ASHCROFT GXLdp Differential Indicating Pressure Transmitter Instruction Manual

June 3, 2024
ASHCROFT

GXLdp Differential Indicating Pressure Transmitter

Installation and Operating Instructions for GXLdp Differential Indicating Pressure Transmitter
Ashcroft Inc. 250 East Main Street, Stratford, CT 06614 USA Tel: 203-378-8281, Fax: 203-385-0402 www.ashcroft.com All sales subject to standard terms and conditions of sale. © 2021 Ashcroft Inc. I&M011-10287_RevC_04-22-21 1

2

TABLE OF CONTENTS
Warnings/ General Information…………………………………………………………… 4 Keypad Functions & LCD Display………………………………………………………… 5 Menu Functions/Programming…………………………………………………………… 6-14 Error Messages………………………………………………………………………………..15 Display Resolution Table…………………………………………………………………… 16 Wiring Diagrams……………………………………………………………………………… 17-18 Specifications…………………………………………………………………………………..19 General Dimensions…………………………………………………………………………. 20 Panel Mount Dimensions…………………………………………………………………… 21 Load Limitation Chart……………………………………………………………………….. 22
3

m WARNING! READ BEFORE INSTALLATION m

DESCRIPTION: The Ashcroft Model GXLdp Differential Indicating Pressure Transmitter is to be used with clean, dry, non-corrosive gases. The accuracy is ±0.25% or ±0.50% of Span Terminal Point, and its performance is traceable to the U.S National Institute of Standards and Technology (NIST). Both unidirectional (e.g. 0 to +1.0 in. H2O) and bidirectional (e.g. ±0.25 in. H2O) type ranges are available.
GENERAL: A failure resulting in injury or damage may be caused by excessive overpressure, excessive vibration or pressure pulsation, excessive instrument temperature, corrosion of the pressure containing parts, or other misuse. Consult Ashcroft Inc. Stratford, Connecticut, USA before installing if there are any questions or concerns.
OVERPRESSURE: Pressure spikes in excess of the rated overpressure capability of the transmitter may cause irreversible electrical and/or mechanical damage to the pressure measuring and containing elements.

INSTALLATION AND WIRING INSTRUCTIONS Mounting: The GXLdp transmitter can be mounted on a 35 mm DIN rail or with #8 or #10 screws using the 3 mounting holes provided. Torque limits on the three mounting holes provided is 9.6 inch-pounds. For optional panel mounting information, please refer to page 21.
Electrical Wiring: To open the housing, push the latch through the opening on the right side of the unit until the font cover releases from the body. Connect wiring to the pluggable/unpluggable terminal block. See wiring diagrams on pages 17-18. Use a screwdriver to tighten after the stripped wire is fully inserted. To close the unit, press the front cover against the rear cover firmly until the latch engages. The use of shielded cable is recommended for optimum performance. Connect the shield to the guard terminal on the reading instrument (meter etc.) if available or to ground. The GXLdp will automatically detect if a 2-wire or 3-wire power supply has been used to power up the device.

STATIC ELECTRICAL CHARGES: Any electrical device may be susceptible to damage when exposed to static electrical charges. To avoid damage to the transducer the operator/installer should follow proper ESD (electrostatic discharge) protection procedures before handling the pressure transducer.

4

KEYPAD FUNCTIONS AND LCD DISPLAY INFORMATION
Keypad Functions: Up Arrow Backlight/Back SpoolCalTM Key
Down Arrow Menu/Enter
LCD Display Information: The top (numerical) display portion reads the current pressure range during normal operation. The lower (alphanumeric) display portion reads the engineering units during normal operation. SW1 is present if SW1 (Switch 1) is active. ON or OFF displays depending on trip status of the switch. SW2 is present if SW2 (Switch 2) is active. ON or OFF displays depending on trip status of the switch. mA or Vdc will display depending on the selected Analog Output. 2W or 3W will display depending on if a 2-wire or 3-wire input power supply is connected to the GXLdp.
5

MENU FUNCTIONS/PROGRAMMING Keypad Functions Backlight/Back

The back button

generally moves back

one screen in the menu. The back button also

allows you to continue to move back until you

return to the main menu if you wish to exit

from a specific menu function. This button

also allows the user to turn the Backlight

function on or off with a (2-second) long

button press.

BL ON will flash on the display when the Backlight function is being turned on.

Up Arrow Button

G

The up arrow G generally scrolls up in the menu tree, or performs an adjustment. The up arrow G also allows the user to check the configuration/settings of the GXLdp: Units, Range, Output and Firmware version will all display with a (2-second) long button press. Please note that only the Analog Output is field selectable and the other parameters are as built at the factory. If a long button press of the up arrow G occurs, the menu screens will appear as shown below. Each of these parameters will flash on the screen briefly and then disappear.

BL OFF will flash on the display when the Backlight function is being turned off. After a couple of seconds, the BL OFF message will disappear from the screen.
6

Up Arrow Button (continued)

G MAIN MENU SELECTIONS: A OUT ­ Analog Output: Allows user to choose output signal. DAMP ­ Dampening: Allows user to vary the response time of the GXLdp output. The digital display and the analog output are both updated with the use of the DAMP function. RECAL ­ Recalibration: Allows user to perform a field calibration of the zero and span setting of the GXLdp. RESET ­ Reset: Allows user to reset the GXLdp to its original factory settings. ZERO ­ Zero: Allows the user to perform a user zero offset of the GXLdp SWITC (Optional) ­ Switch function: Allows the user to enable and set one or two NPN or PNP switch outputs.

Down Arrow Button

H

The down arrow H scrolls down in the menu tree.

Menu/Enter

The Menu/Enter button

moves right in

the menu tree, if there is an item to the right.

If there is no item to the right, the Menu/

Enter button

saves the user’s changes

to (non-volatile) memory and exits the menu

tree. This button also allows the user to Zero

the unit from the live display with a (2-second)

long button press. Press Menu/Enter

with

a long button press. The word `ZERO’ will

flash briefly. The unit is now zeroed and will

then return to the main menu (live pressure

readings).

A OUT: Analog Output Analog Output choices are selectable through the menu. There are five Analog Outputs to choose from: 4-20 mA, 0-5 Vdc, 0-10 Vdc, 1-5 Vdc, 1-6 Vdc . a. 4-20 mA is designated by mA’ b. 0-5 Vdc is designated by V0-5′
c. 0-10 Vdc is designated by V0-10′ d. 1-5 Vdc is designated byV1-5′ e. 1-6 Vdc is designated by `V1-6′
Please note that 4-20 mA output can be powered up by a 2-wire or 3-wire Input Power Supply, while a Voltage output must be powered by a 3-wire Input Power Supply. If 4-20 mA output is selected and the SWITCH function is activated, the unit requires a 3-wire Input Power Supply. The GXLdp can automatically detect if the input power is a 2-wire or a 3-wire device. The current Analog Output default can be seen on the digital display of the main menu using one of the designations noted above. A new unit ships with mA (4-20 mA) set as the default.

7

Field Selection of the Analog Output:

1. To change the Analog Output, press the

Menu/Enter button

, and scroll

through the main menu until `A OUT’ is

flashing.

Then press Menu/Enter button

again.

The currently selected analog output will

be flashing.

2. To keep the output the same, press

Menu/Enter

and then while `SAVE’ is

flashing, press Menu/Enter

to return

to the live display.

3. To change the current Analog Output use

the up or down arrow buttons G H until

the desired output is flashing and then

press Menu/Enter

. `SAVE’ will then

be flashing. Press Menu/Enter

to

save this new selection and then you will

return to the live display.

4. f you do not want to save this selection

scroll from SAVE’ toCANCL’, and while

`CANCL’ is flashing, press Menu Enter

and then the unit will return to the live

display with no change to the Analog

Output setting.

DAMP: Dampening User can select from four display response times: a. 250 ms b. 1 sec c. 3 sec d. 5 sec. 250 ms is the standard factory default.

Modify the `DAMP’ (Dampening) selection

in the field:

1. To change the `DAMP’ setting press the

Menu/Enter button

and scroll using

the up or down arrow buttons G H

until `DAMP’ is flashing. Then press the

Menu/Enter button

.

2. The current `DAMP’ setting will be flashing.

3. Scroll using the up or down arrow buttons

G H until the desired dampening time

is flashing. Then press Menu/Enter

Then `SAVE’ will be flashing. Press Menu/

Enter

to save the new DAMP setting.

The unit will then revert to live pressure

readings.

4. If you do not want to save the new `DAMP’

setting, scroll using the up or down arrow

buttons G H until `CANCL’ is flashing.

Press Menu/Enter

. The DAMP set-

ting will not be changed from the previous

setting and the display will revert to live

pressure readings.

RECAL: Re-Calibration The `RECAL’ function in the GXLdp menu provides the user the ability to field calibrate the product. The most recent factory calibration is permanently retained in memory and can be recalled at any time. Both zero and span adjustments are made through the menu.

When a factory new GXLdp is being re-calibrated for the first time in the field, you will have the following options: 1. FACT ­ reverts to the original Factory
Calibration settings. 2. NEW ­ allows the user to perform a new
Calibration in the field.

After the GXLdp has been re-calibrated at least once in the field, you will have the following options: 1. FACT ­ reverts to the original Factory
Calibration settings. 2. NEW ­ allows the user to perform a new
Calibration in the field. 3. FIELD ­ reverts to the most recently
performed Field Calibration.

Factory Calibration (FACT)

Enter Factory Calibration to reset the unit to

its most recent factory calibration parameters.

1. Press the Menu/Enter button

and

8

scroll using the up or down arrow buttons

G H until `RECAL’ is flashing on the dis-

play. Then press Menu/Enter

again.

2. Then the menu choices will be FACT/

FIELD/NEW. Press the up or down arrow

buttons G H until `FACT’ is flashing on

the display.

3. When `FACT’ is flashing on the display,

press the Menu/Enter button

.

4. Then with `SAVE’ flashing on the display

press the Menu/Enter button

.

5. This will restore the most recent factory

calibration.

6. If `SAVE’ is flashing and you do not wish

to `SAVE’ the factory calibration, use the

up or down arrow buttons G H to scroll

to CANCL’ and whileCANCL’ is flashing

on the display, press Menu/Enter

which will return you to the main menu.

New Field Calibration (NEW)

Enter New Field Calibration if you wish to

perform a field calibration of the GXLdp.

1. Press the Menu/Enter button

and

scroll using the up or down arrow buttons

G H until `RECAL’ is flashing on the

display. Press the Menu/Enter Button

.

2. There will be three menu choices FACT/

FIELD/NEW. Scroll using the up or down

arrow buttons G H until `NEW’ is flashing.

3. When `NEW’ is flashing on the display,

press the Menu/Enter Button

.

4. `ADJST/ZERO’ will now be flashing on the

display. This will allow you to calibrate

the Zero value for the GXLdp.

5. Apply zero pressure to the Hi and Lo ports

of the GXLdp. This can be best accom-

plished by shorting the HI and LO ports on

the GXLdp.

6. Using the up or down arrow buttons

G Hscroll until the display reads zero.

Then press the Menu/Enter button .

The unit is now zeroed.

7. `ADJST/SPAN’ will now be flashing on the

display.

8. You will need an external reference pres-

sure source to adjust the span setting.

9. Connect tubing from the reference

pressure source to both the Hi and Lo

pressure ports of the GXLdp.

10. Using the external reference pressure

source, increase the pressure to the

full-scale value of the GXLdp. Then scroll

using the up or down arrow buttons

G H until the display reads the same as

the pressure reference. Note: Span can

be adjusted between 90% and 100% of

the full scale value.

11. Press the Menu/Enter button

.

12. The menu will now flash `SAVE’ on

the display. If you wish to save the

NEW calibration, press the Menu/Enter

button .

13. If you do not want to save the NEW

calibration, use the up or down arrow

buttons G H to scroll from SAVE to

CANCL. With `CANCL’ flashing on the

display press the Menu/Enter button

. This will return the GXLdp to the

main menu and the NEW calibration will

not be saved. The unit will maintain its

most recent calibration.

14. Once you have finished a NEW calibra-

tion, this will be stored as the FIELD

Calibration.

Field Calibration (FIELD)

Enter Field Calibration if you wish to recover

the most recent field calibration values stored

in the GXLdp.

1.Press the Menu/Enter button

and

scroll using the up or down arrow buttons

G H until `RECAL’ is flashing on the

display. Then press Menu/Enter

again.

2. Then the menu choices will be FACT/

FIELD/NEW. Press the up or down arrow

buttons G H until `FIELD’ is flashing on

the display.

9

3. When `FIELD’ is flashing on the display,

press the Menu/Enter button

.

4.Then with `SAVE’ flashing on the display

press the Menu/Enter button

.

5. This will restore the most recent field

calibration.

6. If `SAVE’ is flashing and you do not wish

to `SAVE’ the field calibration, use the up

or down arrow buttons G H to scroll to

CANCL’ and whileCANCL’ is flashing on

the display, press Menu/Enter

which will return you to the main menu.

RESET: This will allow the user to revert to all menu settings as shipped from the factory. This includes: Analog Output, Switch settings (if option is applicable), Damping, and User Zero. This will also clear any saved Field Calibration from memory and reset the GXLdp to the Factory Calibration.

To perform the RESET procedure:

1. Press Menu/Enter

and scroll using

the up or down arrows G H until `RESET’

is flashing. Then press Menu/Enter .

2. `SAVE’ will now be flashing on the display.

If you wish to restore all factory default

settings, press Menu/Enter

while

`SAVE’ is flashing on the display. The unit

will then return to the main menu and all

factory settings will be re-stored including

FACTORY Calibration.

3. If you do not want to restore all factory

default settings, scroll using the up or

down arrow keys G H until `CANCL’ is

flashing on the display, and then press

Menu/Enter . The unit will return to

the main menu and no settings will be

changed.

ZERO (Zeroing function) In addition to being able to Zero from the live display, the user can also Zero the unit through the Menu.

1. Press Menu/Enter

and scroll using

the up or down arrows G H until `ZERO’

is flashing on the display.

2. Press Menu/Enter

and then while

`SAVE’ is flashing press Menu/Enter

again. This will zero the unit, and return

to live pressure readings.

OPTIONAL FEATURES:

SWITC: Switch function The GXLdp is available with an optional switch function. If ordered this feature will allow the user to choose between 1 or 2 PNP or NPN switches as well as allowing the user to choose the set and reset point of each switch. If the user chooses to use two switches, they must be the same type, either PNP or NPN.

NOTE: To set an Increasing set point, the reset value must be lower than the set point To set a Decreasing set point, the reset value must be higher than the set point

To enable and set the switch feature

1. To enable the optional switch, press the

Menu/Enter button

, and scroll

through the main menu using the up or

down arrow buttons G H until `SWITC’ is

flashing. Then press Menu/Enter button

again.

2. Initially, PNP will be flashing on the dis-

play, and you can change the switch type

to NPN by pressing the up or down arrow

buttons G H

3. Once you are on the desired switch type

press the Menu/Enter button

.

4. Initially, SW1 DISAB will be flashing on

the display. Press the up or down arrow

buttons G H until SW1 ENABL is flashing

on the display. Then press the Menu/

Enter button

.

10

5. SW1SP will be flashing on the display.

This will allow the user to calibrate the

SW1 (Switch 1) set point.

6. Press the Up arrow G, this will cause the

first digit to flash.

7. If you wish to change this digit press the

up or down arrow buttons G H

(NOTE: for Bidirectional ranges you can

set the switch for a negative set point,

this will be designated by a minus sign

showing in front of the set point on the

display).

8. Once you adjust the digit to the appropri-

ate number, press the Menu/Enter button

to get to the next digit.

9. Repeat steps 7 & 8 until all 5 digits are

displaying correctly. While the last digit is

flashing, press the Menu/Enter button

. Then SW1SP will be flashing on

the display. Press the Menu/Enter button

again.

10. SW1RS will be flashing on the display.

This will allow the user to calibrate the

Switch 1 reset point.

11. Press the Up arrow G, this will cause

the first digit to flash.

12. To change this digit press the up or

down arrow buttons G H

(NOTE: for Bidirectional ranges you can

set the switch for a negative set point,

this will be designated by a minus sign

showing in front of the set point on the

display).

13. Once you adjust the digit to the appro-

priate number, press the Menu/Enter

button

to get to the next digit.

14. Repeat steps 12 & 13 until all 5 digits

are displaying correctly. While the last

digit is flashing, press the Menu/Enter

button

. Then SW1RS will be

flashing on the display. Press the Menu/

Enter button

again. SW1 setup is

now complete.

15. Then SW2 DISAB will flash on the dis-

play. If you also want to enable switch

two (SW2) repeat steps 4 through 14 to

setup SW2. If you do not wish to enable

SW2, simply press the Menu/Enter but-

ton

while SW2 DISAB is flashing.

16. SAVE will flash on the display. Press

the Menu/Enter button

to save

the settings for both SW1 and SW2. The

display will return to the main menu.

NOTE: Once you have completed the set up for the SWITCH (SWITC) function, any enabled switch is indicated in the lower left portion of the display. If SW1 or SW2 are energized the display will show ON under the appropriate switch, if SW1 or SW2 are de-energized the display will show OFF under the appropriate switch.

SpoolCalTM (XPV): The rotating process valve actuator in conjunction with the SpoolCalTM actuator tool provides two types of available tests including Calibrate (CAL) and Monitor (MONITOR) through the appropriate Hi and Lo Port of the SpoolCal actuator tool. In the CAL (Calibrate) mode, the GXLdp is isolated from the process and allows externally generated test pressure input for calibration. In the MONITOR (Monitor) mode, the live system pressure can be monitored with an ASHCROFT ATE-2 Calibrator or other handheld instrument without physically unplugging the process tubes. The “XPV” option supplies a SpoolCalTM actuator and 7 of silicon tubing. The actuator tool can be set to either CAL (Calibrate mode), MONITOR (Monitor mode) or OFF, and also includes HI (high) and LO (low) differential pressure ports.

11

GXLdp SPOOL CALTM OPERATION
From the `OFF’ position, the SpoolCalTM actuator tool can be inserted and removed. Rotate the actuator tool 90° clockwise for Calibration mode (CAL) or 90° counter clockwise for Monitor mode (MONITOR)
CAL
ROTATE KEY 90° CLOCKWISE TO (CAL) POSITION

OFF HI

MONITOR
LO

OFF POSITION

OFF HI

ROTATE KEY 90° COUNTER CLOCKWISE TO (MONITOR) POSITION
MONITOR
12

Calibration (CAL): Both zero and span adjustments are made through the menu. (For complete calibration details of the GXLdp without using the Spool Cal option, refer to the RECAL section- page 8). A 90-degree clockwise rotation of the SpoolCal key places the unit into `CAL’ mode, this isolates the GXLdp from the process pressure. The RECAL function in the GXLdp menu provides the user the ability to field calibrate the product. The most recent factory calibration is permanently retained in memory and can be recalled at any time.

Once you enter the Re-Calibration (RECAL) Mode you will have the following options: 1. FACT ­ Factory Calibration 2. NEW ­ New Field Calibration 3. FIELD ­ Field Calibration Note: On initial calibration, Field Calibration will not show in the menu. To perform the initial field calibration you will choose New (New Field Calibration). Once you have saved the New Calibration, Field Calibration will appear the next time you enter Calibration Mode.

Factory Calibration (FACT)

Enter Factory Calibration to reset the unit to

its most recent factory calibration parameters.

1. Press the Menu/Enter button

and

scroll using the up or down arrow buttons

G H until `RECAL’ is flashing on the dis-

play. Then press Menu/Enter

again.

2. Then the menu choices will be FACT/

FIELD/NEW. Press the up or down arrow

buttons G H until `FACT’ is flashing on

the display.

3. When `FACT’ is flashing on the display,

press the Menu/Enter button

.

4. Then with `SAVE’ flashing on the display

press the Menu/Enter button

.

5. This will restore the most recent factory

calibration.

6. If SAVE’ is flashing and you do not wish toSAVE’ the factory calibration, use the up or down arrow buttons G H to scroll to CANCL’ and whileCANCL’ is flashing on the display, press Menu/Enter which will return you to the main menu.

New Field Calibration (NEW):

Enter New Field Calibration if you wish to

perform a field calibration of the GXLdp.

1. Press the Menu/Enter button

and

scroll using the up or down arrow buttons

G H until `RECAL’ is flashing on the

display. Press the Menu/Enter Button

.

2. There will be three menu choices FACT/

FIELD/NEW. Scroll using the up or down

arrow buttons G H until `NEW’ is flashing.

3. When `NEW’ is flashing on the display,

press the Menu/Enter Button

.

4. `ADJST/ZERO’ will now be flashing on the

display. This will allow you to calibrate the

Zero value for the GXLdp.

5. Apply zero pressure to the Hi and Lo

ports. This can be best accomplished

by shorting the HI and LO ports on the

SpoolCalTM actuator tool using the silicon

tubing supplied.

6. Using the up or down arrow buttons G H

scroll until the display reads zero. Then

press the Menu/Enter button

. The

unit is now zeroed.

7. `ADJST/SPAN’ will now be flashing on the

display.

8. Remove the silicone tubing from the

SpoolCalTM actuator tool.

9 You will need an external pressure source

to adjust the span setting.

10. Connect tubing from the pressure source

to both the Hi and Lo pressure ports of

the SpoolCalTM actuator tool.

11. Using the external pressure source,

increase the pressure to the full-scale value

of the GXLdp. Then scroll using the up or

down arrow buttons G H until the display

reads the same as the pressure reference.

13

12. Press the Menu/Enter button

.

13. The menu will now flash `SAVE’ on

the display. If you wish to save the

NEW calibration, press the Menu/Enter

button

.

14. If you do not want to save the NEW

calibration, use the up or down arrow

buttons G H to scroll from SAVE to

CANCL. With `CANCL’ flashing on the

display press the Menu/Enter button

.This will return the GXLdp to the

main menu and the unit will maintain its

most recent calibration.

15. Once you have finished a NEW calibra-

tion, this will be stored as the FIELD

Calibration.

Field Calibration (FIELD):

Enter Field Calibration if you wish to recover

the most recent field calibration values stored

in the GXLdp.

1. Press the Menu/Enter button

and

scroll using the up or down arrow buttons

G H until `RECAL’ is flashing on the dis-

play. Then press Menu/Enter

again.

2. Then the menu choices will be FACT/

FIELD/NEW. Press the up or down arrow

buttons G H until `FIELD’ is flashing on

the display.

3. When `FIELD’ is flashing on the display,

press the Menu/Enter button

.

4. Then with `SAVE’ flashing on the display

press the Menu/Enter button

.

5. This will restore the most recent field

calibration.

6. If `SAVE’ is flashing and you do not wish

to `SAVE’ the field calibration, use the up

or down arrow buttons G H to scroll to

CANCL’ and whileCANCL’ is flashing on

the display, press Menu/Enter

which will return you to the main menu.

Monitor (MONITOR): While in MONITOR’ (Monitor) mode, the GXLdp can provide the (live) system pressure measurement without having to physically unplug the process tubes. Insert the SpoolCalTM actuator tool into the side of the GXLdp, while the SpoolCalTM is in theOFF’ position. A 90-degree counterclockwise rotation tee’s the process to both the GXLdp unit and out through the SpoolCalTM actuator tool, and provides external measurement capability with the use of a portable instrument such as the Ashcroft ATE-2. Connect the tubing from the portable instrument to both the high and low pressure port of the SpoolCalTM actuator tool. The user can then verify (live) system pressure readings.

14

GXLdp Error Messages

Note: Multiple Errors may be displayed.

Err02
Err03 Err04 Err05 Err06 Err07 LIMIT OVER S LOC UNDER Z LOC

Configuration Error. Mismatch between sensor serial number on the sensor board and the sensor serial number recorded on the display board. FATAL ERROR.
Calibration Error. Device has not been factory calibrated or the factory calibration data is corrupt. FATAL ERROR.
Settings Error. User Settings (Menu settings) are corrupt. FATAL ERROR.
Communication Error. Pressure sensor has stopped working. FATAL ERROR.
3-Wire Power Error. Voltage output is selected, but there is no external power. This may be field correctable.
Range data missing or corrupt. FATAL ERROR
LIMIT will display if the user tries to Zero more than 5% of Span. LIMIT will also display if the user tries to adjust Span by more than 5% of the positive full-scale value.
OVER will display if the unit is Over-Pressured.
S LOC will display if the user attempts to make a span adjust-
ment at less than 90% of the positive full-scale value.
UNDER will display if the unit is Under-Pressured.
Z LOC will display if the user attempts to make a zero offset adjustment while outside of Zero ±10% of positive full-scale.

15

GXLdp Display Resolution Table

in. H2O Unidirectional 0.10 in. H2O 0.20 in. H2O 0.25 in. H2O 0.40 in. H2O 0.50 in. H2O 0.60 in. H2O 0.75 in. H2O 1.00 in. H2O 2.00 in. H2O 2.50 in. H2O 3.00 in. H2O 5.00 in. H2O 10.00 in. H2O 15.00 in. H2O 20.00 in. H2O 25.00 in. H2O Pa Unidirectional 25 Pa 50 Pa 60 Pa 100 Pa 125 Pa 160 Pa 200 Pa 250 Pa 300 Pa 400 Pa 500 Pa 600 Pa 1.00 kPa 1.60 kPa 2.00 kPa 2.50 kPa 4.00 kPa 5.00 kPa 6.00 kPa

MIN 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.000 0.000 0.000 0.000 0.000 0.00 0.00 0.00 0.00 MIN 0.00 0.00 0.00 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000

MAX 0.1000 0.2000 0.2500 0.4000 0.5000 0.6000 0.7500 1.000 2.000 2.500 3.000 5.000 10.00 15.00 20.00 25.00 MAX 25.00 50.00 60.00 100.0 125.0 160.0 200.0 250.0 300.0 400.0 500.0 600.0 1.000 1.600 2.000 2.500 4.000 5.000 6.000

mb Unidirectional 0.25 mb 0.50 mb 0.60 mb 1.00 mb 1.25 mb 1.60 mb 2.00 mb 2.50 mb 3.00 mb 4.00 mb 5.00 mb 6.00 mb 10.00 mb 16.00 mb 20.00 mb 25.00 mb 40.00 mb 50.00 mb 60.00 mb

MIN 0.0000 0.0000 0.0000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.00 0.00 0.00 0.00 0.00 0.00 0.00

MAX 0.2500 0.5000 0.6000 1.000 1.250 1.600 2.000 2.500 3.000 4.000 5.000 6.000 10.00 16.00 20.00 26.00 40.00 50.00 60.00

in. H2O Bidirectional (±) 0.05 in. H2O (±) 0.10 in. H2O (±) 0.25 in. H2O (±) 0.50 in. H2O (±) 1.00 in. H2O (±) 2.00 in. H2O (±) 2.50 in. H2O (±) 3.00 in. H2O (±) 5.00 in. H2O (±) 8.00 in. H2O (±) 10.00 in. H2O (±) 15.00 in. H2O (±) 25.00 in. H2O

MIN -0.0500 -0.1000 -0.2500 -0.500 -1.000 -2.000 -2.500 -3.000 -5.00 -8.00 -10.00 -15.00 -25.00

MAX 0.0500 0.1000 0.2500 0.500 1.000 2.000 2.500 3.000 5.00 8.00 10.00 15.00 25.00

Pa Bidirectional (±) 15 Pa (±) 25 Pa (±) 30 Pa (±) 50 Pa (±) 60 Pa (±) 100 Pa (±) 125 Pa (±) 160 Pa (±) 200 Pa (±) 300 Pa (±) 400 Pa (±) 500 Pa (±) 600 Pa (±) 1.0 kPa (±) 1.25 kPa (±) 1.6 kPa (±) 2.00 kPa (±) 2.50 kPa (±) 4.00 kPa (±) 5.00 kPa mb Bidirectional (±) 0.15 mb (±) 0.25 mb (±) 0.30 mb (±) 0.50 mb (±) 0.60 mb (±) 1.00 mb (±) 1.25 mb (±) 1.60 mb (±) 2.00 mb (±) 3.00 mb (±) 4.00 mb (±) 5.00 mb (±) 6.00 mb (±) 10.00 mb (±) 12.50 mb (±) 16.00 mb (±) 20.00 mb (±) 25.00 mb (±) 40.00 mb (±) 50.00 mb
16

MIN -15.00 -25.00 -30.00 -50.0 -60.0 -100.0 -125.0 -160.0 -200.0 -300.0 -400 -500 -600 -1.000 -1.250 -1.600 -2.000 -2.500 -4.00 -5.00 MIN -0.1500 -0.2500 -0.3000 -0.500 -0.600 -1.000 -1.250 -1.600 -2.000 -3.000 -4.00 -5.00 -6.00 -10.00 -12.50 -16.00 -20.00 -25.00 -40.0 -50.0

MAX 15.00 25.00 30.00 50.0 60.0 100.0 125.0 160.0 200.0 300.0 400 500 600 1.000 1.250 1.600 2.000 2.500 4.00 5.00 MAX 0.1500 0.2500 0.3000 0.500 0.600 1.000 1.250 1.600 2.000 3.000 4.00 5.00 6.00 10.00 12.50 16.00 20.00 25.00 40.0 50.0

GXLdp Wiring Diagrams 2 Wire 4-20mA Output V+ V- Vout EXT S1 S2

+ Power Vdc –

Optional Low-Side current sense shown in dashed lines

3 Wire 4-20mA Output V+ V- Vout EXT S1 S2

+ Power Vdc –

3 Wire 4-20mA Output V+ With PNP Switches

V- Vout EXT S1 S2
30Vdc/50mA Max 30Vdc/50mA Max

+ Power Vdc –

PNP Load PNP Load

3 Wire 4-20mA Output V+ With NPN Switches

V- Vout EXT S1 S2
30Vdc/50mA Max 30Vdc/50mA Max

+ Power Vdc –

NPN Load NPN Load 17

GXLdp Wiring Diagrams 3 Wire Voltage Output V+ V- Vout EXT S1 S2

+ Power

V

Vdc/Vac –

3 Wire Voltage Output V+ V- Vout EXT S1 S2

With NPN Switches

30Vdc/50mA Max 30Vdc/50mA Max

+ Power Vdc/Vac –

+ V

NPN Load NPN Load

3 Wire Voltage Output V+ V- Vout EXT S1 S2

with PNP Switches

30Vdc/50mA Max 30Vdc/50mA Max

+ Power Vdc/Vac –

+ V

PNP Load PNP Load

18

GXLdp SPECIFICATIONS

Accuracy: ±0.25% or ±0.50% of Span, Terminal Point Method
Range Capability (Unidirectional): 0.1 in. H2O through 25 in. H2O, 25 Pa through 6 kPa, 0.25 mb through 60 mb
Range Capability (Bidirectional): ±0.05 in. H2O through ±25 in. H2O, ±15 Pa through ±5 kPa, ±0.15 mb through ±50 mb
Adjustable Display Response Time Dampening): 250 ms, 1 sec, 3 sec, 5 sec
Temperature Limits: Storage: -22°F to 176°F (-30°C to 80°C) Operating: -4°F to 176°F (-20°C to 80°C) Compensated: 35°F to 130°F (1.6°C to 54°C)
Max. Static (Line) Pressure: 25 psi
Proof Pressure: 15 psid
Burst Pressure: 25 psid
Zero Adjustment: ±5% of span (accessible through menu)
Span Adjustment: ±5% of full scale value (accessible through menu)
Field Selectable Output Signals: Current: 4-20 mA (2-wire or 3-wire) with Supply Voltage: 12-40 Vdc (24 Vdc typical)
Voltage: 0-5 Vdc, 0-10 Vdc, 1-5 Vdc, 1-6 Vdc (all 3-wire) with Supply Voltage: 12-40 Vdc or 24 Vac(± 20%) (24 Vdc/Vac typical)
Reverse polarity and mis-wire protected:
LCD Display: 3-5 digits: The resolution/decimal place is fixed based on the range and is not field changeable. See display resolution chart on Page 16

LCD Screen Dimensions: 2.63 Width x 1.38 Height
LCD Character Size: 7-segment (Numeric display): 0.32 Width x 0.65 Height
14-segment (Alphanumeric display) : 0.28 Width x 0.49 Height
Pressure Connection: 1/8 NPT Female, ¼ Barbed Male, 3/16 Barbed Male
Electrical Connection: ½ NPT Female Conduit Connection / PG9 Watertight Cable Gland included.
Electrical connections made to a pluggable terminal block which accepts 18-24 AWG wires.
Enclosure Rating: UL 94-V0 Flame-retardant ABS, IP67/Nema 4
Process Media: The GXLdp is designed to measure clean, dry non-corrosive gases. Not for use with liquids.
Weight: 0.8 lbs
Mounting: Din Rail/ Wall Mount standard, optional Panel Mount
Optional Switch Feature: Two independent switch outputs, NPN or PNP. Field Programmable -set and reset points. (See detailed description on Pages 10-11)
Optional Spool Cal Actuator: (See detailed description on Pages 11-14)

19

GXLdp GENERAL DIMENSIONS

.21

.50

R.10

5.14
1.86 2.68

2.70 4.09
1.45

.47 1.95 1.59. 5.49.

2X Ø .20 1.34 TYP.

R5.24 150°

1.40 .60

.63

5.93

.12

HIGH SIDE

1.00 [25.5] 1.71 [43.3]

LOW SIDE

0.83 [21.0]

1.23 [31.2] 3.97 [100.9] ‘OFF’ SPOOL-CAL POSITION

20

1.67 .12

GXLdp PANEL MOUNTING INSTRUCTIONS & DIMENSIONS

To install the unit to the panel mounting: 1. Make a cutout 7 minimum vertical x 5.9 minimum horizontal in
your panel or mounting location. 2. Provide (4) 6-32 threaded holes as shown in the drawings below. 3. Place 3 spacers between the unit and the panel mount adapter
and insert 6-32 x 1½ screws from the back side of the unit and thread them into the panel mount adapter as shown in the drawings below. 4. Mount to the panel using provided (4) 6-32 x ½ length screws.

3.13 [79.4]

6.07 [170.2] 3.35 85.1

0.30

5.81

[7.6] [147.5]

8.45 [214.7] 7.70 [195.5]

6.91 [175.6]

3.35

1.79 4X Ø .15

85.1

[3.8]

.12

21

LOAD LIMITATION GRAPH

Load Limitations 4-20 mA Output Only
1273 1200

1000

Loop Resistance ()

800

600

545

OPERATING

REGION

400

200

0

0

10 12

20 24 30

40

VMIN = 12V + [0.022A x (RL )] (includes a 10% safety factor)
RL = RS + RW RL = Loop Resistance (Ohms) RS = Sense Resistance (Ohms) RW = Wire Resistance (Ohms)

22

23

Ashcroft Inc. 250 East Main Street, Stratford, CT 06614 USA Tel: 203-378-8281, Fax: 203-385-0402, www.ashcroft.com All sales subject to standard terms and conditions of sale. © 2021 Ashcroft Inc. I&M011-10287_RevC_04-22-21

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

ASHCROFT User Manuals

Related Manuals