 12.5
SINGLE PHASE FULL LOAD CURRENT DRAW
(SIMULTANEOUS OPERATION)
Element Wattage| 120V| 208V| 240V| 277V| 380V| 415V| 480V
1500/1500| 25.0| 14.4| 12.6| 10.8| 7.8| 7.2| 6.2
2000/2000| 33.4| 19.2| 16.6| 14.4| 10.6| 9.6| 8.4
2500/2500| 41.6| 24| 20.8| 18.0| 13.2| 12.0| 10.4
3000/3000| N/A| 28.8| 25.0| 21.6| 15.8| 14.4| 12.6
3500/3500| N/A| 33.6| 29.2| 25.2| 18.4| 16.8| 14.6
4000/4000| N/A| 38.4| 33.4| 28.8| 21.0| 19.2| 16.6
4500/4500| N/A| 43.2| 37.6| 32.4| 23.6| 21.6| 18.8
5000/5000| N/A| 48.0| 41.6| 37.6| 26.4| 24.0| 20.8
5500/5500| N/A| N/A| 45.8| 39.8| 29.0| 26.6| 23.0
6000/6000| N/A| N/A| N/A| 43.4| 31.6| 29.0| 25.0
THREE PHASE (UNBALANCED DELTA) FULL LOAD CURRENT DRAW (NON-SIMULTANEOUS
OPERATION: TERMINALS L1, L2 & L3)
Element Wattage| 208V| 240V| 380V| 415V| 480V
1500/1500| 7.2| 6.3| 3.9| 3.6| 3.1
2000/2000| 9.6| 8.3| 5.3| 4.8| 4.2
2500/2500| 12.0| 10.4| 6.6| 6.0| 5.2
3000/3000| 14.4| 12.5| 7.9| 7.2| 6.3
3500/3500| 16.8| 14.6| 9.2| 8.4| 7.3
4000/4000| 19.2| 16.7| 10.5| 9.6| 8.3
4500/4500| 21.6| 18.8| 11.8| 10.8| 9.4
5000/5000| 24.0| 20.8| 13.2| 12.0| 10.4
5500/5500| N/A| 22.9| 14.5| 13.3| 11.5
6000/6000| N/A| N/A| 15.8| 14.5| 12.5
THREE PHASE (UNBALANCED DELTA) FULL LOAD CURRENT DRAW
(SIMULTANEOUS OPERATION: TERMINAL L3 / TERMINALS L1 & L2)
Element Wattage| 208V| 240V| 380V| 415V| 480V
1500/1500| 12.5/7.2| 10.8/6.3| 6.8/4.0| 6.3/3.6| 5.4/3.1
2000/2000| 16.6/9.6| 14.4/8.3| 9.1/5.3| 8.3/4.8| 7.2/4.2
2500/2500| 20.8/12.0| 18.0/10.4| 11.4/6.6| 10.4/6.0| 9.0/5.2
3000/3000| 25.0/14.4| 21.6/12.5| 13.7/7.9| 12.5/7.2| 10.8/6.3
3500/3500| 29.1/16.8| 25.2/14.6| 15.9/9.2| 14.6/8.4| 12.6/7.3
4000/4000| 33.3/19.2| 28.8/16.7| 18.2/10.5| 16.7/9.6| 14.4/8.3
4500/4500| 37.4/21.6| 32.4/18.8| 20.5/11.8| 18.8/10.8| 16.2/9.4
5000/5000| 41.6/24.0| 36.0/20.8| 22.8/13.2| 20.8/12.0| 18.0/10.4
5500/5500| N/A| 39.6/22.9| 25.0/14.5| 22.9/13.3| 19.9/11.5
6000/6000| N/A| N/A| 27.3/15.8| 25.0/14.5| 21.7/12.5
GENERAL OPERATION
Before closing the switch to allow electric current to flow to the water heater, make certain that the water heater is full of water and that the cold water inlet valve is open. Complete failure of the heating element(s) will result if they are not totally immersed in water at all times. Failure of the element(s) due to dry-firing is not covered by warranty. When the switch is closed, the operation of this electric water heater is automatic. The thermostats are preset BELOW the “HOT” setting to provide a water temperature of approximately 125°F (52°C) to reduce the risk of scald injury.
CAUTION Scalding may occur within five (5) seconds at a temperature setting of 140°F (60°C). Care must be taken whenever using hot water to avoid scalding injury. Certain appliances require high temperature hot water (such as dishwashers and automatic clothes washers).
TO FILL THE WATER HEATER
- Close the water heater drain valve (if provided) by inserting a standard flat head screwdriver into the slot and turning clockwise.
- Open the cold water supply shut-off valve.
- Open several hot water faucets to allow air to escape from the system.
- When a steady stream of water flows from the faucets, the water heater is filled. Close the faucets and check for water leaks at the water heater drain valve, combination temperature and pressure relief valve and the hot and cold water connections.
TO DRAIN THE WATER HEATER
Should it become necessary to completely drain the water heater, make sure you
follow the steps below:
- Disconnect the power supply to the water heater. Consult the plumbing professional or electric company in your area for service.
- Close the cold water supply shut-off valve.
- Open the drain valve (if provided) on the water heater by inserting a standard flat head screwdriver into the slot and turning counter-clockwise. The drain valve has threads on the end that will allow connection of a standard hose coupling. For those models not equipped with a drain valve, disconnect cold water inlet piping at a convenient connection location as close to an adequate drain as possible. CAUTION! THIS WATER MAY BE HOT.
- Open a hot water faucet to allow air to enter the system.
To refill the water heater, refer to “TO FILL THE WATER HEATER.”
Thermostat Adjustment
CAUTION Before adjusting thermostat(s), turn off power supply to the
water heater.
The temperature of the water can be changed by adjusting the thermostat(s).
Before any work is done on the water heater, disconnect all power to the water
heater by opening the switch at the main electrical circuit breaker or fuse
box. Remove the access panels or front panel on table tops, fold the
insulation outward away from the controls. Set the thermostat(s) to the
desired water temperature using a screwdriver to move the thermostat dial. The
thermostat has been factory preset to approximately 125°F (52°C). Rotate the
temperature dial clockwise to increase water temperature. Replace the
insulation making sure that the controls are well covered and that the plastic
terminal shield has not been displaced; replace the access panel. The water
heater is now ready for operation and the main switch can be closed.
DA NGER Hotter water increases the risk of scald injury. Scalding may
occur within five (5) seconds at a temperature setting of 140°F (60°C). To
protect against hot water injury, install an ASSE approved mixing valve in the
water system. This valve will reduce point of discharge water temperatures by
mixing cold and hot water in branch water lines. A licensed plumbing
professional or local plumbing authority should be consulted.
Note: This water heater is equipped with an energy cut out device to
prevent overheating. Should overheating occur, turn off the electrical supply
to the water heater and contact a qualified service technician.
MAINTENANCE
IMPORTANT The water heater should be inspected at a minimum of annually
by a qualified service technician for damaged components. DO NOT operate this
water heater if any part is found damaged.
Shut off the electric power whenever the water supply to the water heater is
off. Shut off the electric power and water supply, drain the heater completely
to prevent freezing whenever the building is left unoccupied during the cold
weather months. In order to insure efficient operation and long tank life,
drain the water heater at least once a month through the drain valve until the
water runs clear. Failure to do this may result in noisy operation and lime
and sediment buildup in the bottom of the tank. Check the temperature-pressure
relief valve to insure that the valve has not become encrusted with lime. Lift
the lever at the top of the valve several times until the valve seats properly
without leaking and operates freely.
WARNING When lifting lever of temperature-pressure relief valve, hot water will be released under pressure. Be certain that any released water does not result in bodily injury or property damage. The magnesium anode rod should be inspected periodically and replaced when necessary to prolong tank life. The following maintenance should be performed by a qualified service technician at the minimum periodic intervals suggested below. In some installations, the maintenance interval may be more frequent depending on the amount of use and the operating conditions of the water heater. Regular inspection and maintenance of the water heater will help to insure safe and reliable operation.
-
Annually, check the operation of the thermostat(s).
-
Bi-annually, check the seal around the heating elements for leaks. If there is any sign of leaking, disconnect the power supply to the water heater and contact the plumbing professional who installed this water heater or a qualified service technician.
-
At least once a year, check the combination temperature and pressure relief valve to insure that the valve has not become encrusted with lime. Lift the lever at the top of the temperature-pressure relief valve several times until the valve seats properly without leaking and operates freely.
WARNING When lifting lever of temperature-pressure relief valve, hot water will be released under pressure. Be certain that any released water does not result in bodily injury or property damage. -
If the combination temperature and pressure relief valve on the appliance discharges periodically, this may be due to thermal expansion in a closed water supply system. Contact the water supplier or local plumbing inspector on how to correct this situation. Do not plug the combination temperature and pressure relief valve outlet for any reason.
-
Monthly, drain off a gallon of water from the water heater to remove silt and sediment.
WARNING! THIS WATER MAY BE HOT. -
A combination sacrificial anode rod/hot water outlet nipple has been installed to extend tank life. The anode rod should be inspected periodically (every 2 years) and replaced when necessary to prolong tank life. Water conditions in your area will influence the time interval for inspection and replacement of the anode rod. Contact the plumbing professional who installed the water heater or the manufacturer listed on the rating plate for anode replacement information. The use of a water softener may increase the speed of anode consumption. More frequent inspection of the anode is needed when using softened (or phosphate treated) water.
CAUTION FOR YOUR SAFETY, DO NOT ATTEMPT TO REPAIR THERMOSTAT(S), HEATING ELEMENTS, OR ELECTRICAL WIRING. REFER SUCH REPAIRS TO A QUALIFIED SERVICE TECHNICIAN.
Contact your local plumbing supplier or plumbing professional for replacement
parts or contact the company at the address displayed on the rating plate of
the water heater.
For faster and better service, please provide the part name, model, and serial
number(s) of the water heater(s) when ordering parts.
READ THE WARRANTY FOR A FULL EXPLANATION OF THE LENGTH OF TIME THAT PARTS AND
THE WATER HEATER ARE WARRANTED.
Manufactured under one or more of the following U.S. Patents:
5,277,171; 5,341,770; 5,372,185; 5,485,879; 5,574,822; 5,596,952; 5,660,165;
5,682,666; 5,761,379; 5,943,984; 5,954,492; 5,988,117; 6,056,542; 6,142,216;
6,442,178; 6,684,821; 6,935,280; 7,063,132; 7,063,133; 7,007,748; 7,270,087;
7,334,419; 7,337,517; 7,409,925; 7,458,341; 7,559,293; 7,621,238; 7,634,976;
7,650,859; 7,665,210; 7,665,211; 7,699,026; 7,866,168; 7,900,589; 7,971,560;
7,992,526 8,082,888; 8,146,772; Other U.S. and Foreign patent applications
pending. Current Canadian Patents: 2,092,105; 2,107,012; 2,108,186; 2,112,515;
2,143,031; 2,239,007; 2,262,174; 2,314,845; 2,409,271; 2,476,685; 2,504,824;
2,548,958
Complete the following information and retain for future reference:
- Model No:
- Serial No:
- Service Phone
- Days:
- Nights:
- Address:
- Supplier:
- Supplier Phone No: