Schaller LF-TD Profinet Air Humidity Transmitter Series Moisture Meter User Manual
- September 13, 2024
- Schaller
Table of Contents
- Schaller LF-TD Profinet Air Humidity Transmitter Series Moisture Meter
- Introduction
- For your safety
- On receipt of your device
- Installation of the transmitter
- Integration into a B&R control system
- Technical drawing LF-TD Profinet
- Adjustment behaviour of the sensor
- Cleaning and maintenance
- Checking the calibration
- Storage and disposal
- Technical data
- CONTACT
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Schaller LF-TD Profinet Air Humidity Transmitter Series Moisture Meter
Your LF-TD Profinet at a glance
The main unit
No. | Name |
---|---|
1 | Air humidity and temperature sensor |
2 | Sensor head |
3 | Sensor cable |
4 | Aluminum housing |
5 | Sensor plug |
6 | RJ45 plug |
7 | Mounting bracket |
Introduction
Information about this operating manual
This operating manual is designed to enable you to use the LF-TD Profinet
safely and effectively. It is part of the device, has to be stored nearby and
must be easily accessible to users at all times.
All users are required to carefully read and make sure that they have
understood this operating manual before using the LF-TD Profinet. All of the
safety and operating instructions detailed in this manual have to be observed
to ensure the safety of the device.
Limitation of liability
All of the information and instructions provided in this operating manual have
been compiled based on the current standards and regulations, the state of the
art, and the extensive expertise and experience of Schaller Messtechnik GmbH.
Schaller Messtechnik GmbH does not accept any liability for damage associated
with the following, which also voids the warranty:
- Non-observance of this operating manual
- Improper use
- Inadequately qualified users
- Unauthorised modifications
- Technical changes
- Use of unapproved spare parts
This fast-measurement procedure can be affected by a range of different
factors.
We, as the manufacturer, do not accept any liability for any incorrect
measurements and associated consequential damage
Symbols used in this manual
All of the safety information provided in this manual is shown with a
corresponding symbol.
ATTENTION
- It is essential to observe this warning. Non-compliance can lead to damage to property or equipment.
Information
- This symbol indicates important information that enables users to use the device more efficiently and cost-effectively.
Customer service
For technical advice, please contact our customer service department at:
Schaller Messtechnik GmbH
- Max-Schaller-Straße 99
- A – 8181 St.Ruprecht an der Raab
- Telephone: +43 (0)3178 28899
- Fax: +43 (0)3178 28899 – 901
- E-Mail: info@humimeter.com
- Internet: www.humimeter.com
- © Schaller Messtechnik GmbH 2024
Information
Your purchased measuring instrument can be calibrated, and the adjustment
checked by using suitable test ampoules/calibration ampoules. For this
purpose, use only the calibration solutions distributed by Schaller
Messtechnik Gmbh.
You can download a calibration certificate for your test ampoules/calibration
ampoules with the batch number printed on the ampoul from
https://www.humimeter.com/certificates/.
For your safety
The device complies with the following European directives:
- Restriction of Hazardous Substances in Electrical and Electronic Equipment (RoHS)
- Electromagnetic compatibility (EMC)
The device corresponds to state-of-the-art technology. However, it is still
associated with a number of residual hazards.
These hazards can be avoided through strict observance of our safety
information.
Proper use
- Transducer for measuring and transmitting relative humidity and temperature in fixed installation
- The sensor technology used makes it possible to detect even small fluctuations in humidity and their tendencies quickly and reliably so that preventive actions can be taken.
- For some applications (e.g. installation in sewage pipes) it is necessary to use a remote measuring probe for the reason of temperature adjustment.
Improper use
- The device must not be used in ATEX.
User qualifications
The device must only be operated by people who can be expected to reliably
take the measurements. The device must not be operated by people whose
reaction times may be slowed due to, e.g. the use of drugs, alcohol or
medication.
All persons using this device must have read, understood and follow the
instructions provided in the operating manual.
General safety information
- The following safety information has to be observed at all times to avoid damage to objects and injury to people:
- In case of damages or loose parts on the device, contact Schaller Messtechnik GmbH or your dealer.
- All of the device’s technical features have been inspected and tested before delivery.
- Every device has a serial number. Do not remove the tag with the serial number.
Warranty
The warranty does not apply to:
- Damage resulting from non-observance of the operating manual
- Damage resulting from third-party interventions
- Products that have been used improperly or modified without authorization
- Products with missing or damaged warranty seals
- Damage resulting from force majeure, natural disasters, etc.
- Damage from improper cleaning
On receipt of your device
Taking the device out of its packaging
- Take the device out of its packaging.
- Next, make sure that it is not damaged and that no parts are missing.
Making sure that all of the components have been included
Make sure that all of the components have been included by checking the
package contents against the following list:
Scope of supply
- LF-TD Profinet
- Connecting cable of 1.9 m length
- Operating manual
Optional accessories:
- Display for LF-TD
- Display with keypad for LF-TD
- Relay output for moisture for LF-TD
- Mounting bracket for LF-TD
- Brass sinter sensor cap
- Drip-catcher for LF-TD
- Stainless steel lattice filter
- Custom-made design – flat rate for air humidity transmitter series per order
- Factory calibration certificate, calibration equipment, certified calibration ampoules and reference devices – for continuous monitoring
Installation of the transmitter
Laying of the supply line or transmission line
- The cable must not be laid in the area of interference fields.
- Do not operate the transmitter in the area of electromagnetic interference fields.
- The permissible cross-sections for the installation must be observed.
- The cable length must be kept as short as possible.
- If an extension of the cable is required, the cross-section of the extension must not be below 0.25 mm2.
- If the electronics housing and the display electronics are grounded, an appropriate equipotential bonding conductor must be provided.
Mounting the transmitter
- The measuring probe must be positioned at a representative location.
- Avoid positions of draught and unnatural temperature fluctuations.
- Do not expose the device to direct sunlight.
- If the sensor tube is twisted, the tightness is no longer guaranteed.
- When there is a possibility of condensation, position the sensor probe slightly upwards (approx. 10 degrees angle).
- The condensation water can then flow away from the sensor probe towards the housing or cable and drain off.
- If it is impossible to place the unit at an upward angle, a drip nose (optional accessory) must be installed.
- Installation inside an air duct (or at mounting locations where temperature differences between sensor probe and sensor housing may occur:
- The sensor must be inserted fully into the opening until it stops, to avoid a temperature drop along the sensor tube. See sketch:
Pin assignment
Cable color | Pin no. | Function |
---|---|---|
Brown | 1 | Power supply V- (0 VDC) Ground current output |
White | 2 | Power supply V+ (12 to 29 VDC) |
Blue | 3 | Analog output humidity 4 – 20 mA |
Black | 4 | n.c. |
Grey | 5 | Analog output temperature 4 – 20 mA |
Purple | Housing | Equipotential bonding GND |
ATTENTION
Damage to the electronics due to incorrectly connected cables
- Incorrect connected cables can lead to severe damage to the electronics.
- Connect all cables correctly.
Wiring diagram
Integration into a B&R control system
GSD package
- The GSD package required for integration into a control system is provided by Schaller.
- The GSD package is a zip file containing the required GSD file and the instructions.
- The integration was realized with a B&R controller.
- The Profinet sensor is connected to the Profinet master using a suitable Ethernet cable (figure 1).
Settings on the B &R Profinet master
- IP address of the master
- Station name of the sensor: „Schaller-lftd2020“
- The IP address of the sensor is assigned by the controller:.
- From the controller’s point of view, 8 words (16BIT) are defined as inputs and 8 words (16BIT) as outputs.
- These settings must be identical on the master and on the sensor for communication to work.
- Overview address table Profinet stations „Schaller-lftd2020“
Settings on the B &R Profinet-Slave
- Overview Profinet sensor Schaller GmbH
- 8 x Input Register (16BIT)
- 8 x Output Register (16BIT).
- Device information Anybus module Profinet
Settings on the B &R software
-
The inputs and outputs are automatically created in the project and must now be assigned to the corresponding process variables.
-
Process variables:
Program code in ANSI C for integration
-
It is recommended to use the counter as a watchdog.
- The counter is incremented by the sensor every millisecond.
-
Thus, the function of the sensor can be monitored by means of the counter.
- If the counter does not change for a longer period of time, a restart of the communication with the module is necessary.
-
With the LFTD-Profinet (new) with display, the Profinet connection is cut when the measuring window is left or the module is deactivated.
- In contrast to the LFTD-Profinet (old) with AnybusIC, the device starts the measurement automatically after power-up.
-
With the variable “ModulOk” or “LFTD20_Online” in connection with the counter
“LFTD20_Cnt”, a reliable check of the function of the sensor and the communication can be realised.- A measurement interval with the provision of data takes less than one second.
Technical drawing LF-TD Profinet
Adjustment behaviour of the sensor
-
In humidity and temperature measurement, several parameters are responsible for the adjustment behavior (time until the actual measured value is displayed). The parameter responsible for the highest measuring error is a temperature discrepancy between the sensor resp. the whole measuring instrument and the material being measured resp. the air.
-
Therefore, let the device adjust until the displayed temperature corresponds to the actual temperature. The graph below shows how long it takes to adjust from 20 °C to 30 °C.
-
To demonstrate the importance of temperature adjustment, the table below shows the measuring errors due to a temperature difference between the measuring instrument and the material being measured of only 1 °C / 1.8 °F, at different ambient temperatures.
10 °C (50 °F) | 20 °C (68 °F) | 30 °C (86 °F) | |
---|---|---|---|
10 % r.h. | +/- 0.7 % | +/- 0.6 % | +/- 0.6 % |
50 % r.h. | +/- 3.5 % | +/- 3.2 % | +/- 3.0 % |
90 % r.h. | +/- 6.3 % | +/- 5.7 % | +/- 5.4 % |
- At room temperature (20 °C / 68 °F) and an assumed humidity value of 50 % relative humidity a temperature difference between the measuring sensor and the material being measured of 1 °C / 1.8 °F causes a measurement error of 3.2 % relative humidity.
- A temperature difference of 3 °C / 5.4 °F would cause a measurement error of more than 10 % relative humidity.
Definition relative humidity
- Indicates the relationship between the current water vapour pressure and the maximum possible, the so-called saturation vapor pressure.
- The relative humidity shows the degree the air is saturated with water vapor.
- Examples:
- 50% relative humidity: At the current temperature and pressure, the air is half saturated with water vapour. 100% relative humidity means that the air is totally saturated with water vapour. If the air has more than 100% humidity, the excessive humidity would condense or precipitate as mist.
Application range
Within the normal application range (normal range) the accuracy of the device
is as indicated. A long-term application beyond the normal application range
(max. range), particularly at an air humidity of more than 80%, can lead to
higher measuring errors. Back in the normal application range, the sensor will
return to the indicated accuracy automatically.
Cleaning and maintenance
- Regularly cleaning and maintaining the device will ensure that it will have a long service life and stay in good condition.
Care instructions
- Do not leave the device out in the rain.
- Do not immerse the sensor in water.
- Do not expose the device to extreme temperatures.
- Protect the device from strong mechanical shocks and loads.
Cleaning the device
ATTENTION
Do not clean with fluids
Water or cleaning fluid getting inside the device can destroy the device.
- Only clean with dry materials.
Aluminum housing and sensor tube
- Clean the aluminum housing and the sensor tube with a dry cloth.
Air humidity and temperature sensor
- The air humidity and temperature sensor cannot be cleaned. In case of a polluted sensor please contact your dealer.
Checking the calibration
To do so: Calibration equipment (art.no.10006) and calibration ampoules (humidity standards art.no. 10005) are required. The device, the calibration equipment and the humidity standards must have a temperature between 20.0 °C and 26.0 °C. It is recommended to store the device, the calibration equipment, and the calibration ampoules in a room with little temperature fluctuation for 24 hours.
Assembling the calibration equipment
- If needed, place the sealing ring over the threads of the lower part as shown in figure 2.
- Put the textile pad in the lower part (figure 3) and carefully pour the humidity standard onto the pad, beginning with the humidity standard of 35 % relative humidity.
- Carefully place the upper part onto the lower part (figure 4) and tighten the upper part clockwise.
- Recommendation: Keep the lower part on the table while screwing on the upper part.
- If necessary, only lift the calibration equipment straight up and do not tilt or turn it over.
- In case it has been lifted, carefully place the calibration equipment onto an even table.
- Insert the sensor tube into the upper part of the calibration equipment (figure 5).
- Take care to lift the device with calibration equipment straight up and not to tilt or turn it over. Otherwise, the sensor may be damaged.
- Leave the calibration equipment mounted on the sensor tube until explicitly stated otherwise.
ATTENTION
Damage to the sensor
By tilting or turning the device with mounted calibration equipment the sensor
can be destroyed.
- Only lift the device with mounted calibration equipment straight up.
Determining the deviation
- Let the sensor adjust to the humidity standard for at least 2 hours.
- Then note down the measured relative humidity and temperature.
- At ideal temperature conditions (device, calibration equipment and humidity standard have a temperature of 23 °C), the value printed on the humidity standard can be used as reference value.
- In case of deviation from the factory temperature (23.0 °C), the real humidity value must first be determined according to the table below.
Temperature| Humidity standards
---|---
| 35 %| 50 %| 80 %
20 °C| 34.6 %| 49.8 %| 79.9 %
21 °C| 34.8 %| 49.8 %| 80.0 %
22 °C| 34.9 %| 49.9 %| 80.0 %
23 °C| 35.0 %| 50.0 %| 80.0 %
24 °C| 35.1 %| 50.1 %| 80.0 %
25 °C| 35.2 %| 50.2 %| 80.0 %
26 °C| 35.4 %| 50.2 %| 80.1 % - Note down the real humidity value.
- Compare the noted displayed measuring value with the real humidity value.
- If the deviation revealed is below 1.5 % relative humidity, it is not recommended to recalibrate.
- If the deviation revealed is more than 1.5 % relative humidity, please contact your dealer.
- Now remove the calibration equipment from the sensor tube and repeat the procedure from “10.1 Assembling the calibration equipment”, optionally with the humidity standard 50 % relative humidity or the humidity standard 80 % relative humidity.
Faults
If the measures listed below fail to remedy any faults or if the device has
faults not listed here, please contact Schaller Messtechnik GmbH.
Fault | Cause | Remedy |
---|---|---|
Measuring error | The temperature is outside the operating temperature: lower |
than -20 °C or higher than
+90 °C
| Only use the device in temperatures between -20 °C and +90 °C.
| Measurement error due to too short temperature adjustment time| Let the
device adjust to the surroundings (see “7. Adjustment behaviour of the
sensor”).
| Sources of heat or cold that do not correspond to the surrounding
temperature| Reposition your device at a location that is representative of
the room climate.
| Dripping water or sprayed water| Direct contact of the sensor with dripping
or sprayed water will destroy it.
| Irreversible damage of the sensor due to aggressive gases| Please contact
your dealer.
| Condensation caused by a change in temperature| Condensation on the sensor
interferes with the calibration. Let the device adjust to the surrounding
temperature.
| Polluted air humidity and temperature sensor| Please contact your dealer.
| Foreign particles on the sensor| Please contact your dealer.
Storage and disposal
Storing the device
The device must be stored as follows:
- Do not store outdoors.
- Store in a dry and dust-free place.
- Protect the device from sunlight.
- Avoid mechanical shocks/loads.
- Storage temperature: -20 °C to +60 °C
Disposing of the device
- Devices marked with this symbol are subject to Directive 2012/19/ EU of the European Parliament and of the Council of 4 July 2012 on waste electrical and electronic equipment (WEEE).
- If the device is being operated outside the European Union, the national regulations on the disposal of such devices that apply in the country of use must be observed.
- Electronic devices must not be disposed of as domestic waste.
- The device must be disposed of appropriately using appropriate collection systems.
Device information
- Name/ address of manufacturer: Schaller Messtechnik GmbH Max-Schaller-Straße 99 A – 8181 St. Ruprecht
- Product designation Schaller
- Type designation: LF-TD-A ; LF-TD 60 ; LF-TD 90 ; LF-TD 120 ; LF-TD 150; LF LFTD 180 ; LF-TD-E ; LF-TD-U ; LF-TD-ER ; LF-TD Profinet ; LF-TD-H
- Product Description Measuring instrument for determining relative humidity and derived measured variables
- The designated product conforms with European directives
- RoHS – Richtlinie 2011/65/EG RoHS-Directive 2011/65/EU
- Full compliance with the standards listed below proves the conformity of the designated product with the provisions of the above-mentioned EC Directives:
- EN 61326–1:2013 Electrical equipment for measurement, control, and laboratory use – EMC requirements
- EN IEC 63000:2019-05 replaced EN 50581:2012 Technical documentation for the assessment of electrical and electronic products to the restriction of hazardous substances.
- For the mentioned product complete documentation with a manual of instructions in the original version is available.
- In case of any changes not agreed upon with the manufacturer, this declaration of conformity loses its validity.
DECLARATION OF CONFORMITY
Technical data
Measuring range rel. air humidity | 0 % to 100 % |
---|---|
Calibration rel. air humidity | 10 % to 90 % |
Accuracy rel. air humidity | +/- 2.0 % (at 25 °C) |
Measuring range temperature | -20 °C to +90 °C |
Calibration temperature | +10 °C to +60 °C |
Accuracy temperature | +/- 0.3 °C (at 25 °C) / +/- 0.5 °F (at 77 °F) |
Operating temperature | -20 °C to +90 °C (sensor tube) |
-20 °C to +85 °C (electronics)
Outputs| rel. air humidity (4 – 20 mA)
-Scaling (0 % to 100 %)
Temperature (4 – 20 mA)
-Scaling (-20 °C to +90 °C)
Working resistance < 500 Ohm (UB 24 V)
Temperature compensation| Automatic
Power supply| 12 to 29 VDC
Current consumption| 18 mA (without interfaces, display, or any bus systems)
Electrical connection| Sensor plug with 1.9 m cable
Housing dimensions| 70 x 32 x 120 mm
Housing material| Anodized aluminum
Sensor tube dimensions| 12 x 125 mm
Sensor tube material| Stainless steel
Sensor cap| Stainless steel sinter
IP rating electronics housing| IP 54
Notes
Schaller Messtechnik develops, produces, and sells professional moisture meters and turnkey solutions.
CONTACT
- Schaller Messtechnik GmbH
- Max-Schaller-Straße 99, A – 8181 St. Ruprecht an der Raab
- Tel +43 (0)3178 – 28899 , Fax +43 (0)3178 – 28899 – 901
- info@humimeter.com, www.humimeter.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>