AEG VL-40.5 Vacuum Circuit Breaker User Manual
- June 3, 2024
- AEG
Table of Contents
- VL-40.5 Vacuum Circuit Breaker
- Overview
- Structural principle
- Technical parameter
- Propulsion mechanism
- Overall dimensions
- Electrical wiring diagram
- Installation, commissioning and operation
- Maintenance
- Transportation and storage
- Random documents
- Spare parts
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
VL-40.5 Vacuum Circuit Breaker
User Manual
VL-40.5 Vacuum Circuit Breaker
Caution!
Please read this manual carefully before installing and using the circuit
breaker:
The installation and use of circuit breakers must comply with the requirements
of this manual.
Circuit breaker should be used in accordance with the normal indoor
environmental conditions.
Any operation and maintenance of the circuit breaker should be carried out by
professional trained full-time electrical personnel.
It is forbidden to operate the circuit breaker beyond its rated parameters.
Attention must be paid to any identification of circuit breakers.
It is necessary to ensure the applicability and safety of interlocking
conditions and working procedures of circuit breakers.
It is not allowed to carry out maintenance work when the switch cabinet and
secondary control circuit are charged.
It must be ensured that the circuit breaker is not impacted by any external
force, otherwise the equipment will be damaged.
Any illegal operation of the circuit breaker may damage the equipment and even
cause serious accidents.
This manual should be placed in a convenient place.
Professional personnel should be responsible for the safety management of
circuit breakers.
Overview
1-1 General:
VL-40.5 vacuum circuit breaker (hereinafter referred to as circuit breaker) is
applicable to AC 50Hz and 35kV Power Systems, and can be used as protection
and control equipment for industrial and mining enterprises, power plants and
substations, and is applicable to frequently operated occasions.
1-2 General provisions:
The circuit breaker complies with the following standards:
GB/T 1984 | High-voltage alternating-current circuit-breakers |
---|---|
IEC 62271-100 | High-voltage switchgear and controlgear – Part 100: Alternating |
current circuit-breakers
IEC 60694| Common specifications for high-voltage switchgear and controlgear
standards
DL/T 403| HV vacuum circuit-breaker for rated voltage 12kV to 40.5kV
1-3 Normal operating conditions:
Ambient temperature
Maximum temperature:| + 40ºC
Minimum temperature:| – 25ºC
Maximum daily average temperature:| + 35ºC
Ambient humidity
Daily average relative humidity: | ≤95% |
---|---|
Monthly average relative humidity: | ≤90%; |
Daily average saturated vapor pressure: | ≤2.2×10-3 Mpa |
Monthly average saturated vapor pressure: | ≤1.8×10-3 Mpa |
Earthquake intensity: | No higher than Level 8 |
Altitude: | ≤ 1000m, conventional products can be used below 1000m above sea |
level, and high-altitude products need to be noted when ordering.
Others: no inflammable and explosion hazard, no chemical corrosive gas
and no violent vibration.
Note: in case of different use environment or other special requirements,
it is necessary to consult with the manufacturer.
Structural principle
2-1 Main structure
The circuit breaker adopts integrated and modular design, and the overall
structure is simple and reasonable. It adopts upper and lower settings, with
the arc extinguishing chamber part above and the interlocking and operating
mechanism part below. Special spring operating mechanism is used, without
adjustment, and the action is stable and reliable.
The vacuum arc extinguishing chamber of the three-phase conductive circuit of
the circuit breaker is arranged in the closed solid sealing pole column, which
not only improves the insulation performance of the phases, but also protects
each phase circuit from the influence of the external bad environment,
prevents dust and foreign matters from entering the conductive circuit, and
reduces the overall size of the circuit breaker.
2-2 Operating mechanism
The operating mechanism of the circuit breaker is a spring energy storage
mechanism. There are closing unit, opening unit composed of one or several
coils, auxiliary switch, indicating device and other components in the
mechanism box; the front is provided with closing and opening button, manual
energy storage operation hole, spring energy storage status indicator board
and closing and opening indicator board.(Fig.1, 2)
|
|
---|---|---
1 closing spring
2 closing/opening indicator
3 opening latch
4 charging indicator
5 counter
6 micro-switch
7 charging motor
8 manual charging shaft
9 motor output shaft
10 small gear
11 large gear
12 closing coil
13 closing plate
14 opening coil
15 over-current coil/secondary tripping coil| 16 energy storage
keeping block
17 energy storage latch
18 closing interlock block
19 handcart interlock block| 20 upper terminal
21 vacuum chamber
22 fixed pole
23 lower terminal
24 insulating pull rod
25 threaded rod
26 connecting plate
27 crank arm
28 connecting plate
2-2-1 Energy storage
The energy required for closing the circuit breaker is provided by the closing
spring. Energy storage can be done either by motor or by hand with energy
storage handle.
Energy storage operation: it is carried out by the energy storage motor 7
fixed on the frame or by inserting the energy storage handle into the manual
energy storage shaft 8 and shaking it clockwise. The gear system is driven by
motor output shaft 9 for electric energy storage, and the gear system is
driven by manual energy storage shaft 8 for manual energy storage. When the
small gear rotates, it drives the big gear to move together, thus pulling the
energy storage spring to store energy. When the energy storage position is
reached, the energy storage holding block is supported by the energy storage
holding block to separate the clutch and maintain the energy storage position.
The energy storage indicator board shows the tension state of the tension
spring, and the energy storage is completed. The micro switch cuts off the
power supply of the energy storage motor, and the circuit breaker is in the
closing ready state.
2-2-2 Closing
During the closing process, whether manually pressing the “closing” button or
remote operation to make the closing coil 12 act, the energy storage holding
device can be turned away from the energy storage holding block. Under the
action of the closing spring force, the cam drives the cam to rotate, and the
cam drives the connecting rod mechanism to drive the insulating rod 23 and the
moving contact of the arc extinguishing chamber to close.
After the closing action is completed, the opening holding switch and the
opening half shaft are kept in the buckle state. At the same time, the energy
storage indicator board and auxiliary switch are reset, and the motor power
supply circuit is connected. If the external power supply is also connected,
it will enter the energy storage state again, and the connecting rod will pull
the on / off indicator to indicate the position of “┃”, at the same time, pull
the counter to realize counting, and drive the connecting rod to pull the
spindle to drive the auxiliary switch to switch.
Note: when the circuit breaker is in the closing state or the closing locking
device is selected but the external power supply is not connected, the circuit
breaker is in the process of pushing, or the operating handle of the pushing
mechanism is not pulled out, the closing operation cannot be performed.
2-2-3 Opening
It can not only press the “opening” button, but also connect the external
power supply to make the opening coil or over-current coil act, so that the
opening holding switch and the opening half axis are unlocked to realize the
opening operation. The energy stored by the contact spring and the opening
spring 25 separates the dynamic and static contacts of the arc extinguishing
chamber 21. In the later stage of the opening process, the hydraulic buffer
absorbs the residual energy and limits the opening position.
Pull the “O” connecting rod to switch off the switch.
2-3 Anti misoperation interlock
The circuit breaker can provide perfect anti misoperation function
- After the closing operation of the circuit breaker is completed, the closing interlocking board 18 rotates against the closing board 13, and it cannot be closed again when the circuit breaker is not opened.
- After closing the circuit breaker, if the closing electric signal is not removed in time, the internal anti tripping controller of the circuit breaker will cut off the closing circuit to prevent multiple reclosing.
- When the handcart type circuit breaker fails to reach the test position or working position, the handcart interlocking board 19 shall buckle the closing board and cut off the closing circuit to prevent the circuit breaker from entering the load area in the closing state.
- After the handcart type circuit breaker is closed in the working position or test position, the trolley will not be able to move if the roller presses the pushing mechanism, so as to prevent pulling out or pushing the load area in the closing state.
- If electrical closing locking is selected, manual closing operation is prevented when the secondary control power supply is not connected.
Technical parameter
3-1 Main technical parameter
No. | Item | Unit | Value |
---|---|---|---|
1 | Rated voltage | kV | 40.5 |
2 | Rated power frequency withstand voltage (1 min) | 95/118 | |
Rated lightning impulse withstand voltage | 185/215 | ||
3 | Rated frequency | Hz | 50 |
4 | Rated current | A | 630/1250/1600/2000/2500/3150 |
5 | Rated short circuit duration | s | 4 |
6 | Rated short-circuit breaking current | kA | 25 31.5 |
7 | Rated short-time withstand current | 25 31.5 | |
8 | Rated short-circuit making current | kA | 63 80 |
9 | Rated peak withstand current | kA | 63 80 |
10 | Rated operation procedure | O-0.3s-CO-180s-CO | |
11 | Opening/closing rating voltage | V | AC: 110/220; DC: 110/220 |
12 | Rated voltage of energy storage motor | V | AC: 110/220; DC: 110/220 |
13 | Classification | class | E2-M2-C2 |
3-2 Mechanical characteristic parameters
No. | Item | Unit | Value |
---|---|---|---|
1 | Rated voltage | A | 630/1250/1600/2000/2500/3150 |
2 | Contact distance | mm | 18±1.0 (Fixed sealing pole) |
21±2.0 (Insulating cylinder)
3| Contact travel| mm| 4.0±1.0
4| Three-phase closing| ms| ≤2
5| Three-phase opening| ms| ≤2
6| Closing bounce time| ms| ≤3
7| Average opening speed| m/s| 1.3~1.9
8| Average closing speed| m/s| 0.5~1.0
9| Opening time (rated voltage)| ms| 20~50
10| Closing time (rated voltage)| ms| 30~70
11| Opening/closing rating voltage| V| AC: 110/220; DC: 110/220
12| Rated voltage of energy storage motor| V| AC: 110/220; DC: 110/220
13| Main loop resistance| μΩ| 630~1250A≤55; 1600~2000A≤45;
above 2500A≤35
14| Energy storage time| s| ≤10
3-3 Technical parameters of operating mechanism and locking electromagnet
Rate voltage (V)| Energy storage motor (A)| Closing coil (A)|
Opening coil (A)| Lockout electromagnet (mA)
---|---|---|---|---
DC 110| 2| 2.2| 2.2| 35
DC 220| 1| 1.3| 1.3| 20
Propulsion mechanism
4-1 Cabinet entry of handcart
Close the valve of the interlocking piece 2 of the pushing mechanism, operate
the left and right handles 1 to position B, and push the circuit breaker
handcart into the switch cabinet along the guide rail until the pins 5 on both
sides correspond to the positioning holes of the switch cabinet. Release the
left and right handles to fix the circuit breaker handcart in the switch
cabinet. Operate the grounding interlock handle 4 to position a to make it in
the insertion position. (if the propulsion mechanism is not equipped with
grounding interlock, this step can be skipped).
4-2 Pushed in or pulled out of handcart
Put the circuit breaker in the opening state (manual or electric), open the
valve of the interlocking piece 2, and insert the operating handle to make the
circuit breaker advance and exit in the cabinet. When the circuit breaker
enters the working position or retreats to the test position, the “click”
sound of clutch slipping can be heard, and the handcart does not move. At this
time, the shaking of the operating handle should be stopped. The advancement
and withdrawal of the circuit breaker handcart in the cabinet shall be
flexible without obvious jamming. (Note: when the circuit breaker touches the
valve mechanism of the cabinet and is almost in place, the propulsion force
should be significantly increased, which is normal).
4-3 Closing operation
- Push the handcart into the switch cabinet and operate the left and right handles to position A.
- Open the earthing switch and operate the earthing interlock handle to the position A.
- Press the interlocking piece and turn the main operating shaft clockwise with the handle to push the circuit breaker to the working position in the cabinet.
- Close the interlocking piece, close the circuit breaker and operate.
4-4 Emergency opening
When the switch cabinet is in an emergency, the emergency opening handle 3
rotates counterclockwise to open the circuit breaker.
4-5 Illustration (working position)
- Left and right handles
- Interlocking piece
- Emergency opening handle
- Grounding interlock handle
- Bolt
Overall dimensions
● Fixed sealing pole – 300mm apart
|
---|---
**Note:*** refers to circuit breaker with specification of 3150A-40k4
| A| B
---|---|---
Specification 1| 328| 1061
Specification 2| 400| 1100
Specification (spring mechanism)| D| Net weight kg
---|---|---
12504/25-40k4| 49| 420
16004/25–40k4| 55| 440
20004/25-40k4| 79| 470
25004/25-40k4| 109| 490
31504/25-40k4| 109| 550
● Fixed sealing pole – 440mm apart **Note:*** refers to circuit breaker with specification of 3150A-40kA
| A| B
---|---|---
Specification 1| 328| 1061
Specification 2| 400| 1100
Specification (spring mechanism)| 0| Net weight kg
---|---|---
1250A4/25-40kA| 49| 445
1600A/25-40kA| 55| 465
2000A/25-40kA| 79| 495
2500A/25-40kA| 109| 515
3150A/25-40kA| 109| 575
● Insulating cylinder- 300mm apart
Specification (spring mechanism) | D | Netweight (kg) |
---|---|---|
12504/25–31.5k4 | 49 | 420 |
16004/25–31.5k4A | 55 | 440 |
20004/25-31.5k4 | 79 | 470 |
25004/25-31.5k4 | 109 | 490 |
Electrical wiring diagram
● 58 core, with auxiliary contact of propulsion mechanism
S9: Limit switch | HQ: Closing coil | V1∼V4: Rectifier |
---|---|---|
S8: Limit switch | TQ: Opening coil | K0: Anti+-pumping relay(Optional) |
S4: Auxiliary switch for blocking coil | RO∼R1: Resistance | Y1: Blocking |
coil(Optional)
S1∼S3: Energy storage position switch| a∼q: Jumper terminal| S6: Position
locking of propulsion mechanism
QF: Auxiliary switch| M: Energy-storage motor|
Installation, commissioning and operation
7-1 When the circuit breaker is lifted from the packing box, the hook
shall be hung on the lifting position with lifting mark on the circuit
breaker. When moving, the upper and lower outlet arms shall not be stressed,
and the circuit breaker shall not be subject to large impact and vibration.
7-2 In case of problems in operation, determine the causes according to
the table below. If it can’t be solved, please contact the manufacturer. Do
not disassemble the circuit breaker by yourself.
No. | Fault phenomena | Reasons |
---|---|---|
1 | Failure to closing | 1.The breaker is in the closing position state |
2.The handcart does not fully come into operation position or test position
3.The closing locking device is employed and the auxiliary supply is
unconnected or lower than the specifications
4.secondary circuit is incorrect
2| The handcart cannot be pushed in or pulled out| 1 The breaker is in the
closing position state
2 The pushing- handle is not fully inserted into the pushing hole.
3.The pushing mechanism is not fully placed at the test position, so that the
clapper cannot be unlocked with the cabinet body
4.The cabinet body earthing interlocking is not released
7-3 The commissioning and operation work shall be carried out by
specially trained personnel who have a detailed understanding of the
performance of the circuit breaker. The corresponding protection and
prevention measures must be considered in the work.
One of the preconditions for trouble free operation is to use the circuit
breaker under normal working conditions according to the corresponding
provisions of GB /T 1984 and IEC 60694 standards.
- Check the circuit breaker for damage or any other harmful environmental impact. If there is such a phenomenon, it should be eliminated before power on to restore to normal working conditions.
- Remove dirt, especially on the surface of insulating parts. These may be due to contamination during transportation or storage, which may affect the insulation performance of the product.
- Check the connection status of primary circuit contact, secondary circuit connection and grounding body.
- Manual operation test.
Maintenance
Maintenance must be carried out by AEG personnel or the user’s personnel who
are familiar with the equipment and have been trained and qualified. If the
maintenance is carried out by the user’s personnel, the user shall be
responsible for the consequences of the repair.
8-1 During normal use, the circuit breaker is free of maintenance.
Because the circuit breaker has the characteristics of simple structure and
durability, it has a long service life. The maintenance work is related to the
wear and aging of parts. In order to make the circuit breaker work reliably,
the interval time and range of maintenance work needed to be carried out will
depend on the influence of working environment, operation times, operation
time and short circuit current breaking times and other factors.
8-2 Before maintenance, all auxiliary power supply must be disconnected
and there is no danger of power transmission again. The circuit breaker itself
is open and the spring is not stored energy. In order to prevent accidents,
special care should be taken in the operation mechanism.
8-3 Disassembly and replacement of circuit breaker parts shall be carried
out by AEG personnel or corresponding trained personnel, especially during
reassembly, necessary adjustment shall be made.
8-4 Maintenance of circuit breaker
a. The operation structure shall be inspected when the circuit breaker
has been operated for 5 years (from the day when the new equipment is put into
operation) or when the circuit breaker operates for the specified times (5000
times for the circuit breaker with 25kA and below, 4000 times for the circuit
breaker with 31.5kA):
- Cut off the energy storage power supply and operate the circuit breaker to close and open once to release energy.
- Check the grease condition of rolling or sliding bearing surface.
- Check the correctness of each component function during electrical and mechanical action.
- Do a comprehensive appearance inspection。
b. The operation structure shall be maintained after 10 years of operation (calculated from the day when the new equipment is put into operation) or the operation times of the circuit breaker (25 kA and less than 10000 times, 31.5 kA circuit breaker for 8000 times, 40kA circuit breaker for 5000 times):
- Cut off the energy storage power supply and operate the circuit breaker to close and open once to release energy.
- Re apply grease to supporting shaft, rolling and sliding bearing.
- Check the correctness of each component function during electrical and mechanical action.
- Check the condition or looseness of fasteners installed at connecting rod, crank arm and supporting rod.
- During maintenance, it is important to check the parts which are subjected to high stress during operation.
In case of replacement of parts, all fasteners shall be replaced.
Comprehensive review of operating mechanism.
8-5 After the circuit breaker has been running for about 5 years or when
the operating mechanism is under maintenance, the circuit breaker body should
also be inspected. Especially when inspecting the appearance, it is also
necessary to check the contamination, damp and corrosion of the equipment
surface. Clean the dust on the surface of insulating parts with dry cloth, and
then wipe all kinds of dirt with silk cloth with household alkaline cleaning
agent or safety cleaner (pay attention to whether the detergent used is
applicable to plastic and synthetic rubber materials), and do not use carbon
tetrachloride or trichloroethylene to wipe.
The minimum interval of the above inspection work shall be less than 5 years
for the switchgear operating in some special use occasions or under harmful
environmental conditions (such as in the environment with high pollution and
heavy corrosive gas).
Transportation and storage
9-1 When the product is transported, the circuit breaker shall be placed
in a closed packing box without energy storage, and a proper amount of
desiccant shall be built in. The circuit breaker shall be protected with
plastic film to prevent water penetration during loading and unloading and
dust intrusion during storage.
9-2 The following tools shall be used to load and unload the packing box
- Crane
- Forklift
- Driving
9-3 Pay attention to the following items during transportation:
- Avoid shocks
- Avoid other destructive mechanical forces
- The lifting appliance should not be hooked on the circuit breaker body or operating mechanism. It should be hooked at the lifting position with lifting mark.
9-4 The circuit breaker shall be stored in the state of opening of
operating mechanism and energystorage spring without energy storage.
Basic storage requirements
- The dry and well ventilated storage room shall meet the relevant provisions of GB /T 1984 and IEC 60694.
- The temperature of the storage room shall not be lower than – 15 ° C.
- Do not disassemble or damage the package. Cover with a protective light covering and maintain adequate ventilation.
- Regularly check whether there is condensation phenomenon and other conditions not suitable for storage requirements.
Random documents
a. Product certificate
b. Factory inspection report
c. Packing list
Spare parts
When the user needs, the spare parts can be determined according to the following list, and put orward when ordering, so as to meet the needs.
Order number (SAP) | Product model |
---|---|
26400056 | Over-current tripping coil (Y8) |
36490042 | Over-current control circuit board |
26490381 | Closing locking electromagnet (S4) |
26490463 | Closing/opening control circuit board (please mention: operation |
voltage, whether there is anti-tripping, whether there is locking)
26490093| Closing/opening auxiliary switch (OF)
26490090| Handcart position auxiliary switch (58, S9)
26490580| Energy storage position switch (S1, S2, S3)
26490598| Position locking switch (110V)
26490076| Position locking switch (220V)
26400055| Closing/Opening coil (110V)
26400054| Closing/Opening coil (220V)
26490375| Breaker energy-saving motor (110V)
26490359| Breaker energy-saving motor (220V)
26490349| Pushing handle for withdrawable-type breaker
26490365| Mechanism energy-saving handle
26490033| Counter
26490508| Propelling mechanism handle
Shanghai AEG Enterprise Development Co., Ltd. http://weixin.qq.com/r/hnVxaVvESgY1rR8K9yCU
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>