red Smoke Alarms RHA240SL 240V AC Mains Power Heat Alarm with Sealed Lithium Battery Backup User Manual
- June 3, 2024
- red Smoke Alarms
Table of Contents
- red Smoke Alarms RHA240SL 240V AC Mains Power Heat Alarm with Sealed
- Main Features
- SPECIFICATION
- LOCATING THE ALARMS
- POSITIONING THE ALARMS
- INSTALLING THE HEAT ALARM
- OPERATING YOUR HEAT ALARM
- IMPORTANT SAFEGUARDS
- LIMITATIONS OF THE HEAT ALARM
- YOUR HEAT ALARM GUARANTEE
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
red Smoke Alarms RHA240SL 240V AC Mains Power Heat Alarm with Sealed
Lithium Battery Backup
MODEL: RHA240SL
(With Sealed Lithium Battery for Backup)
Main Features
- Interconnection up to 40 heat/smoke alarms
- 10 year lithium battery back up (included)
- Sound level 85dB at 3m
- Alarm condition. Audible signal pattern (ISO 7731)
- No need to change the battery
- Fast and easy installation
- Tested and approved to AS1603.3:2018
- Connects with RAC wireless wall controller & R10RF smoke alarms when fitted with RHARFM Wireless Module
- Connects with R240 and R240RC smoke alarms when fitted with RHARFM Wireless Module
- Connects with RHA10RF heat alarms when fitted with RHARFM Wireless Module
This instruction manual contains important information on the correct installation and operation of your heat alarm. Read this manual fully before attempting installation and retain for future reference
SPECIFICATION
- Power Source: 220-240Vac~ 50-60Hz with 3V battery back-up (battery included)
- Battery Back-up: 3V Sealed Lithium Battery
- Battery Back-up Life 10 Year under normal usage In the event of a break in the mains supply the battery will give detector operation for 1 month minimum
- Operation Current: <40mA operation (In Alarm)
- Temperature Rating: 55-59ºC Fixed temperature only
- Maximum Ambient: 40ºC
- Recommended Coverage: 56m2
- Recommended Spacing 13.5m
- Maximum Distance from wall: 7.7m
- Alarm Sound Level: 85 Decibels at3metres (10ft)
LOCATING THE ALARMS
- Heat alarms are intended to be supplementary to smoke alarms and should only be placed in areas where smoke alarms cannot be used. This heat alarm is a multiple station heat alarm and can only be connected to other alarms of the same make and type. This interconnect feature allows up to 40 heat alarms and / or smoke alarms to be connected together over 150 metres maximum, using either wired or wireless connection (when fitted with RARFM wireless module), and thus allowing all alarm to sound when any one, interconnected alarm is activated.
- This heat alarm cannot be connected to any other device such as a fire alarm panel.
- This heat alarm gives a fire warning when the temperature at the unit reaches 55-59ºC. It is ideal for kitchens, garages, cellars and other areas where there are normally high levels of fumes, smoke or dust which preclude the use of smoke alarms due to the risk of false alarms.
- All the heat alarms and smoke alarms should be interconnected to ensure the early warning will be heard, particularly by somebody sleeping. A properly designed early warning fire system ensures an alarm is given to occupants of a dwelling before the escape routes become blocked with smoke. Therefore there must be Smoke Alarms along the escape routes as Heat Alarms would not give sufficient warning. However, a fire in a closed room (e.g. kitchen) adjoining the escape route, can eventually cause the corridor to become smoke-logged due to smoke leaking out from around the door before adequate warning can be given by detectors in the corridor. A heat Alarm in the closed room may give early warning of fire in that room
- If your dwelling is on a single storey, for minimum protection you should fit a smoke alarm in a corridor or hallway between the sleeping and living areas. Place it as near to the living areas as possible and ensure the audible alarm can be heard when the bedrooms are occupied. See Figure 1 for examples.
- If your dwelling is multi-storey, for minimum protection one smoke alarm should be fitted at the bottom of the staircase with further alarms fitted on each upstairs landing.
- This includes basements but excludes crawl spaces and unfinished attics. See Figure 2 for examples.
POSITIONING THE ALARMS
Ceiling Mounting
As hot smoke rises and spreads quickly, it is advisable to mount the unit on the ceiling in a central position. Avoid areas where there is no air circulation, e.g. corners of rooms and keep away from items which may prevent the free flow of air. Place the unit at least 300mm from any light fitting or decorative object which might obstruct smoke / heat entering the alarm. Keep at least 300mm away from walls.
Wall Mounting
Do not mount tight into the corners. Put the top edge of your smoke alarm
between 150 and 300mm below the ceiling. Keep at least 300mm from room
corners. See Figure 3i
(Wall mounting is not recommended for heat alarms)
On a Sloping Ceiling
In areas with sloping or peaked ceilings install your heat alarm 900mm from the highest point measured horizontally because “dead air” at the apex may prevent smoke from reaching the unit. See Figure 3ii.
Areas to be avoided include the following :
- Situations where the temperature may fall below -10oC or rise above 40oC
- Humid areas such as bathrooms, kitchens, shower rooms where the relative humidity may exceed 90%
- Near a decorative object, door, light fitting, window molding etc., that may prevent smoke or heat from entering the alarm.
- Adjacent to or directly above hot components such as radiators or wall vents that can effect the direction of air currents.
- In very dusty or dirty environments such as workshops.
- Locate unit at least 1.5m and route wiring at least 1m away for fluorescent light fittings as electrical “noise” and/or flickering may affect the unit. Do not wire into the same circuit as fluorescent lights or dimmers.
- Do not locate in insect infested areas. Insects and contamination on the heat alarm sensor can increase its response time.
INSTALLING THE HEAT ALARM
WARNING – This heat alarm is mains powered and must be installed by a
licensed electrician.
The circuit used to power the heat alarm must be a dedicated permanent supply
that cannot be switched off accidentally by the normal user. Before installing
ensure the electrical supply is isolated.
WARNING : To prevent injury, this heat alarm must be securely attached to
the ceiling/wall in accordance with the installation instructions.
The heat alarm will function correctly either as a stand-alone alarm or
interconnected. All interconnected heat alarms must be supplied from a single
power circuit. A common neutral must be used for the interconnectiont to
function.
- Disconnect the AC main power from the circuit that is going to be used.
- Having established the mounting location install a junction box suitable for locating the termination point. Ensure that there is no other electrical wiring or pipe work in the area adjacent to the mounting surface.
- To fix the mounting base into position
- Use a Screw driver to remove the Wiring Cover. See Figure 5.
- Connect the wires to the correct terminals (on the mounting base) to incoming supply. If the smoke/heat alarm are to be interconnected, link out the interconnection terminals. Ensure the screws are fully tightened. See Figure 6.
- Fix mounting base in position.
- Wire connection instruction to the mounting base
- Strip the Active/Neutral and Inter-connect (if used) wires.
- The alarm must be wired in accordance with National wiring codes.
LIVE | Connect to house wires coloured Brown, Red or marked with L. |
---|---|
NEUTRAL | **Connect to house wires coloured Blue, Black or marked with |
N.
INTER- CONNECT| Normally not used except to hardwire interconnect
to the mains smoke/heat (Garvan model GNS-Series.) Never use EARTH wire for
interconnect wire.**
WARNING: Do not connect the Interconnect wire to Live or Neutral
- Assemble alarm unit to the mounting base
- Before assembling the alarm unit to the mounting base, test the correct operation of the heat alarm (operating from the battery only) by pressing the test button on the front of the alarm. The unit should emit a loud pulsating alarm.
- Assemble the alarm unit onto the mounting base by sliding it in according to the direction of the arrows.
- Restore the AC supply
- Test the correct operation of the heat alarm by pressing the test button on the front of the detector. The unit should emit a loud pulsating alarm.
- To remove the alarm unit from the mounting base
- Use a screw drive to release the alarm unit from the mounting base by pushing up the temporary latch with a screw driver. See Figure 4
- Slide the alarm unit out from the mounting base.
WARNING: Connection to the EARTH terminal is not needed for correct functioning of the heat alarm. It is just for conveniently terminating any earth supply wire coloured green or green/yellow. It does not provide protective Earth for the heat alarm
OPERATING YOUR HEAT ALARM
Once the heat alarm has been installed a small GREEN indicator light (LED)
should be visible through the alarm grill indicating that AC supply is
healthy. A RED indicator light (LED) should also flash approximately once a
minute to indicate the battery is healthy and the unit is operating properly.
When the heat alarm senses temperature above 60ºC (plus or minus a few
degrees), the unit will emit a loud (85dB) pulsating alarm until the
temperature drops below 60ºC. During the alarm condition, the LED indicator
light (LED) willflashquickly
TESTING YOUR HEAT ALARM
- It is recommended that you test your heat alarm once a week to ensure the detector is working correctly.
- Push and hold the test button for approximately 3 seconds. A loud pulsating alarm should sound and a RED flashing indicator light (LED) can be seen to indicate the correct function.
NOTE – for multiple interconnected Smoke / heat alarms, only the RED indicator light (LED) of the originating unit will flash rapidly. All other units in the interconnect system will sound an alarm but their RED indicator light (LED) will NOT flash. Test each alarm checking that the alarm is triggered on all other alarms installed.
MAINTAINING YOUR HEAT ALARM
Clean your heat alarm at least once every six months to prevent dust build up.
This can be done using a vacuum cleaner with the brush attachment. Clean
gently around the front grilled section and sides.
WARNING: The apparatus shall not be exposed to dripping or splashing and
no objects filled with liquids, such as vases, shall be placed on the
apparatus.
LOW BATTERY WARNING
-
If the heat alarm emits a short ‘beep’ once every 40 seconds the battery is at the end of its life and this detector should be replaced immediately.
-
This low voltage warning will be given for at least 30 days.
-
If the red indicator light (LED) does not flash every 40 seconds then replace the whole heat alarm unit.
Note : the other interconnected units in the system which are NOT in low battery condition will also chirp, however only for a few seconds, once an hour, for as long as the detector with the “dead” battery beeps. -
The Heat alarm that chirps every 40 seconds is the only heat alarm that needs to be replaced.
WARNING : BATTERY IS NON-REPLACEABLE
The secondary backup power for the heat alarm is supplied by a non-removable rechargeable lithium battery. The battery is sealed in the heat alarm and cannot be replaced. If the red indicator light (LED) does not flash every minute then replace the heat alarm.
IMPORTANT SAFEGUARDS
Installation of your heat alarm is only one step in your safety plan. Other important steps should be taken to further improve your safety:-
- Install the heat alarm properly, following this instruction manual
- Test your Heat Alarm weekly
- Do not smoke in bed
- Keep matches & lighters away from children
- Store flammable materials in a proper manner and never use them near naked flames or sparks
- Maintain emergency equipment such as Fire Extinguishers, escape ladders etc and ensure all occupants know how to use them correctly.
- Plan an escape route/s from your building in advance and ensure all occupants are aware of them. Re-enforce this awareness periodically through-out the year.
- Make sure escape routes remain free of any obstructions.
WARNING: IF THERE IS ANY QUESTION AS TO THE CAUSE OF AN ALARM IT SHOULD
BE ASSUMED THAT THE ALARM IS DUE TO AN ACTUAL FIRE AND THE DWELLING SHOULD BE
EVACUATED IMMEDIATELY.
THIS PRODUCT IS A SEALED UNIT AND CANNOT BE REPAIRED – IF THE UNIT IS TAMPERED
WITH IT WILL INVALIDATE THE WARRANTY. IF THE UNIT IS FAULTY PLEASE RETURN IT
TO YOUR ORIGINAL SUPPLIER WITH YOUR PROOF OF PURCHASE.
LIMITATIONS OF THE HEAT ALARM
Heat Alarms are not designed to be life saving devices against fire and smoke.
In most fires, hazardous levels of toxics gases and smoke can build up before
the Heat Alarm will operate. In cases where life safety is an issue, Heat
Alarms should only be used to provide an added source of protection.
Heat alarms cannot provide an alarm if heat does not reach the alarm.
Therefore, Heat Alarms may not sense fires starting on the other side of a
closed door or on a different floor. Smoke alarms should be installed in each
sleeping area, on every level of a home and be interconnected with each other
and the heat alarms.
Home fires develop in different ways and are often unpredictable. No one type
of alarm is always best, and a given alarm may not always provide warning of a
fire.
YOUR HEAT ALARM GUARANTEE
These Heat Alarms are guaranteed to be free from defects in materials and
workmanships under normal use and service for a period of ten years from date
of manufacture. The company will not be obligated to repair or replace parts
which are found to be in need of repair because of misuse, damage or
alterations occur after the date of purchase. The liability of the company
arising from the sale of this Heat Alarm shall not in any case exceed the cost
of replacement of Heat Alarm and in no case shall the company be liable for
consequential loss or damages resulting from the failure of the Heat Alarm.
Interconnection to any other brand of heat or smoke alarm apart from RED, will
void warranty on this product
RED SMOKE ALARMS PTY. LTD SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY OR
PROPERTY DAMAGE, OR ANY SPECIAL INCIDENTAL, CONTINGENT OR CONSEQUENTIAL DAMAGE
OF ANY KIND RESULTING FROM A FIRE. THE EXCLUSIVE REMEDY FOR BREACH OF THE
LIMITED WARRANTY CONTAINED HEREIN IS THE REPAIR OR REPLACEMENT OF THE
DETECTIVE PRODUCT AT RED SMOKE ALARMS PTY. LTD OPTION. IN NO CASE SHALL RED
SMOKE ALARMS PTY. LTD’S LIABILITY UNDER ANY OTHER REMEDY PRESCRIBED BY LAW
EXCEED THE PURCHASE PRICE. YOUR HEAT ALARM IS NOT A SUBSTITUTE FOR PROPERTY,
DISABILITY, LIFE OR OTHER INSURANCE OF ANY KIND. APPROPRIATE COVERAGE IS YOUR
RESPONSIBILITY. CONSULT YOUR INSURANCE AGENT.
- This does not affect your statutory rights.
- This alarm is only suitable for single occupancy private dwellings only and not intended for multi occupancy private dwellings or commercial or industrial dwellings.
- Alternative Energy Sources – (Wind, Solar, UPS etc.) This product is designed to be connected to a Pure or True Sine Wave 230V AC supply. If connecting to a power source that utilises an inverter, e.g. PV solar panel, the Total Harmonic Distortion (THD) must be less than 5%. If in doubt please check with the manufacturer of the inverter.
- This also applies to battery powered UPS (Uninterruptible Power Supply) inverters.
- Waste electrical products should not be disposed of with normal household waste. Please recycle where facilities exist. Check with your Local Authority or retailer for recycling advice.
- Red Smoke Alarms reserves the right to change specifications, modify designs and discontinue items without incurring obligation and whilst every effort is made to ensure that descriptions, specifica-tions and other information in this catalogue are correct, no warranty is given in respect these of and the company shall not be liable for any error therein.
© Red Smoke Alarms 2021
This material copyright under Australian and international laws. Except as
permitted under the relevant law, no part of this work may be reproduced by
any process without prior written permission of and acknowledgment to Red
Smoke Alarms.
RED SMOKE ALARMS PTY. LTD 35 Hitech Drive, Kunda Park QLD 4556
service@redsmokealarms.com.au
www.redsmokealarms.com.au
1300 316 552