elektrotechnik SCHABUS 300892 GAS ALARM GX-A1+ Multifunction Gas Detectors Instruction Manual
- June 3, 2024
- Elektrotechnik SCHABUS
Table of Contents
SCHABUS 300892 GAS ALARM GX-A1+ Multifunction Gas Detectors
Instruction Manual
THANK YOU FOR YOUR CONFIDENCE!
In order to be able to constantly guarantee the product’s optimum
functionality and readiness for operation as well as your safety, we have a
request: Please thoroughly read this operating instruction prior to the first
use and observe all safety instructions! The operating instruction is a
component of this product. Keep this, so you can always refer to it.
DELIVERY SCOPE
► 1 control device GX-A1+ without sensor
► 1 operating manual
► 1 Assembly material (4 screws , wall plugs)
Accessories (not included in delivery)
► gas sensor, must be ordered separately according to the type of gas
► warning lamp
► telephone dialer
► cut-off valve
► alarm horn
SAFETY INSTRUCTIONS
2.1 General
- Before you start mounting the device please read the operating instructions carefully.
- The installation shall be performed by qualified personnel.
- Packaging material is not a children´s toy. Keep it away from children!
2.2 Ambient conditions
The standards used to assess the product specify limit values for use in the
living area, business area and in small enterprises; the product has been
intended for use in the following operating environments:
- Residential buildings/living areas such as houses, flats, rooms, etc. selling areas such as shops, wholesale markets, etc.
- Premises of small enterprises such as workshops, service centers, etc.
- All areas of application characterize themselves by a connection to the public low voltage mains.
APPROPRIATE USE
The GAS ALARM GX-A1+ is a gas warning device for various gases and can already
deliver a warning at a gas concentration that lies below life-threatening
values. This monitoring system is, therefore, in line with its purpose, set to
a very high sensitivity. For each type of gas, a suitable sensor must be used
(for information on trigger levels and minimum concentration, see the
instructions for the sensor).
An LCD display keeps you continually informed of the current gas
concentration. The alarm is signalled acoustically and optically. At the same
time, a potential-free relay contact is closed, which can be used, for
example, to cut off the gas line by means of a magnetic cut-off valve so that
no further gas can escape from any leakage of the gas line or gas furnance.
The device may not be used in areas with a risk of explosion. Another use of
the device as described above is not authorized.
INSTALLATION INSTRUCTIONS
The assembly must be carried out by a qualified specialist.
Please note the five safety rules!
The GAS ALARM GX-A1+ and the sensor may only be installed in dry interiors of
residential buildings and rooms with similar uses and must be correctly
positioned depending on the gas type so that the warning device functions
properly.
4.1 Wall mounting
GX-A1+ For wall mounting, the four housing screws at the corners of the front
panel must be loosened. Then the front panel is removed and, if necessary, the
ribbon cable is pulled off the connector. The lower shell of the housing can
now be mounted on a wall (mounting material is included).
Important! The connection cables that lead to the gas detector must be
permanently installed as surface-mounted cables.
4.2 Sensor mounting
Depending on the type of sensor connected, the device detects various gases,
e.g. town and natural gas (methane/butane), coolants and refrigerants or CO2.
A prescribed mounting height is necessary for each sensor type, as gases have
different properties.
For carbon monoxide there are specialized gas warning systems, e.g. the
GX-C300 series.
It is essential to pay attention to the prescribed mounting height!
Please read the instructions for use of the sensor you want to use and find
out the specified mounting height from it!
Available and compatible sensors (07/2021)
GX-SE | 200897 | Town / natural gas (methane, butane, propane, ethanol, …) |
---|---|---|
GX-CFC | 200901 | Coolant / refrigerant (R22, R32, R404a, R410a, R1234yf, …) |
GX-DS | 200884 | Carbon dioxide from used air (2500 ppm) |
GX-CO2-25 | 200989 | CO2 from used air (2500 ppm with its own alarm) |
GX-CO2-30 | 300315 | CO2 from techn. systems under pressure (3% vol., own alarm) |
4.3 Pin assignment sensor
Note the color coding of the sensor cable (see also 4.5 Connection diagram).
brown | 5 volts operating voltage | connection terminal 1 (left) |
---|---|---|
white | sensor voltage | connection terminal 2 (middle) |
green | gnd / 0 volt / ground | connection terminal 3 (right) |
4.4 Terminal assignment relay
When connecting accessory devices to the potential-free relay, make sure that
the max. switching current of 5 amperes is not exceeded.
► Relay status in monitoring mode:
The relay is “picked up” (normally open contact closed / normally closed
contact open)
► Relay status in alarm or error mode:
The relay “drops out” (NO contact open / NC contact closed)
Limit data:
Application
example
connections:| Re1 (alarm) 250 V ~ / 5 A
• Shutdown of the gas boiler
• Solenoid shut-off valve
• Signal horn / warning light| Re2 (error) 60 V = / 5 A
• building management system
• Telephone dialer
• Bus connection modules
---|---|---
COMMISSIONING/FUNCTIONAL TEST
An electrical function test is carried out when the mains voltage is applied,
then the heatingup phase is started for approx. 3 minutes, the display shows
System: OK and Sensor: Preheat until the sensor has reached the required
operating temperature, then Sensor: Ready Please note: Even in the event of a
power failure, the test and the heating-up phase are restarted.
5.1 This is how the warning system works
The GX-A1+ evaluates voltages supplied by the sensor. In passive sensors, such
as the GXSE, the gas-sensitive tin oxide is located in a voltage divider,
which changes its partial voltage according to the detected gas concentration.
With active sensors such as the GX-CO2-30, this voltage is generated by a
µController. The following voltage ranges are interpreted and displayed by the
GX-A1+ :
Display: top line | bottom line |
---|---|
0,0 | … 0,1V |
0,1 | … 0,3V |
0,3 … | 2,0V |
2,0 | … 2,5V |
2,5 | … 5,0V |
Cable break or total sensor failure Sensor error, voltage too low Monitoring
mode, idle Pre-alarm, sensor voltage in mV Main alarm, sensor voltage in mV *)
Exemplary values.
And this is how the two relays switch depending on the sensor voltage, with
reference to the normally open contact between connections G and S:
Re1 (Alarm) | Re2 (Error) |
---|
0,0 … 0,1V open
0,1 … 0,3V closed
0,3 … 2,0V closed
2,0 … 2,5V closed
2,5 … 5,0V open| open
open
closed
closed
closed
Re drop off after 10 s. ►5.3 (page14)
Re2 drop off after some seconds
Relays pick up during commissioning
Relays remain energized
Re1 drop off after about 10 seconds
In order to prevent the relays from fluttering in the limit range, switch
always take a time delay of around 10 seconds into account.
This is how the display of the three status LEDs and the acoustic alarm of the
built-in piezo sounder are dependent on the sensor voltage:
| OPERATE green| ERROR
yellow| ALARM
red
---|---|---|---
0,0 … 0,1V| lights up| flashes| off
0,1 … 0,3V| lights up| flashes| off
0,3 … 2,0V| lights up| off| off
2,0 … 2,5V| lights up| off| off
2,5 … 5,0V| lights up| off| flashes
acoustic alarm
one beep every 30 seconds a double beep every 10 seconds no sounds one beep
every 10 seconds interrupted continuous alarm tone
5.2 The RESET / TEST button
5.2.1 The test function
The GX-A1+ has a test function for its internal systems. The connected sensor
is not also tested. To test the sensor, please refer to its operating
instructions to find out what is recommended for the respective type.
To protect your ears from the loud alarm sound, place the heel of your right
hand on the sound opening of the piezo alarm device and press and hold the
RESET / TEST button with your left index finger. After a few seconds each,
the following will happen one after the other:
- The alarm tone sounds continuously, the green and yellow LEDs light up, the red LED and the display backlight flashes
- Relay Re2 „Fault“ drops out
- Relay Re1 „Alarm“ drops out
- After releasing the RESET / TEST button, the Re2 „Fault“ relay pulls immediately on again, LEDs, display and alarm device are back to normal
- Relay Re1 „Alarm“ picks up again
So you can be sure that all acoustic and visual alarms are reliable and that the switching of the relays and their delays work properly. If the test is activated during the „pre-alarm“ phase, no alarm tone can be heard.
5.2.2 The reset function for the acoustic alarm
During the „Alarm“ phase, pressing the RESET / TEST button for 2 seconds has
the function of an acoustic alarm reset, only the acoustic alarm is silenced,
the alarm relay remains deenergized and the visual warning is retained. For
the time the button is pressed during the “alarm” phase, the Re2 “fault” relay
drops out briefly in order to inform the building management system (and
possibly its recording) of the acknowledgment.
5.3 The SERVICE button
In monitoring mode, use the SERVICE button to scroll through the 15 different
display pages to obtain additional information / statistics on your warning
system. A longer (not harder) press on the SERVICE button switches back to the
main display page. Some meters will often already have a number, because we
test your device before delivery. The following information can be called up:
Operating voltage :
Power consumption:| 110 … 240 V~ / 50-60 Hz
2 … 10 VA, depending on the operating status
---|---
Relay contacts:
Relais Re1 „Alarm“:
Relais Re2 „Error“:| 2x potential-free changeover contacts n.o. / n.c.
250 V~ / 5 A / secured
60 V= / 5 A / secured
Sensor connections:
Sensor Operating voltage:
Analysis:| max. 1 sensor possible
5 V= / max. 300 mA
voltage / ADC
Sound pressure piezo alarm device: 2x 16 characters display :| 85dB(A)@1m
white on blue, backlit, flashes in the event of an alarm, text in English
green operate, yellow error, red alarm
Temperature range:
humidity:
Protection class:| 10°C … +50°C
10%rH … 90%rH, not condensing
IP20 (IP65 possible with surcharge)
Connection type:
mounting:
Permanent installation:| Screw terminals (all connections)
Wall mounting (4 screws, dowels included)
Fixed lines as surface-mounted, feed from below, thread prepared for PG screw
connections
Dimensions (H x B x D) :| 80 x 160 x 55 mm
item no. / EAN (GTIN)| 300892 / 4044764004566
GENERAL
Elektrotechnik Schabus GmbH & Co. KG is not liable for damages and/or losses
of any kind such as individual damages or consequential damages brought about
by the gas detector not issuing an alarm despite the presence of an elevated
gas concentration.
To ensure that the sensor is always in a proper functioning state, you should
replace it after 5 years for safety’s sake.
7.1 Cleaning and care
Avoid the effects of moisture (spray or rain water), dust as well as direct
insolation on the device. Clean the device exclusively with a dry linen cloth;
in case of heavy dirt accumulation, it may be slightly moistened. Do not use
any detergents containing solvents.
7.2 Declaration of conformity
The CE mark on the device confirms that it conforms to relevant EU directives.
The declaration of conformity is available for viewing at the address below.
Elektrotechnik Schabus GmbH & Co. KG
Baierbacher Straße 150
D-83071 Stephanskirchen
All rights, technical changes, errors and misprints are reserved.
7.3 Warranty
We grant an implied warranty on material and quality defects of your
electronic product by Elektrotechnik Schabus from the date of purchase.
Elektrotechnik Schabus will repair orreplace your device free of charge on
the following conditions:
-
In case of implied warranty, the device has to be returned with the following documents: error description, proof of purchase as well as your address and delivery address (name, phone number, street, house number, postcode, city, country).
-
Devices returned to Elektrotechnik Schabus shall be sufficiently packaged. Elektrotechnik Schabus will not take liability for any damage or loss during shipment.
-
The device has to have been used in accordance with the operating instructions.
Elektrotechnik Schabus will not take liability for any damage resulting from accident, abuse, modifications or carelessness. -
Elektrotechnik Schabus will not take liability for any loss, damage or costs resulting from the use of the devices or the accessory equipment.
-
The warranty does not affect your statutory rights as consumer.
7.4 Return shipment
Should your device be defective, we offer you the following option:
Contact Elektrotechnik Schabus by
Phone +49 (0) 80 36 / 67 49 79 – 0
Fax +49 (0) 80 36 / 67 49 79 – 79
Email info@elektrotechnik-schabus.de
7.5 Environmental information
For the production of the purchased product, natural raw materials had to be
obtained and used. It may contain substances hazardous to health and the
environment.
In order to avoid the distribution of these substances in your environment and
save natural resources, we ask you to use the appropriate take-back systems.
Thanks to these systems, the materials of your product can be recycled in an
environmentally friendly way, after its service life has expired. (WEEE-NO:
91394868)
The strike-through wastepaper basket symbol reminds you of the use of these
systems.
Should you wish to obtain more information on collection, reuse and recycling
systems, please refer to the waste advisory service in your city. You may also
refer to us to obtain more information on the environmental compatibility of
our products.
Elektrotechnik Schabus GmbH & Co. KG
Baierbacher Str. 150
D-83071 Stephanskirchen
TEL +49 (0) 80 36 / 67 49 79 – 0
FAX +49 (0) 80 36 / 67 49 79 – 79
MAIL info@elektrotechnik-schabus.de
WEB www.elektrotechnik-schabus.de