Skinner EM Emergency Pipe Repair Clamp Instruction Manual
- June 3, 2024
- Skinner
Table of Contents
Skinner EM Emergency Pipe Repair Clamp
INSTALLATION PROCEDURE
EMERGENCY CLAMPS:
The Skinner Emergency Clamps are designed for use on Steel, Ductile and Cast
Iron pipes to repair pit holes, splits, and corrosion leaks. This clamp can be
used on pipes for Gas, Water, Oil, or Ammonia. Sizes and pressure ratings are
as follows:
Size| Bolt Torque| Max. Working
Pressure
---|---|---
0.50”| 10 ft/lb| 600 psi
0.75”| 10 ft/lb| 600 psi
1.00”| 18 ft/lb| 600 psi
1.25”| 18 ft/lb| 600 psi
1.50”| 18 ft/lb| 600 psi
2.00”| 40 ft/lb| 600 psi
2.50”| 40 ft/lb| 600 psi
Size| Bolt Torque| Max. Working
Pressure
---|---|---
3.00”| 40 ft/lb| 500 psi
3.50”| 40 ft/lb| 500 psi
4.00”| 50 ft/lb| 500 psi
5.00”| 50 ft/lb| 450 psi
6.00”| 50 ft/lb| 400 psi
8.00”| 60 ft/lb| 300 psi
10” & 12”| 60 ft/lb| 200 psi
Installation Procedure:
Step #1| Thoroughly clean the damaged area with a wire brush. Remove all pipe scale, rust, and foreign material. This will
help insure a “bubble tight” seal.
---|---
Step #2| Place the clamp around the pipe so that the leak is
completely covered by the clamp gasket.
Step #3| Tighten the bolts evenly to the recommended torque shown
above.
Step #4| Pressure test the complete installation for leaks.
Step #5| Check for leaks before leaving repair site.
GASKET Material: Buna-N (Nitrile Rubber) rated at 250 F Max to -20 F Min Temp.
IMPORTANT: DO NOT EXCEED TEMPERATURE OR PRESSURE RATINGS!
-
The Skinner Company
-
1519 Evans Pond Road
-
Greenwood, South Carolina 29649
-
USA
-
877-923-7700 (Ph)
-
864-953-9724 (Fx)
Documents / Resources
|
Skinner EM Emergency Pipe Repair
Clamp
[pdf] Instruction Manual
EM Emergency Pipe Repair Clamp, EM, Emergency Pipe Repair Clamp, Pipe Repair
Clamp, Repair Clamp, Clamp, EM Emergency Pipe Repair Clamp
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>