Carrier Manufacturing Poland Sp z o o FC-555-024 Radio Cluster Communicator RCC Installation Guide
- September 12, 2024
- Carrier Manufacturing Poland Sp z o o
Table of Contents
- Pre installation
- Components
- Mounting location guidelines
- Optional PCB / PSU removal
- Remove cable entry points
- Fix to the wall
- Connection wiring
- Apply power
- Configuration
- Close the RCC
- Specification
- Regulatory information
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Carrier Manufacturing Poland Sp z o o FC-555-024 Radio Cluster Communicator RCC Installation Guide
Pre installation
Installation must conform to applicable local installation codes and should only be installed by a fully trained competent person.
- Ensure the RCC is installed as per the site survey.
- Refer to step 3 to ensure optimised wireless performance.
- If using remote aerials with this product, refer to the remote aerial installation guide (MK293) for more information.
- This device contains electronics that may be susceptible to damage from Electrostatic Discharge (ESD). Take appropriate precautions when chandling electronic boards.
Components
- 4x corner covers,
- 4 x lid screws,
- RCC lid,
- RCC PCB,
- RCC back box
Mounting location guidelines
For optimum wireless performance, the following must be observed:
- Ensure the RCC is not installed within 2 m of other wireless or electrical equipment.
- The RCC must not be installed within 0.6 m of any metal work.
Note: the above points exclude the power supply, provided it is mounted below the RCC as shown
Optional PCB / PSU removal
- Remove the three circled retaining screws, before unclipping the PCB.
Remove cable entry points
- Drill the cable entry points as necessary
Fix to the wall
- All five circled fixing positions are available for use as required.
- The key hole can also be used for locating and fixing where required.
Connection wiring
- Power cables should only be passed via the access points available.
- Flame retardant cable glands should be used.
- DO NOT leave excess cable in the RCC.
Apply power
Apply power to the power supply. The normal LED states for the RCC are as below:
- HEALTHY LED – green LED will be on.
- FAULT LED – yellow LED will be off.
- SYS FAULT LED – yellow LED will be off.
- POWER 1 LED – green LED will be on.
- POWER 2 LED – green LED will be on.
Configuration
The RCC’s programming and loop address are configured within the menu structure of the radio hub.
- Refer to the programming manual (MK98) for full programming information.
Free to download from www.emsgroup.co.uk
Close the RCC
- Ensure that the RCC PCB is correctly inserted and the PCB retaining screws are refitted.
- Refit the RCC lid, ensuring LEDs are not damaged by the light pipe when refitting.
Specification
- Operating temperature -10 to +55 °C
- Storage temperature 5 to 30 °C
- Humidity 0 to 95% non-condensing
- IP rating IP54
- Operating voltage 17 to 28 VDC
- Power requirements 17 mA at 24 VDC
- Operating frequency 868 MHz
- Output transmitter power 0 to 14 dBm (0 to 25 mW)
- Signalling protocol X
- Dimensions (W x H x D) 270 x 205 x 85 mm
- Weight 0.95 kg
- Location Type A: For indoor use
Regulatory information
-
Manufacturer : Carrier Manufacturing Poland Sp. z o.o.
Ul. Kolejowa 24. 39-100 Ropczyce, Poland -
Year of manufacture : See devices serial number label
-
Certification : CE13
-
Certification body : 0905
-
CPR DoP : CPR DoP
-
Approved to : EN54-18:2005. Fire detection and fire alarm systems. Part 18: Input/output devices.
EN54-25:2008. Incorporating corrigenda September 2010and March 2012. Fire detection and fire alarm systems. Part 25: Components using radio link. -
European Union Directives:
EMS declares that this device is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet address: www.emsgroup.co.uk
2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see www.recyclethis.info Dispose of your batteries in an environmentally friendly manner according to your local regulations.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>