INTRODUCTION

The MAGPOWR Model PS90 is an isolated controllable current regulator for 90 VDC magnetic particle clutches and brakes. The PS90 also provides a small amount of  reverse current to minimize the drag torque of the clutch / brake.
The Model PS90 has four jumper selectable current ranges. Maximum outputs for the individual ranges are 0.125, 0.25, 0.5 and 1.0 ADC. The appropriate range is  determined by the current rating of the clutch or brake to be controlled. For best torque control resolution, the lowest current range providing sufficient current for  maximum operating torque should be selected.
The PS90 accepts either a remote adjustment potentiometer, or a 0 to 10 VDC analog control signal.
Connections are provided for an external 1 mADC current meter. The meter display will indicate output current as a percentage of the output range selected.
The control circuits are electrically isolated from the power circuits.

INSTALLATION

The PS90 is intended for installation on a vertical panel with a DIN 35 rail, with the wiring terminals facing down. Figure 1 shows the enclosure dimensions.MAXCESS PS90 90 VDC Power Supply - Figure 1

SETUP

Remove the enclosure top by inserting a flat blade screwdriver under the retaining tabs in the base (See Figure 2). Set the JP1 current range selection jumpers to the range  appropriate for the clutch / brake connected to the PS90 (See Figure 3 for current range settings). The factory setting is 1/8 amp range. Replace the enclosure top.

MAXCESS PS90 90 VDC Power Supply - Figure 2

ELECTRICAL CONNECTIONS

Wiring to and from the PS90 must be done with double or reinforced insulation or protective screening which provides protective separation. All wiring should comply with  the essential requirements of the appropriate standard(s) and is the responsibility of the installer.
Route AC power away from control wiring. The clutch / brake wires and the remote meter wires should be twisted pair. Run the signal input wiring in shielded cable. Connect  the shield to the provided terminal marked SHIELD. The maximum shield length and maximum length of wires outside of the shield is 3.0 inches. (75 mm).
When using a 0 to 10 VDC input instead of a potentiometer, connect the negative of the input to terminal 26 and the positive of the input to terminal 25.
The 90 VDC output and the remote meter output are not isolated from the AC line and must not be ground referenced. The potentiometer input is isolated and may be ground referenced.

MAXCESS PS90 90 VDC Power Supply - Figure 3 Figure 4. Wiring Connections

Required connections:
115 VAC power
90 VDC output for clutch/brake
1 to 10 kohm Potentiometer

MAINTENANCE

The only maintenance that may be required on the TSA is fuse replacement. See specifications on next page.
Remove AC power, and then open the enclosure by inserting a flat blade screwdriver under the retaining tabs in the base (See Figure 2 on previous page). Replace fuse and  reassemble.
The enclosure must be re-installed to maintain the IP rating.

TROUBLESHOOTING

Symptom Possible Cause Solution or Diagnostic
No clutch / brake output. No AC power. Verify incoming power is correct

voltage and frequency.
Fuses blown.| Clutch / brake wires shorted together or shorted to ground.
Clutch / brake wires open circuit.| Disconnect clutch / brake wires at the PS90 and check for proper
clutch / brake resistance between the wires.
Remote potentiometer or external power supply not wired correctly, or shorted together.| Voltage between terminal 24 and 26 should be 10 VDC.
Voltage between terminal 25 and 26 should vary from 0 to 10 VDC as the potentiometer or external 0 to10 VDC power supply is moved through its range of travel.
Remote meter not working.| Incorrect type of meter.| Meter should be a current meter with 1 mA full scale and no more than 3 kohm resistance.
Meter wires shorted or open.| Disconnect meter wiring at the PS90 and check for proper meter resistance between the wires.

OPTIONS

The PS90 is factory adjusted to provide full reverse current with 0 VDC input. If some other current is desired with 0 VDC input or the minimum remote potentiometer  setting, the minimum current potentiometer may be adjusted by cutting out the hole shown on the label and then using a trimpot adjustment tool. Modifying this setting will  cause the clutch / brake drag torque to be higher than expected and is not recommended.

SPECIFICATIONS

Supply Voltage: 115 VAC, +/- 10%, 50/60 Hz, 1.1 amp maximum, sinusoidal
Fuses:  F1, F2 1.6 amp slow-blow, Littelfuse Part No. 21501.6, or

Cooper-Bussman Part No. S505-1.6-R
Enclosure:| IP20
Climatic Class:| 3K3  (EN60721)
Temperature Range:|
Operating:| 0° C to 50° C
Storage:| -30° C to 80° C
Relative Humidity:| 5% to 85%
Pollution Degree:| 2  (IEC664-1)
Altitude:| 0 to 2000 m
Compatible Residual Current
Device Types:| A or B (IEC755)
Worst Case Fault Current:| 1.6 amp
Inputs:
Signal| Potentiometer:  1 to 10 kohm, ¼ watt minimum, or
Voltage:  0 to 10 VDC, 100 kohm input impedance
Outputs:
Clutch / Brake Voltage:
Current:| 3 to 90 VDC, full wave, phase controlled
Adjustable in four ranges:
-0.004 to 0.125 ADC
-0.008 to 0.25 ADC
-0.016 to 0.5 ADC
-0.032 to 1.0 ADC
Regulation:| < 1% of range
Current Drift:| 0.024 %/° C
Meter Signal:| 0 to 1 mADC, +/-2% into 3 kohm maximum
Potentiometer Supply Voltage:| 10 VDC +/-2%, 10 mADC maximum

SERVICE REQUESTS AND REPLACEMENT PARTS

To request service or to get replacement parts, contact one of the following addresses:

Fife Corporation
222 West Memorial Rd.
Oklahoma City, OK, 73114, USA
Phone: 1-405-755-1600
Fax: 1-405-755-8425
Web: www.maxcessintl.com| Fife-Tidland GmbH
Fife-Tidland GmbH
Max-Planck-Strasse 8 65779 Kelkheim
Deutschland
Telefon: +49.6195.7002.0
Fax: +49.6195.7002.933
Web: www.maxcess.eu
---|---

Siemensstrasse 13-15
48683 Ahaus
Deutschland

AMERICAS Tel +1.405.755.1600 Fax +1.405.755.8425 sales@maxcessintl.com www.maxcessintl.com
EUROPE, MIDDLE EAST AND AFRICA Tel +49.6195.7002.0 Fax +49.6195.7002.933 sales@maxcess.eu www.maxcess.eu
CHINA Tel +86.756.881.9398 Fax +86.756.881.9393 info@maxcessintl.com.cn www.maxcessintl.com.cn
INDIA Tel +91.22.27602633 Fax +91.22.27602634 india@maxcessintl.com www.maxcess.in
JAPAN Tel +81.43.421.1622 Fax +81.43.421.2895 japan@maxcessintl.com www.maxcess.jp
KOREA, TAIWAN, AND SE ASIA asia@maxcessintl.com www.maxcess.asia

© 2018 Maxcess

Documents / Resources

| MAXCESS PS90 90 VDC Power Supply [pdf] Instruction Manual
PS90 90 VDC Power Supply, PS90, 90 VDC Power Supply, Power Supply, Supply
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals