CT MORLEY One Way Cassette Mini Splits AC and Heat Units User Manual
- September 14, 2024
- CT MORLEY
Table of Contents
- One Way Cassette Mini Splits AC and Heat Units
- Specifications:
- Product Overview:
- Product Installation:
- Install Your Indoor Unit:
- Install Your Outdoor Unit:
- Refrigerant Piping Connection:
- Wiring Precautions:
- Air Evacuation:
- Panel Installation:
- Test Run:
- Indoor Unit Display:
- Remote Control Operations:
- Q: How often should I clean the air filters?
- Q: What should I do if the air conditioner stops cooling?
One Way Cassette Mini Splits AC and Heat Units
“`html
Specifications:
- Product Model: xxxxxxxxx
- Power source: xxxxxx
- Cooling capacity: xxxx
- Heating capacity: xxxx
- Rated current: xxxx
- Rated power input: xxxxxxxx
- Outdoor unit resistance class: IPX4
Product Overview:
NOTE ON ILLUSTRATIONS: Illustrations in this
manual are for explanatory purposes. The actual shape of your
indoor unit may be slightly different. The actual shape shall
prevail.
Product Installation:
Install Your Indoor Unit:
Follow the steps outlined in the manual to correctly install
your indoor unit. Ensure proper positioning and secure mounting to
avoid any instability or damage.
Install Your Outdoor Unit:
Properly place and secure the outdoor unit following the
provided guidelines. Make sure it is placed in a well-ventilated
area with sufficient clearance for optimal performance.
Refrigerant Piping Connection:
Connect the refrigerant piping according to the instructions
provided. Take care to seal all connections properly to prevent
leaks and ensure efficient cooling.
Wiring Precautions:
When handling wiring, follow safety precautions to avoid
electrical hazards. Ensure proper insulation and connection of all
wires as per the wiring diagram provided.
Air Evacuation:
Prior to operation, perform air evacuation as instructed to
remove any air from the system. Proper air evacuation is essential
for optimal cooling performance.
Panel Installation:
Install the panels securely on both the indoor and outdoor units
to protect components from dust and debris. Follow the manual for
correct panel installation steps.
Test Run:
After installation, conduct a test run of the air conditioner to
ensure all functions are working correctly. Monitor for any unusual
noises or malfunctions during the test run.
Operation Instructions:
Indoor Unit Display:
Familiarize yourself with the indoor unit display indicators to
understand the status of the air conditioner. Refer to the manual
for details on each display symbol.
Remote Control Operations:
Use the remote control to adjust settings such as temperature,
fan speed, and mode. Follow the instructions in the manual to
operate the air conditioner effectively using the remote
control.
Cleaning and Maintenance:
Regularly clean and maintain your air conditioner to ensure
efficient operation. Follow the cleaning instructions provided in
the manual to keep your unit in optimal condition.
Troubleshooting:
If you encounter any issues with your air conditioner, refer to
the troubleshooting section of the manual for guidance on
identifying and resolving common problems.
FAQ:
Q: How often should I clean the air filters?
A: It is recommended to clean the air filters every 2 weeks for
optimal performance and air quality.
Q: What should I do if the air conditioner stops cooling?
A: Check for any obstructions blocking the airflow and ensure
that the thermostat settings are correct. If the issue persists,
contact a qualified technician for assistance.
“`
One-way Cassette
USER MANUAL
IMPORTANT NOTE: Read this manual carefully before installing or operating your
new air conditioning unit. Make sure to save this manual for future reference.
THANK YOU LETTER
Thank you for choosing Midea! Before using your new Midea product, please read
this manual thoroughly to ensure that you know how to operate the features and
functions that your new appliance offers in a safe way.
CONTENTS
THANK YOU LETTER
01
SAFETY PRECAUTIONS
02
SPECIFICATIONS
06
PRODUCT OVERVIEW
07
PRODUCT INSTALLATION
08
Install Your Indoor Unit
09
Install Your Outdoor Unit
15
Refrigent Piping Connection
21
Wiring Precautions
24
Air Evacuation
27
NOTE on adding refrigerant
28
Electrical And Gas Leak Checks
29
Panel Installation
30
Test Run
33
Unit Specifications and Features
34
OPERATION INSTRUCTIONS
35
Indoor Unit Display
35
Remote Control Operations
37
CLEANING AND MAINTENANCE
48
TROUBLESHOOTING
51
TRADEMARKS, COPYRIGHTS AND LEGAL STATEMENT 54
DISPOSAL AND RECYCLING
54
DATA PROTECTION NOTICE
55
01
SAFETY PRECAUTIONS
It’s really important you read Safety Precautions Before Operation and
Installation Incorrect installation due to ignoring instructions can cause
serious damage or injury. The seriousness of potential damage or injuries is
classified as either a WARNING or CAUTION.
Explanation of Symbols
Warning of electrical voltage This symbol indicates that there is a danger to
life and health of persons due to voltage. Warning The signal word indicates a
hazard with a medium level of risk which, if not avoided, may result in death
or serious injury. Caution The signal word indicates a hazard with a low
degree of risk which, if not avoided, may result in minor or moderate injury.
Attention The signal word indicates important information (e.g. damage to
property), but not danger. Observe instructions This symbol indicates that a
service technician should only operate and maintain this appliance in
accordance with the operating instructions.
Read these operating instructions carefully and attentively before
using/commissioning the unit and keep them in the immediate vicinity of the
installation site or unit for later use!
WARNING
This appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the hazards involved.
Children shall not play with the appliance. Cleaning and user maintenance
shall not be made by children without supervision(European Union countries).
This appliance is not intended for use by persons(including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety. Children should
be supervised to ensure that they do not play with the appliance.
02
WARNING FOR PRODUCT USE
° If an abnormal situation arises (like a burning smell), immediately turn off
the unit and disconnect the power. Call your dealer for instructions to avoid
electric shock, fire or injury.
° Do not insert fingers, rods or other objects into the air inlet or outlet.
This may cause injury, since the fan may be rotating at high speeds.
° Do not use flammable sprays such as hair spray, lacquer or paint near the
unit. This may cause fire or combustion.
° Do not operate the air conditioner in places near or around combustible
gases. Emitted gas may collect around the unit and cause explosion.
° Do not operate your air conditioner in a wet room such as a bathroom or
laundry room. Too much exposure to water can cause electrical components to
short circuit.
° Do not expose your body directly to cool air for a prolonged period of time.
° Do not allow children to play with the air conditioner. Children must be
supervised
around the unit at all times. ° If the air conditioner is used together with
burners or other heating devices,
thoroughly ventilate the room to avoid oxygen deficiency. ° In certain
functional environments, such as kitchens, server rooms, etc., the use of
specially designed air-conditioning units is highly recommended. ° Toxic fumes
may be produced if the refrigerant in this unit comes into contact with
naked flames (such as from a heater, gas stove/burners, or electric
appliances). ° Dispose of this unit’s packaging carefully, so children cannot
playwith it. Packaging,
especially plastic packaging, can be dangerous, can cause serious injury or
death. Screws, staples and other metal packaging components can be sharp and
should be disposed of carefully to avoid injury. ° Do not open or remove the
unit’s panel when the unit is powered on. Touching the unit’s internal
components while the unit is powered on can lead to electric shocks or
injuries caused by moving parts such as the unit’s fan. ° Do not spray any
liquids onto the unit or allow any liquids to drip onto the unit. ° The
refrigerant in this unit is safe and should not leak if the system is designed
and installed properly. However, if a large amount of refrigerant leaks into a
room, the oxygen concentration will decrease rapidly, which can cause serious
injury or death. The refrigerant used in this unit is heavier than air, so the
danger is greater in basements or other underground spaces. In the event of a
refrigerant leak, turn off any devices that produce a naked flame and any
heating devices, ventilate the room, and contact your supplier or service
engineer immediately.
CLEANING AND MAINTENANCE WARNINGS
° Turn off the device and disconnect the power before cleaning. Failure to do
so can cause electrical shock.
° Do not clean the air conditioner with excessive amounts of water. ° Do not
clean the air conditioner with combustible cleaning agents. Combustible
cleaning agents can cause fire or deformation.
03
ELECTRICAL WARNINGS
° Only use the specified power cord. If the power cord is damaged, it must be
replaced by the manufacturer, its service agent or similarly qualified persons
in order to avoid a hazard.
° Do not modify the length of the power supply cord or use an extension cord
to power the unit. The product must be properly grounded at the time of
installation, or electrical shock may occur.
° For all electrical work, follow all local and national wiring standards,
regulations, and the Installation Manual. Connect cables tightly, and clamp
them securely to prevent external forces from damaging the terminal. Improper
electrical connections can overheat and cause fire, and mayalso cause shock.
All electrical connections must be made according to the Electrical Connection
Diagram located on the panels of the indoor and outdoor units.
° All wiring must be properly arranged to ensure that the control board cover
can close properly. If the control board cover is not closed properly, it can
lead to corrosion and cause the connection points on the terminal to heat up,
catch fire, or cause electrical shock.
° Disconnection must be incorporated in the fixed wiring in accordance with
the wiring rules.
CAUTION
° Turn off the air conditioner and disconnect the power if you are not going
to use it for a long time.
° Turn off and unplug the unit during storms. ° Make sure that water
condensation can drain unhindered from the unit. ° Do not operate the air
conditioner with wet hands. This may cause electric shock. ° Do not use device
for any other purpose than its intended use. ° Do not climb onto or place
objects on top of the outdoor unit. ° Do not allow the air conditioner to
operate for long periods of time with doors or
windows open,or if the humidity is very high. ° Some parts of the unit are
sharp and can cause injury if touched. To prevent injury,
when the unit is being serviced, gloves should be worn.
TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner’s circuit board (PCB) is designed with a fuse to provide
overcurrent protection. The specifications of the fuse are printed on the
circuit board, examples of such are T5A/250VAC and T10A/250VAC.
WARNING FOR PRODUCT USE
° Installation must be performed by an authorized dealer or specialist.
Defective installation can cause water leakage, electrical shock, or fire.
° Installation must be performed according to the installation instructions.
Improper installation can cause water leakage, electrical shock, or fire.
° Contact an authorized service technician for repair or maintenance of this
unit. This appliance shall be installed in accordance with national wiring
regulations.
° Only use the included accessories, parts, and specified parts for
installation. Using non-standard parts can cause water leakage, electrical
shock, fire, and can cause the unit to fail.
° Install the unit in a firm location that can support the unit’s weight. If
the chosen location can not support the unit’s weight, or the installation is
not done properly, the unit may drop and cause serious injury and damage.
04
° Install drainage piping according to the instructions in this manual.
Improper drainage may cause water damage to your home and property.
° For units that have an auxiliary electric heater, do not install the unit
within 1 meter (3 feet) of any combustible materials
° Do not install the unit in a location that may be exposed to combustible gas
leaks. If combustible gas accumulates around the unit, it may cause fire.
° Do not turn on the power until all work has been completed.
ELECTRICAL WARNINGS
° When moving or relocating the air conditioner, consult experienced service
technicians for disconnection and reinstallation of the unit.
° How to install the appliance to its support, please read the information for
details in “indoor unit installation” and “outdoor unit installation”
sections.
05
SPECIFICATIONS
Product Model Power source Cooling capacity Heating capacity Rated current Rated power input Outdoor unit resistance class
xxxxxxxxx
xxxxxx xxxxx xxxx xxxx
xxxxxxxxx xxxxxxx
xxxxx xxxx xxxx xxxx
IPX4
xxxxxxxxx
xxxxxx xxxxxx xxxx xxxx
b
06
PRODUCT OVERVIEW
NOTE ON ILLUSTRATIONS:
Illustrations in this manual are for explanatory purposes. The actual shape of
your indoor unit may be slightly different. The actual shape shall prevail.
5
4
1
7
2
3
9
8 10
6
1 Display panel
2 Air outlet(Air flow louver) 3 Air inlet(with air filter in it)
4 Installation part
5 Air-break switch
6 Outdoor Unit
7 Drain pipe
8 Refrigerant piping
9 Remote controller
10 Outdoor unit power cable
07
PRODUCTION INSTALLATION
ACCESSORIES
The air conditioning system comes with the following accessories. Use all of
the installation parts and accessories to install the air conditioner.
Improper installation may result in water leakage, electrical shock and fire,
or cause the equipment to fail. The items are not included with the air
conditioner must be purchased separately.
Manual
1
Installation cardboard template
Remote controller
AAA Battery
2
Cable tie
6
Water receiver
Seal Drain joint Wire controller (optional) Rubber ring
Drainpipe adaptor
1
Screw kits (ST850, M422, ST3.916, ST4.812, ST3.9*10)
Copper nut
1 (8,8,2,2,3)
2
Name
Shape
WiFi controller (optional) Panel
Q`ty(pc)
Connecting pipe assembly
Liquid side Gas side
6.35( 1/4 in)
9.52( 3/8in)
To purchase based on actual project requirements.
12.7( 1/2in)
1 1 1 1 1
1
1
Note
Parts you must purc hase separately. Consult the dealer about the proper pipe
size of the unit you purchased.
NOTE
Panel installation should be performed after wiring and piping have been
completed.
08
Install You Indoor Unit
1 Select installation location
NOTE
Before installing the indoor unit, you must choose an appropriate location.
The following are standards that will help you choose an appropriate location
for the unit.
Before Installation:
· Determine the route to move the unit to the installation site. · First
unseal and unpack the unit. Then, hold the seats of the hanger (4 pcs) to move
the unit. Refrain from
exerting force on other parts of the unit, especially the refrigerant piping,
water discharge piping, and the plastic parts.
Proper installation locations meet the following standards:
Enough room exists for
Enough room exists for the
There is no direct radiation
installation and maintenance. connecting the pipe and drainpipe.
from heaters.
The air inlet and outlet The airflow can fill
are not blocked.
the entire room.
The ceiling is horizontal and its structure can
sustain the weight of the indoor unit.
DO NOT install unit in the following locations:
Areas with oil drilling or fracking
Coastal areas with high salt content in the air
Areas with caustic gases in the air, such as hot springs Areas that experience
power fluctuations, such as factories
Enclosed spaces, such as cabinets Kitchens that use natural gas Areas with strong electromagnetic waves Areas that store flammable materials or gas Rooms with high humidity, such as bathrooms or laundry rooms
09
2 Confirm various sizes
Installation place
Type A Wall
500mm (19.69 in)
Ceiling
Roof Ceiling hole
(unit: mm/inch)
500mm (19.69 in)
225mm (8.86 in) 220mm (8.66 in) 16mm(5/8 in ) 2500mm(98.43 in)
Type B
Ceiling
GROUND Wall
200mm(7.87 in)
16mm(5/8 in )
air outlet Ceiling hole
air inlet
Indoor parts installation size
Type A 1105mm(43.5in)
GROUND Type B
(unit: mm/inch)
423mm (16.65in) 335mm(13.19in)
250mm(9.84in) 205mm(8.07in)
475mm(18.4in)
1360mm(53.54in)
10
3 Indoor Unit Installation
Make sure that only specified components are used for the installation works.
Model A: with circuit breaker
Remove the four screws to open the indoor control box and circuit breaker box.
Connect the wire to the air breaker according Four to the wire connecting diagram. screws
Remove the pre-cutting cover on the circuit breaker box.
TO INDOOR UNIT MAIN BOARD
Circuit Breaker
Y/G
32 1
TO OUTDOOR UNIT
32 1
WARNING
The ground wire should be tighten firmly without loosening.
Pre-cutting cover
11
Fasten and fix the wire body with a tie.
Model B: with terminal
Remove the four screws to open the indoor control box and terminal box.
Four screws
Fasten and fix the wire body with a tie
Install the circuit breaker cover by fixing the two screws.
Two screws
Remove the pre-cutting cover on the terminal box. Remove the two screws, then take out the clip.
Pre-cutting cover
Two screws
12
Connect the wire to the terminal according to the wire connecting diagram.
Install the terminal cover by fixing the two screws.
Select one to connect ground wire
Two screws 2. Install the indoor air handler
Fix the wire with the clip by using the two screws.
NOTE:
After you have finished installing the main body, when choosing where to
start, determine the direction of the pipes to be drawn out. Especially in
cases where there is a ceiling involved, align the refrigerant pipes, drain
pipes, and indoor and outdoor lines with their connection points before
mounting the unit.
After you selecting an installation location, drill a hole with the diameter
of 6mm or less into the roof beam based on the layout of the installation
board (accessory Installation cardboard template). After drilling the hole,
remove the installation board.
1300mm(51.18”)
CUTTING LINE
430mm (16.93”)
TO INDOOR UNIT MAIN BOARD
1 23
Installation cardboard template
TO OUTDOOR UNIT
13
Connecting the wire from the control box.
To CCM Comm.Bus
TO 485 WIRE CONTROLLER
4
TO 2 WIRE Wire-controller
MAGNETIC RING
X Y E CN3
CN40
HB HA CN41
INDOOR UNIT MAIN BOARD
CN41 is a customised part.
Connecting the other side of the connecting cable to the wire controller.
WARNING
Please follow local regulations and take measures to isloate high voltage and
low voltage.
NOTE:
Be sure to reserve a length of the connecting wire for periodic maintenance.
If there is a connection lug at the end of shielded wire, the connection lug
should be properly grounded.
Wire controller
The connective wires group
CN41 2-core wire (customer purchases wiring)
shielded wire (some units)
for ground wire
CN40 4-core wire
Pass a tie through the hole to fix wire .
14
Install Your Outdoor Unit
1
Select installation location
NOTE : PRIOR TO INSTALLATION
Before installing the outdoor unit, you must choose an appropriate location.
The following are standards that will help you choose an appropriate location
for the unit.
Proper installation locations meet the following standards:
60cmc24″ above
30cmc12″ on left
30cmc12″ from back wall
Good air circulation Firm and solid–the
Noise from the unit
and ventilation.
location can support the will not disturb other
unit and will not vibrate. people.
200cmc79″ in front
60cmc24″ on right
Long-term
Meets all spatial requirements shown in Installation Protected from prolonged periods Where snowfall is anticipated, take
Space Requirements above.
of direct sunlight or rain.
appropriate measures to prevent
ice buildup and coil damage.
NOTE
Install the unit by following local codes and regulations , there may be differ slightly between different regions.
CAUTION:
SPECIAL CONSIDERATIONS FOR EXTREME WEATHER
If the unit is exposed to heavy wind:
Install unit so that air outlet fan is at a 90° angle to the direction of the wind. If needed, build a barrier
in front of the unit to protect it from extremely heavy winds. See Figures below.
If the unit is frequently exposed to heavy rain or snow:
Build a shelter above the unit to protect it from the rain or snow. Be careful not to obstruct air flow
around the unit.
If the unit is frequently exposed to salty air(seaside):
Use outdoor unit that is specially designed to resist corrosion.
Strong wind
Wind Baffle
Shelter
Strong wind
90° angle to the direction of the wind
Strong wind
Build a wind Baffle to protect the unit
Build a shelter to protect the unit
DO NOT install unit in the following locations:
Near an obstacle that will block air inlets and outlets
Near a public street, crowded areas, or where noise from the unit will disturb
others.
Near animals or plants that will be harmed by hot air discharge.
Near any source of combustible gas.
In a location that is exposed to large amounts of dust
In a location exposed to a excessive amounts of salty air.
15
2 Install drain joint(Heat pump unit only)
Step 1 Find out the base pan hole of outdoor unit.
Seal
Base pan hole of outdoor unit
Step 2 ° Fit the rubber seal on the end of the drain joint that will connect
to the
outdoor unit. ° Insert the drain joint into the hole in the base pan of the
unit. The drain joint
will click in place. ° Connect a drain hose extension (not included) to the
drain joint to redirect
water from the unit during heating mode.
IN COLD CLIMATES
In cold climates, make sure that the drain hose is as vertical as possible to
ensure swift water drainage. If water drains too slowly, it can freeze in the
hose and flood the unit.
16
3 Anchor Outdoor Unit
WARNING
WHEN DRILLING INTO CONCRETE, EYE PROTECTION IS RECOMMENDED AT ALL TIME.
° The outdoor unit can be anchored to the ground or to a wall-mounted bracket
with bolt(M10). Prepare the installation base of the unit according to the
dimensions below.
° The following is a list of different outdoor unit sizes and the distance
between their mounting feet. Prepare the installation base of the unit
according to the dimensions below.
Outdoor Unit Types and Specifications (Split Type Outdoor Unit)
D B
H
A H
W
W
Front view
Top view
Outdoor Unit Dimensions W x H x D
760x590x285 (29.9×23.2×11.2) 810x558x310 (31.9x22x12.2) 845x700x320
(33.27×27.5×12.6) 900x860x315 (35.4×33.85×12.4) 945x810x395 (37.2×31.9×15.55)
990x965x345 (38.98x38x13.58) 938x1369x392 (36.93×53.9×15.43) 900x1170x350
(35.4x46x13.8) 800x554x333 (31.5×21.8×13.1) 845x702x363 (33.27×27.6×14.3)
946x810x420 (37.24×31.9×16.53) 946x810x410 (37.24×31.9×16.14) 952x1333x410
(37.5×52.5×16.14) 952x1333x415 (37.5×52.5×16.34) 890x673x342 (35×26.5×13.46)
765x555x303 (30.1×21.8×11.9) 805x554x330 (31.7×21.8×12.9) 770x555x300
(30.3×21.8×11.8)
(unit: mm/inch) Rows of series installation
Mounting Dimensions Distance A Distance B
The relations between H, A and L are as follows.
530 (20.85) 290 (11.4)
549 (21.6) 325 (12.8)
560 (22)
335 (13.2)
590 (23.2) 333 (13.1)
L
L 1/2H L H
1/2H < L H
A 25 cm / 9.8″ or more 30 cm / 11.8″ or more
640 (25.2) 405 (15.95) 624 (24.58) 366 (14.4)
L > H
Can not be installed
634 (24.96) 404 (15.9) 590 (23.2) 378 (14.88)
514 (20.24) 540 (21.26)
340 (13.39) 350 (13.8)
673 (26.5) 403 (15.87)
673 (26.5) 403 (15.87) 634 (24.96) 404 (15.9)
634 (24.96) 663 (26.1) 452 (17.8)
404 (15.9) 354 (13.94) 286(11.3)
o2r5mcomre/ 9.8″
o2r5mcmore/ 9.8″
511 (20.1)
317 (12.5)
H
487 (19.2) 298 (11.7)
L A
300 cm / 118″ or more
150 ocrmm/o5r9e”
60
cm or
m/ 2o3r.e6″
17
If you are installing the outdoor unit on the ground,or a concrete mounting
platform,use the following steps: 1. Mark the positions for four expansion
bolts based on dimensions in the Mounting Dimensions
chart and illustrations above. 2.Pre-drill holes for expansion bolts. 3.Clean
concrete dust away from the holes. 4.Place a nut on the end of each expansion
bolt. 5.Hammer expansion bolts into the pre-drilled holes. 6.Remove the nuts
from the expansion bolts,and place outdoor unit on bolts. 7.Put a washer on
each of the expansion bolts,then reinstall the nuts. 8.Using a wrench,tighten
each nut until snug.
WARNING
WHEN DRILLING INTO CONCRETE,EYEPROTECTION IS RECOMMENDED AT ALL TIMES.
If you are installing the unit on a wall-mounted bracket, follow these steps:
CAUTION:
Before installing a wall-mounted unit,make sure that the wall is made of solid
brick, concrete,or a similarly strong material. The wall must be able to
support at least 4 times the weight of the unit.
1. Mark the position of the bracket holes based on the dimensions in the
Mounting Dimensions chart on the previous page.
2.Pro-drill the holes for the expansion bolts. 3.Clean dust and debris away
from the holes. 4.Place a washer and nut on the end of each expansion bolt.
5.Thread expansion bolts through the holes in the mounting brackets.Then,put
the mounting brackets in
position and hammer the expansion bolts into the wall. 6.Check that the
mounting brackets are level. 7.If the feet of the outdoor unit have rubber
pads already installed , and you are using a local dealer’s
wall-mounting bracket,remove them before attempting to mount the condenser to
the bracket.The mounting bracket has rubber isolating pads on it that will
take the place of these. 8.Carefully lift the unit and place its mounting feet
on the brackets. 9.Then,bolt the unit firmly to the brackets.
TO REDUCE VIBRATION OF WALL-MOUNTED UNIT
If allowed, you can install the wall-mounted unit with rubber gaskets to
reduce vibration and noise.
18
Drainpipe Installation
The drainpipe is used to drain water away from the unit. Improper installation
may cause unit and property damage.
CAUTION:
Before installing a wall-mounted unit,make sure that the wall is made of solid
brick, concrete,or a similarly strong material. The wall must be able to
support at least 4 times the weight of the unit.
· Insulate all piping to prevent condensation, which could lead to water
damage. · If the drainpipe is bent or installed incorrectly, water may leak
and cause a water-level switch
malfunction.
· In HEAT mode, the outdoor unit will discharge water. Ensure that the drain
hose is placed in an
appropriate area to avoid water damage and slippage.
· DO NOT pull the drainpipe forcefully. This could disconnect it.
NOTE ON PURCHASING PIPES
Installation requires a PVC tube (exterior diameter = 1in(25mm) ) (depending
on models ), which can be obtained at your localhardware store or dealer.
Indoor Drainpipe Installation
Install the drainpipe as illustrated in the following Figure. Connect
drainpipe to the indoor unit via drain adaptor.
Drain adaptor
Drainpipe Metal clamp connecting port
Drainpipe
1-1.5m (39-59″)
Downward slope 1/100
NOTE ON DRAINPIPE INSTALLATION · When using an extended drainpipe, tighten
the indoor connection with an additional protection tube to prevent it from
pulling loose.
· The drainpipe should slope downward at a
gradient of at least 1/100 to prevent water from flowing back into the air
conditioner.
· To prevent the pipe from sagging, space
hanging wires every 1-1.5m (39-59″).
· If the outlet of the drainpipe is higher than
the body’s pump joint, provide a lift pipe for the exhaust outlet of the
indoor unit. The lift pipe must be installed no higher than 75cm (29.5″) from
the ceiling board and the distance between the unit and the lift pipe must be
less than 30cm (11.8″) (depending on models ). Incorrect installation could
cause water to flow back into the unit and flood.
· To prevent air bubbles, keep the drain hose
level or slightly tiled up (<75mm / 3″) (some models ).
1 – 1.5m (39-59″) 30cm (11.8″)
53cm(20.8″) 75cm (29.5″)
22cm (8.6″)
0 – 75mm (3″)
19
0-53cm (20.8″)
10cm (4″)
Pass the drain hose through the wall hole. Make sure the water drains to a
safe location where it will not cause water damage or a slipping hazard.
NOTE
The drainpipe outlet should be at least 5cm (1.9″) above the ground. If it
touches the ground, the unit may become blocked and malfunction. If you
discharge the water directly into a sewer, make sure that the drain has a U or
S pipe to catch odors that might otherwise come back into the house.
Drill wall hole
1. Using a 65mm (2.5in) or 90mm(3.54in) (depending on models )core drill,
drill a hole in the wall. Make sure that the hole is drilled at a slight
downward angle, so that the outdoor end of the hole is lower than the indoor
end by about 5mm to 7mm (0.2-0.275in). This will ensure proper water drainage.
2. Place the protective wall cuff in the hole. This protects the edges of the
hole and will help seal it when you finish the installation process.
CAUTION:
When drilling the wall hole, make sure to avoid wires, plumbing, and other
sensitive components.
Wall
Indoor
Outdoor
5-7mm (0.2-0.275in)
NOTE: When the gas side connective pipe is
16mm(5/8in) or more, the wall hole should be
90mm(3.54in).
20
Refrigerant Piping Connection
When connecting refrigerant piping, DO NOT let substances or gases other than the specified refrigerant enter the unit. The presence of other gases or substances will lower the unit’s capacity, and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and injury.
Notes on pipe length and elevation
The maximum length and drop height based on models.(Unit:m/ft.)
Type of model
North America, Australia and The
EU frequency conversion split
type
Other Split Type
Capacity (Btu/h)
<15K 15K-<24K 24K-<36K 36K-<60K
12K 18K-24K 30K-36K 42K-60K
Length of piping
25/82 30/98.4 50/164 75/246
15/49 25/82 30/98.4 50/164
Maximum drop height
10/32.8 20/65.6 25/82 30/98.4
8/26 15/49 20/65.6 30/98.4
Ensure that the length of the refrigerant pipe, the number of bends, and the drop height between the indoor and outdoor units meets the requirements shown in the table next to it
CAUTION
Oil trap
Gas piping
Indoor unit/ Outdoor unit
Oil traps
If oil flows back into the outdoor unit’s compressor, this might cause liquid
compression or deterioration of oil return. Oil traps in the rising gas piping
can prevent this. An oil trap should be installed every 6m(20ft) of vertical
suction line riser (36000Btu/h unit). An oil trap should be installed every
10m(32.8ft) of vertical suction line riser (36000Btu/h unit).
Indoor unit/ Outdoor unit
6m/20ft (<36000Btu/h unit) 10m/32.8ft Liquid piping(36000Btu/h unit)
6m/20ft (<36000Btu/h unit) 10m/32.8ft (36000Btu/h unit)
21
Connection Instructions–Refrigerant Piping
CAUTION
· The branching pipe must be installed horizontally. An angle of more than 10°
may cause malfunction. · DO NOT install the connecting pipe until both indoor
and outdoor units have been installed. · Insulate both the gas and liquid
piping to prevent condensation.
Step 1: Cut pipes
When preparing refrigerant pipes, take extra care to cut and flare them
properly. This will ensure efficient operation and minimize the need for
future maintenance.
Measure the distance between the · indoor and outdoor units.
Using a pipe cutter, cut the pipe a · little longer than the measured
distance. Make sure that the pipe is cut at a · perfect 90° angle.
90°
Oblique Rough Warped
Point down
Pipe Reamer
Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight seal.
· After removing burrs from cut pipe, seal the ends with PVC tape to prevent
foreign materials from entering the pipe.
· Sheath the pipe with insulating material. · Place flare nuts on both ends of
pipe. Make sure
they are facing in the right direction, because you can’t put them on or
change their direction after flaring.
Flare nut
DO NOT DEFORM PIPE WHILE CUTTING
Be extra careful not to damage, dent, or deform the pipe while cutting. This
will drastically reduce the heating
Copper pipe
· Remove PVC tape from ends of pipe when ready to perform flaring work.
· Clamp flare from on the end of the pipe. The end of the pipe must extend
beyond the flare form.
Flare form
Step 2: Remove burrs
Burrs can affect the air-tight seal of refrigerant piping connection. They
must be completely removed. · Hold the pipe at a downward angle to
prevent burrs from falling into the pipe. · Using a reamer or deburring tool,
remove
all burrs from the cut section of the pipe.
Pipe
· Place flaring tool onto the form. · Turn the handle of the flaring tool
clockwise
until the pipe is fully flared.
22
PIPING EXTENSION BEYOND FLARE FORM
Pipe gauge
Tightening torque
Flare dimension(A) (Unit:mm/lnch)
Min.
Max.
Flare shape
(180-200kgf.cm)
32-39 N.m (320-390kgf.cm)
49-59 N.m (490-590kgf.cm)
57-71 N.m (570-710kgf.cm)
67-101 N.m (670-1010kgf.cm)
85-110 N.m (850-1100kgf.cm)
· Remove the flaring tool and flare form, then inspect the end of the pipe for
cracks and even flaring.
Step 4: Connect pipes
Connect the copper pipes to the indoor unit first, then connect it to the
outdoor unit. You should first connect the low-pressure pipe, then the
highpressure pipe.
· When connecting the flare nuts, apply a thin coat of refrigeration oil to
the flared ends of the pipes.
· Align the center of the two pipes that you will connect.
Indoor unit tubing
Flare nut Pipe
· Tighten the flare nut snugly by hand. · Using a wrench, grip the nut on the unit tubing. · While firmly gripping the nut, use a torque
wrench to tighten the flare nut according to
the torque values in above table.
NOTE
Use both a spanner and a torque wrench when connecting or disconnecting pipes
to/from the unit. Outdoor unit
Liquid side piping (Smaller diameter)
(Bigger
Torque wrench
CAUTION
Ensure to wrap insulation around the piping. Direct contact with the bare
piping may result in burns or frostbite. · Make sure the pipe is properly
connected.
Over tightening may damage the bell mouth and under tightening may lead to
leakage.
NOTE MINIMUM BEND RADIUS
Carefully bend the tubing in the middle according to the diagram below. DO NOT
bend the tubing more than 90° or more than 3 times.
Use appropriate tool
min-radius 10cm(3.9 ) · After connecting the copper pipes to the
indoor unit, wrap the power cable, signal cable and the piping together with
binding tape.
NOTE
DO NOT intertwine signal cable with other wires. While bundling these items
together. DO NOT intertwine or cross the signal cable with any other wiring.
· Thread this pipeline through the wall and connect it to the outdoor unit.
· Insulate all the piping , including the valves of the outdoor unit.
· Fix the water receiver (supplied in Accessories box) to the indoor unit by a
screw.
NOTE: Two ST4.812 screws are supplied, one of which is spare.
ST4.812 screw
· Open the stop valves of the outdoor unit to start the flow of the
refrigerant between the indoor and outdoor unit.
CAUTION
Check to make sure there is no refrigerant leak after completing the
installation work. If there is a refrigerant leak, ventilate the area
immediately and evacuate the system. (refer to the Air Evacuation section of
this manual)
23
Wiring precautions
WARNING
BEFORE PERFORMING ANY ELECTRICAL WORK, READ THESE WARNINGS.
° All wiring must comply with local and national electrical codes, regulations
and must be installed by a licensed electrician.
° All electrical connections must be made according to the Electrical
Connection Diagramlocated on the panels of the indoor and outdoor units.
° If there is a serious safety issue with the power supply, stop work
immediately. Explain your reasoning to the client, and refuse to install the
unit until the safety issue is properly resolved.
° Power voltage should be within 90-110% of rated voltage. Insufficient power
supply can cause malfunction, electrical shock, or fire.
° Installation of an external surge suppressor at the outdoor disconnect is
recommended.
° If connecting power to fixed wiring, a switch or circult breaker that
disconnects all poles and has a contact separation of at least 1/8in (3mm)
must be incorporated in the fixed wiring. The qualified technician must use an
approved circuit breaker or switch.
° Only connect the unit to an individual branch circuit. Do not connect
another appliance to that outlet.
° Make sure to properly ground the air conditioner. ° Every wire must be
firmly connected. Loose
wiring can cause the terminal to overheat, resulting in product malfunction
and possible fire.
° Do not let wires touch or rest against refrigerant tubing, the compressor,
or any moving parts within the unit.
° If the unit has an auxiliary electric heater, it must be installed at least
1 meter (40in) away from any combustible materials.
° To avoid getting an electric shock, never touch the electrical components
soon after the power supply has been turned off. After turning off the power,
always wait 10 minutes or more before you touch the electrical components.
° Make sure that you do not cross your electrical wiring with your signal
wiring. This may cause distortion, interference or
° possibly damage to circuit boards. ° No other equipment should be connected
to the same power circuit. ° Connect the outdoor wires before
connecting the indoor wires.
WARNING
BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, TURN OFF THE MAIN POWER TO
THE SYSTEM.
NOTE ON AIR SWITCH
When the maximum current of the air conditioner is more than 16A, an air
switch or leakage protection switch with protective device shall be
used(purchased seperately). When the maximum current of the air conditioner is
less than 16A, the power cord of air conditioner shall be equipped with plug
(purchased seperately). In North Americathe applicance should be wired
according to NEC and CEC requirements.
(A)
Air switch (purchased seperately)
Outdoor unit power wires Indoor & Outdoor connective wires
(purchased seperately)
(B)
Indoor unit power wires
Air switch (purchased seperately)
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Indoor & Outdoor connective wires (purchased seperately)
24
(C) Air switch
(purchased seperately) Indoor unit power wires
Outdoor unit power wires
Outdoor unit
Indoor & Outdoor connective wires (purchased seperately)
(D) Only for the North American
Air switch (purchased seperately)
Air switch (purchased seperately)
Outdoor unit power wires
Indoor & Outdoor connective wires (purchased seperately)
Indoor unit
Outdoor unit
Air switch (purchased seperately)
Indoor unit
NOTE: The cographs are for explanation purpose only. Your machine may be slightly different. The actual shape shall prevail.
OUTDOOR UNIT WIRING
WARNING
Before performing any electrical or wiring work, turn off the main power to
the system.
1. Prepare the cable for connection a. You must first choose the right cable
size. Be sure to use H07RN-F cables.
NOTE: In North America, choose the cable type according to the local electrical codes and regulations.
Minimum Cross-Sectional Area of Power and Signal Cables-For reference
(Not applicable for North America)
Rated Current of Appliance (A)
3 and 6 > 6 and 10 > 10 and 16 > 16 and 25 > 25 and 32 > 32 and 40
Nominal Cross-Sectional Area (mm )
0.75 1 1.5
2.5 4 6
CHOOSE THE RIGHT CABLE SIZE
The size of the power supply cable, signal cable, fuse, and switch needed is
determined by the maximum current of the unit. The maximum current is
indicated on the nameplate located on the side panel of the unit. Refer to
this nameplate to choose the right cable, fuse, or switch. NOTE: In North
America, please choose the right cable size according to the Minimum Circuit
Ampacity indicated on the nameplate of the unit.
b. Using wire strippers, strip the rubber jacketfrom both ends of the signal
cable to reveal approximately 15cm (5.9″) of wire.
c. Strip the insulation from the ends. d. Using a wire crimper, crimp u-lugs
on the ends.
NOTE: When connecting the wires, strictly follow the wiring diagram found inside the electrical box cover.
25
2. Remove the 2 screws fixed on the front panel and side panel, then take it down to perform wire connection(see the figure of outdoor unit A). Unscrew the electrical wiring cover and remove it.(see the figure of outdoor unit B)
4. The wire groups shall be bound with cable ties and fixed on the right side plate after they are connected. The strong electric wire group and weak electric wire group shall be led out separately through the two knock down holes on the bottom of the right side plate and fastened with a locking connector as shown in the figure below.
Cover Screw
2 Screws
Outdoor Unit A
Outdoor Unit B
3. Connect the u-lugs to the terminals Match the wire colors/labels with the
labels on the terminal block. Firmly screw the u-lug of each wire to its
corresponding terminal.
4. Clamp down the cable with the cable clamp.
5. Insulate unused wires with electrical tape. Keep them away from any
electrical or metal parts.
6. Reinstall the cover of the electric control box.
Australia models
Please prepare spanner and flat-blade screwdriver before your installation
work . 1. Remove two fixing screws, then remove the
front panel.
2 Screws
2. Use spanner and flat-blade screwdriver to knock down two metal seals, then
pick the metal flakes out.
3. Connect the power cable and indoor & outdoor connection cable. Clamp down the cable with the cable clamp.
OUTDOOR UNIT WIRING
1. Prepare the cable for connection
a. Using wire strippers, strip the rubber jacket from both ends of the signal
cable to reveal about 15cm (5.9″) of the wire.
b. Strip the insulation from the ends of the wires.
c. Using a wire crimper, crimp the u-lugs to the ends of the wires.
2. Open the front panel of the indoor unit. Using a screwdriver,remove the
cover of the electric control box on your indoor unit.
3. Thread the power cable and the signal cable through the wire outlet.
4. Connect the u-lugs to the terminals.
Match the wire colors/labels with the labels on the terminal block. Firmly
screw the u-lug of each wire to its corresponding terminal. Refer to the
Serial Number and Wiring Diagram located on the cover of the electric control
box.
CAUTION
· While connecting the wires, please strictly follow the wiring diagram.
· The refrigerant circuit can become very hot. Keep the interconnection cable
away from the copper tube.
5. Clamp down the cable with the cable clamp.The cable must not be loose or
pull on the u-lugs.
6. Reattach the electric box cover.
26
AIR EVACUATION
NOTICE
When opening valve stems, turn the hexagonal wrench until it hits against the
stopper. Do not try to force the valve to open further.
Preparations and precautions
Air and foreign matter in the refrigerant circuit can cause abnormal rises in
pressure, which can damage the air conditioner, reduce its efficiency, and
cause injury. Use a vacuum pump and manifold gauge to evacuate the refrigerant
circuit, removing any non-condensable gas and moisture from the system.
Evacuation should be performed upon initial installation and when unit is
relocated.
6. Close the Low Pressure side of the manifold gauge, and turn off the vacuum
pump.
7. Wait for 5 minutes, then check that there has been no change in system
pressure.
8. If there is a change in system pressure, refer to Gas Leak Check section
for information on how to check for leaks. If there is no change in system
pressure, unscrew the cap from the packed valve (high pressure valve).
9. Insert hexagonal wrench into the packed valve (high pressure valve) and
open the valve by turning the wrench in a 1/4 counterclockwise turn. Listen
for gas to exit the system, then close the valve after 5 seconds.
10.Watch the Pressure Gauge for one minute to make sure that there is no
change in pressure. The Pressure Gauge should read slightly higher than
atmospheric pressure.
11. Remove the charge hose from the service port.
Evacuation Instructions
Flare nut
1. Connect the charge hose of the manifold gauge
to service port on the outdoor unit’s low
pressure valve.
2. Connect another charge hose from the manifold
gauge to the vacuum pump.
3. Open the Low Pressure side of the manifold
gauge. Keep the High Pressure side closed.
Cap
4. Turn on the vacuum pump to evacuate the system.
5. Run the vacuum for at least 15 minutes, or until the Compound Meter reads -76cmHG(-105Pa).
valve body
valve stem
Outdoor unit
Manifold Gauge
-76cmHg
12. Using hexagonal wrench, fully open both the high pressure and low
pressure valves.
13. Tighten valve caps on all three valves (service port, high pressure, low
pressure) by hand. You may tighten it further using a torque wrench if needed.
Compound gauge
Pressure gauge
Low pressure
valve Pressure hose
or Charge hose
Low pressure valve
High pressure valve
Charge hose
Vacuum pump
27
NOTE ON ADDING REFRIGERANT
CAUTION
DO NOT mix refrigerant types.
Some systems require additional charging depending on pipe lengths. The
standard pipe length varies according to local regulations. For example, in
North America, the standard pipe length is 7.5m (25′). In other areas, the
standard pipe length is 5m (16`). The refrigerant should be charged from the
service port on the outdoor unit’s low pressure valve. The additional
refrigerant to be charged can be calculated using the following formula:
Refrigerant
6.35( 1/4in)
9.52( 3/8in)
12.7( 1/2in)
R410A: (orifice tube in the indoor unit):
(Total pipe lengthstandara pipe length) ×30g(0.32oz)/m(ft)
R410A: (orifice tube in the outdoor unit):
(Total pipe lengthstandara pipe length) ×15g(0.16oz)/m(ft)
(Total pipe lengthstandara pipe length) ×65g(0.69oz)/m(ft)
(Total pipe lengthstandara pipe length) ×30g(0.32oz)/m(ft)
(Total pipe lengthstandara pipe length) ×115g(1.23oz)/m(ft)
(Total pipe lengthstandara pipe length) ×65g(0.69oz)/m(ft)
CAUTION DO NOT mix refrigerant types.
28
ELECTRICAL AND GAS LEAK CHECKS
WARNING RISK OF ELECTRICAL SHOCK
ALL WIRING MUST BE INSTALLED BY A LICENSED ELECTRICIAN AND COMPLY WITH LOCAL,
STATE, AND NATIONAL ELECTRICAL CODES.
Electrical Safety Checks
After installation is complete, confirm that all electrical wiring has been
installed in accordance with local and national regulations, and according to
the installation manual.
BEFORE TEST RUN
Check Grounding Work Measure grounding resistance by visual detection and with
a grounding resistance tester. Grounding resistance must be less than 0.1 .
NOTE: This may not be required for some locations in North America.
DURING TEST RUN
Check for Electrical Leakage During the Test Run, use an electroprobe and
multimeter to perform a comprehensive electrical leakage test.
IF ELECTRICAL LEAKAGE IS DETECTED
If electrical leakage is detected, turn off the unit immediately and call a
licensed electrician to find and resolve the cause of the leakage. NOTE: This
may not be required for some locations in North America.
Gas Leak Checks
There are two different methods to check for gaseous leaks. Use Fig. 8.1 below
as a guide for the critical points to check for leaks. Soap and Water Method
Using a soft brush or spray bottle, apply a soapy water solution to all of the
pipe connection points of the indoor and outdoor units, watching to see if any
bubbles form. The presence of bubbles indicates there is a leak. Leak Detector
Method If using a leak detector, refer to the device’s operation/instruction
manual for proper usage instructions.
After performing GAS leak checks
After confirming that all of the refrigerant pipe connections points DO NOT
leak, replace the valve cover on the outside unit and wrap and insulate the
piping connections of the indoor unit.
Check-point of indoor unit
Check-point of outdoor unit D
B
C
A
A: Low pressure stop valve B: High pressure stop valve C & D: Indoor unit
flare nuts
Fig. 8.1
29
PANEL INSTALLATION
Step1: Prepare and install ceiling
° Drill 430 mm x 1300 mm( 16.93”x51.18” ) hole into the ceiling based on the
layout of the installation board. The centre of the ceiling opening should
match the centre of the body of the indoor unit. NOTE: In order to keep the
ceiling level and prevent vibrations, reinforce the strength of the ceiling
when necessary.
° Once the ceiling is cut, remove the installation board. then install the
ceiling.
Step2: Panel Installation
Model A
NOTE: The air grille received by the customer is not tightened by the wire
rope,but is specially designed to be loose for easy installation.
° Grab air grille with your fingers and pull it out slowly in the direction of
the arrow.
ST3.916 screw
M422 screw
NOTE:
Eight M422 screws are supplied, two of which are spare. Two ST3.916 screws
are supplied, one of which is spare.
Before fixing this screw, you need to open the screw cover; and after fixing
screw, please close the cover.
° Open the two covers on both sides of the panel, fix the panel to the
cassette by using 3× M4*22 screws.
Grab at these locations
° Pull the panel grille out of the panel, fix the cassette panel to the one-
way cassett by two plastic buckles.
M4*22 screw ° Connect the display board to the main control
board, up to four wires are required to connect. NOTE: The corresponding
colors or corresponding pins are connected each other.
(white 5-core)
(white 10-core) (red 5-core)
( 4 core)
° Manually rotate the air deflector, fix the panel to the cassette by using 3×M422 screws and a ST3.916 screw.
when connection is completed, please clip the wires to the buckle.
30
° Install the control box cover and turn the circuit breaker to ON, then close the two plastic covers on both sides of the panel.
palstic buckle
° Manually rotate the air deflector, fix the panel to the cassette by using
3×M422 screws and a ST3.916 screw.
ST3.9*16 screw
° During the test-run process, the display wil be lighted and the air griller
will rise automatically.
Model B ° Press the circular positon to open the two screw
covers, then remove the two screws.
M422 screw
NOTE:
Eight M422 screws are supplied, two of which are spare. Two ST3.916 screws
are supplied, one of which is spare.
Before fixing this screw, you need to open the screw cover; and after fixing
screw, please close the cover.
° Open the two covers on both sides of the panel, fix the panel to the
cassette by using 3× M422 screws.
Screw Covers
° Hold and open the air grille, then push both of the latch to the middle to
unlock the air grille.
Latch
M4*22 screw
° Connect the display board to the main control board, up to four wires are
required to connect.
NOTE: The corresponding colors or corresponding pins are connected each other.
air deflector (white 5-core)
display panel (white 10-core)
hoisting grille (red 5-core)
Wifi (4 core)
° Pull the panel grille out of the panel, fix the cassette panel to the one- way cassett by two plastic buckles.
when connection is completed, please clip the wires to the buckle.
31
° Install the control box cover and turn the circuit breaker to ON, then close the two plastic covers on both sides of the panel. ° Open the cover with display panel, loosen the screw and remove the cover.
° Re-install the air grille by pushing the latchto lock it and fixing the two screws, then close the two screw covers.
Loosen the screw and remove the cover
Step3: Optinal parts installation
Wireless module Wireless module, or named smart kit, if you choose this
configuration, please follow the steps below to install. NOTE: If you choose
this configuration, it is recommended that installing this wireless module
during the step of panel installation. ° Remove the protective cap of the
wireless
module (smart kit).
32
TEST RUN
CAUTION
Failure to perform the test run may result in unit damage, property damage, or
personal injury.
Before test run
A test run must be performed after the entire system has been completely
installed. Confirm the following points before performing the test: a) Indoor
and outdoor units are properly installed. b) Piping and wiring are properly
connected. c) No obstacles near the inlet and outlet of the unit that might
cause poor performance or product malfunction. d) Refrigeration system does
not leak. e) Drainage system is unimpeded and draining to a safe location. f)
Heating insulation is properly installed. g) Grounding wires are properly
connected. h) Length of the piping and additional refrigerant capacity have
been recorded. i) Power voltage is the correct voltage for the air conditioner
Test Run Instructions
1. Open both the liquid and gas stop valves.
2. Turn on the main power switch and allow the unit to warm up.
3. Set the air conditioner to COOL mode.
4. For the Indoor Unit
a. Double check to see if the room temperature is being registered correctly.
b. Ensure the manual buttons on the indoor unit works properly.
c. Check to see that the drainage system is unimpeded and draining smoothly.
d. Ensure there is no vibration or abnormal noise during operation.
5. For the Outdoor Unit
a. Check to see if the refrigeration system is leaking.
b. Make sure there is no vibration or abnormal noise during operation.
c. Ensure the wind, noise, and water generated by the unit do not disturb your
neighbors or pose a safety hazard.
NOTE: If the unit malfunctions or does not operate according to your
expectations, please refer to the Troubleshooting section of the Owner’s
Manual before calling customer service.
Water Discharge Test
· Before the test, make sure that the water discharge pipeline is smooth, and
check that each connection is sealed properly.
· Conduct the water discharge test in the new room before the ceiling is
paved.
1. Connect the power supply, and set the air conditioner to operate in the
cool mode. Check the running sound of the drainage pump.
2. keep cool mode running at least 10 min. 3. Stop the air conditioner. Wait
for three minutes,
and then check if there is anything unusual. If the water discharge piping
layout is not correct, the excessive water flow will cause the water level
error and “EE” error code will be displayed on the display panel. There may
even be water overflowing from the water pan. 4. Continue to add water until
the alarm for excessive water levels is triggered. Check if the drainage pump
drains water immediately. After three minutes, if the water level does not
fall below the warning level, the unit will shut down. At this time, you need
to turn off the power supply, and drain away the accumulated water before you
can turn on the unit normally. 5. Turn off the power supply, remove the water
manually using the drainage plug, and put the test cap back to the original
place.
CAUTION
The drainage plug at the bottom of the unit body is used to discharge
accumulated water from the drain pan when the air conditioner malfunctions.
When the air conditioner is operating normally, make sure the drainage plug is
properly plugged to prevent water from leaking.
33
UNIT SPECIFICATIONS AND FEATURES
NOTE
Illustrations in this manual are for explanatory purposes. The actual shape of
your indoor unit may be slightly different. The actual shape shall prevail.
Unit Parts
Display Panel
Air Intake Grille
Air Filter Air Vane
Air Outlet Air Inlet
Operating temperature
Electronic Control Box
When your air conditioner is used outside of the following temperature ranges, certain safety protection features may activate and cause the unit to disable.
Inverter Split Type
Room Temperature
COOL mode
16°C – 32°C (61°F – 90°F)
Outdoor Temperature
-25°C – 50°C (-13°F – 122°F)
HEAT mode
0°C – 30°C (32°F – 86°F)
DRY mode
10°C – 32°C (50°F – 90°F)
-25°C – 24°C (-13°F – 75°F)
0°C – 50°C (32°F – 122°F)
FOR OUTDOOR UNITS WITH AUXILIARY ELECTRIC HEATER
When outside temperature is below 0°C(32°F ), we strongly recommend keeping
the unit plugged in at all time to ensure smooth ongoing performance.
NOTE: Room relative humidity less than 80%. If the air conditioner operates in excess of this figure, the surface of the air conditioner may attract condensation. Please sets the vertical air flow louver to its maximum angle (vertically to the floor), and set HIGH fan mode.
34
OPERATION INSTRUCTIONS
NOTE
To further optimize the performance of your unit, do the following: · Keep
doors and windows closed. · Limit energy usage by using TIMER ON and TIMER OFF
functions. · Do not block air inlets or outlets. · Regularly inspect and clean
air filters.
Indoor Unit Display
The display panel has one type and the appearance of the type is shown in
below. ” ” when Electric heating feature is activated. (Not available for this
unit) ” ” when TIMER is set. ” ” when the unit is on. ” ” Alarm indicator. ” ”
when Wireless Control feature is activated. (some units) ” ” when pre-
heating/defrost feature is activated. ” ” Displays temperature, operation
feature and Error codes. ” ” when 8°C heating feature is turned on. ” ” when
Active Clean feature is turned on. ” ” when WiFi module enters AP mode. (some
units) ” ” when Forced cooling feature is turned on.
Features
Default Setting
When the air conditioner restarts after a power failure, it will default to
the factory settings (AUTO mode, AUTO fan, 24°C (76°F)). This may cause
inconsistencies on the remote control and unit panel. Use your remote control
to update the status.
Auto-Restart
In case of power failure, the system will immediately stop. When power
returns, the Operation light on the indoor unit will flash. To restart the
unit, press the ON/OFF button on the remote control. If the system has an auto
restart function, the unit will restart using the same settings.
Three-minute protection feature
A protection feature prevents the air conditioner from being activated for
approximately 3 minutes when it restarts immediately after operation.
Louver Angle Memory Function
Some models are designed with a louver angle memory function. When the unit
restarts after a power failure, the angle of the horizontal louvers will
automatically return to the previous position. The angle of the horizontal
louver should not be set too small as condensation may form and drip into the
machine. To reset the louver, press the manual button, which will reset the
horizontal louver settings.
Refrigerant Leak Detection System (Multi-Zone Systems models do not have this
function)
In the event of a refrigerant leak, the LED DISPLAY will display refrigerant
leak error code and the LED indicator light will flash.
35
Sleep Operation
The SLEEP function is used to decrease energy use while you sleep (and don’t
need the same temperature settings to stay comfortable). This function can
only be activated via remote control. And the Sleep function is not available
in FAN or DRY mode.
Press the SLEEP button when you are ready to go to sleep. When in COOL mode,
the unit will increase the temperature by 1°C (2°F) after 1 hour, and will
increase an additional 1°C (2°F) after another hour. When in HEAT mode, the
unit will decrease the temperature by 1°C (2°F) after 1 hour, and will
decrease an additional 1°C (2°F)after another hour.
The sleep feature will stop after 8 hours and the system will keep running
with final situation.
SLEEP Operation
Set temperature
Cool mode(+1 C/2 F) per hour for the first two hours
1hr
1hr
Heat mode( -1 C/2 F) per hour for the first two hours
Keep running
Lifting panel operation
In the stand-by mode, press the “Mode” and “Down” buttons for 3 seconds at the
same time, the remote controller enters the setting panel state, and the
remote controller displays “F2”. When setting the panel status, press the “Up”
or “Down” buttons of the remote controller to control the rise or fall of the
grille, and press any other button to exit the setting. The up and down height
of the panel can reach a maximum of 1.5 meters. During the decline, if the
grille is raised by the obstacles, it will stop. During the ascending process,
if the grille is blocked and does not rise to the correct height or a finger
is pinched, it will automatically descend after a period of time and then
ascend. If the grille is bocked for the third times, then the display panel
will report an error and prompt for manual processing.
Breeze Away
This feature avoids direct air flow blowing on the body and make you feel
indulging in silky coolness.
Energy Saving Tips
Saving energy during sleep
Active Clean function (Multi-Zone Systems models do not have this function)
The Active Clean Technology washes away dust when it adheres to the heat
exchanger by automatically freezing and then rapidly thawing the frost. A “pi-
pi” sound will be heard. The Active clean operation is used to produce more
condensed water to improve the cleaning effect, and the cold air will blow
out. After cleaning, the internal wind wheel then keeps operating with hot air
to blow-dry the evaporator, thus keeping the inside clean. – When this
function is turned on, the indoor unit display window appears “CL ” , after 20
to 130 minutes, the unit will turn off automatically and cancel Active Clean
function. – For some units, the system will start high temperature cleaning
process, and the temperature of air outlet is very high. Please keep away from
it. And this would lead to the rising of the room temperature .
· DO NOT set the unit to excessive temperature levels.
· While cooling, close the curtains to avoid direct sunlight.
· Doors and windows should be kept closed to keep cool or warm air in the
room.
· DO NOT place objects near the air inlet and outlet of the unit.
· Clean the air filter every two weeks. · Adjust louvers properly and avoid
direct airflow. · Closing curtains during heating also helps keep
the heat in. · Doors and windows should be kept closed.
36
Remote Control Operation
Model Rated Voltage Signal Receiving Range Environment
Quick Start Guide
1 FIT BATTERIES
RG10L3(2HS)/BGEFU1,RG10L3(2HS)/BGEF 3.0V( Dry batteries R03/LR032) maximun 8m
(vertical distance ) -5°C~60°C(23°F~140°F)
2 SELECT MODE
AUTO COOL DRY HEAT FAN
3 SELECT TEMPERATURE
6 PRESS POWER BUTTON
5 POINT REMOTE TOWARD UNIT
4 SELECT FAN SPEED
AU-100%
Mode
HEDARCTYOAOULTO
SET TEMPERATURE LOMWEHDIGFAHN
On/Off Fan
Swing
M
NOT SURE WHAT A FUNCTION DOES? Refer to the How to Use Basic Functions and How
to Use Advanced Functions sections of this manual for a detailed description
of how to use your air conditioner.
SPECIAL NOTE
· Button designs on your unit may differ slightly from the example shown. · If
the indoor unit does not have a particular function, pressing that function’s
button on
the remote control will have no effect.
37
Handling the Remote Controller
Inserting and Replacing Batteries Your air conditioning unit may come with two
batteries(some units). Put the batteries in the remote control before use. 1.
Slide the back cover from the remote control
downward, exposing the battery compartment. 2.Insert the batteries, paying
attention to match
up the (+) and (-) ends of the batteries with 3. the symbols inside the
battery compartment.
Slide the battery cover back into place.
BATTERY NOTES For optimum product performance: · Do not mix old and new
batteries, or
batteries of different types. · Do not leave batteries in the remote
control if you don’t plan on using the device for more than 2 months.
BATTERY DISPOSAL Do not dispose of batteries as unsorted municipal waste.
Refer to local laws for proper disposal of batteries.
NOTES FOR USING REMOTE CONTROL
The device could comply with the local national regulations. · In Canada, it
should comply with
CAN ICES-3(B)/NMB-3(B). · In USA, this device complies with part 15 of
the FCC Rules. Operation is subject to the following two conditions: (1) This
device may not cause harmful
interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation. This
equipment has been tested and found to comply with the limits for a Class B
digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception,which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more
of the following measures: · Reorient or relocate the receiving antenna. ·
Increase the separation between the equipment and receiver. · Connect the
equipment into an outlet on a circuit different from that to which the
receiver is connected. · Consult the dealer or an experienced radio/TV
technician for help. · Changes or modifications not approved by the party
responsible for compliance could void user’s authority to operate the
equipment.
TIPS FOR USING REMOTE CONTROL
· The remote control must be used within 8 meters of the unit.
· The unit will beep when remote signal is received.
· Curtains, other materials and direct sunlight can interfere with the
infrared signal receiver.
· Remove batteries if the remote will not be used more than 2 months.
38
Buttons and Functions
1 4 5 8 9 12
Model:
RG10L3(2HS)/BGEFU1 RG10L3(2HS)/BGEF
Description
No.1
No.2
2 No.3 3
No.4 6 7
ON/OFF Turn the unit on or off.
MODE Scrolls through operation modes as follows: Auto > Cool > Dry > Heat >
Fan
BREEZE AWAY This feature avoids direct air flow blowing on the body and makes
you feel indulging in silky coolness.
TEMP. UP Increases temperature in 0.5°C (1°F) increments. Max. temperature is
30°C (86°F). (Press together & buttons at the same time for 3 seconds will
alternate the temperature display between the °C & °F).
10 No.5 11
13 14
SET
Scrolls through operation functions as follows: Active Clean > Fresh > Sleep >
Follow Me > AP Mode > Active Clean The selected symbol will flash on the
display area, press the OK button to confirm.
No.6
OK Used to confirm the selected functions
No.7
TIMER Set timer to turn unit on or off
No.8 No.9
No.10 No.11 No.12 No.13 No.14
TEMP. DOWN Decreases temperature in 0.5°C (1°F) increments. Min. temperature
is 16°C (60°F)
FAN SPEED AU > 20% > 60% > 80% > 100% Press the TEMP or button to increase/
decrease the fan speed in 1% increments.
SWING Starts and stops the horizontal louver movement. Hold down for 2 seconds
to initiate vertical louver auto swing feature(some units).
ECO/GEAR ECO > GEAR(75%) > GEAR(50%) > Previous setting mode > ECO
BOOST Enables unit to reach preset temperature in shortest possible time.
LED LED Turns LED display & air conditioner buzzer on and off
HUMIDITY Adjust the room humidity during Dry operation in a range of 35%~85%.
Press this button to increase the humidity in 5% increments. NOTE: After
setting, the humidity settings will display on the screen.
39
Remote Screen Indicators Information are displayed when the remote controller is power up.
Not available
Breeze Away
Not
Not
available available
Not Low battery available (If flashes)
Active clean
Fresh mode
Sleep mode
Follow me
MODE display Displays the current mode
Wireless control
AUTO COOL DRY
HEAT
FAN
Transmission ECO GEAR Timer Indicator Feature Feature ON
Timer Lock OFF Feature
Slience Feature
Temperature/Timer/Fan speed display
Displays the set temperature by default, or fan speed or
timer setting when using TIMER ON/OFF functions.
Temperature range: Fan speed setting range:
16-30°C/60-86°F
AU -100%
(20-28°C/68-82°F) Humidity setting range:
(Model dependent) 35% -85%
Timer setting range: This display is blank when
0-24 hours
operating in FAN mode.
FAN SPEED AUTO
SLIENCE
LOW
MED
HIGH
1% 2-20% 21-40% 41-60% 61-80% 81-100% *This fan speed can not be adjusted in AUTO or DRY mode.
Horizontal louver swing JJ J JJ
Vertical louver auto swing
Not available for this unit
CoolFlash mode display
NOTE
1. All indicators shown in the figure are for the purpose of clear
presentation. But during the actual operation, only the relative function
signs are shown on the display window.
40
How to Use Basic Functions
NOTE
ATTENTION! Before operation, please ensure the unit is plugged in and power is
available.
SETTING TEMPERATURE
The operating temperature range for units is 16-30°C (60-86°F)/20-28 C(68-82
F)(Model dependent). You can increase or decrease the set temperature in 0.5°C
(1°F) increments.
AUTO Mode
In AUTO mode, the unit will automatically select the COOL, FAN, or HEAT operation
based on the set temperature. (The AUTO Mode of heating operation is only applicable
to heating and cooling model)
1
1. Press the MODE button to select AUTO.
3
2. Set your desired temperature using the TEMP or TEMP button.
3. Press the ON/OFF button to start the unit. NOTE: FAN SPEED can’t be set in
AUTO mode.
2
COOL Mode
1. Press the MODE button to select COOL
mode.
1
2. Set your desired temperature using the
TEMP or TEMP button.
4
3. Press FAN button to select the fan speed
in a range of AU-100%.
4. Press the ON/OFF button to start the unit.
2
3
DRY Mode (dehumidifying)
1. Press the MODE button to select DRY.
2. Set your desired temperature using the TEMP
1
or TEMP button.
3. Press the ON/OFF button to start the unit.
3 NOTE: FAN SPEED cannot be changed in DRY
mode.
2
41
FAN Mode
1. Press the MODE button to select FAN mode.
2. Press FAN button to select the fan speed
1
in a range of AU-100%.
3. Press the ON/OFF button to start the unit.
3
NOTE: You can’t set temperature in FAN mode.
As a result, your remote control’s LCD screen
will not display temperature.
2
HEAT Mode
1. Press the MODE button to select HEAT mode.
2. Set your desired temperature using the TEMP or TEMP button.
3. Press FAN button to select the fan speed
1
in a range of AU-100%.
4
4. Press the ON/OFF button to start the unit.
NOTE: As outdoor temperature drops, the performance of your unit’s HEAT function may
be affected. In such instances, we recommend
2
using this air conditioner in conjunction with
other heating appliances.
3
42
Setting the TIMER
TIMER ON/OFF – Set the amount of time after which the unit will automatically
turn on/off.
TIMER ON setting
Press TIMER button to initiate the ON time sequence.
Press Temp. up or down button for for multiple times to set the desired time
to turn on the unit.
x5
Point remote to unit and wait 1sec, the TIMER ON will be activated.
1 sec
O N /OFF
M OD E
FA N
TEM P
LEEP
SCHUOTR T TIMER ON
TIMER OFF setting
Press TIMER button to initiate the OFF time sequence.
Press Temp. up or down button for for multiple times to set the desired time
to turn off the unit.
x5
Point remote to unit and wait 1sec, the TIMER OFF will be activated.
1 sec
O N /OFF
M OD E
FA N
TEM P
LEEP
SCHUOTR T TIMER ON
NOTE: 1. When setting the TIMER ON or TIMER OFF, the time will increase by 30
minutes increments with each
press, up to 10 hours. After 10 hours and up to 24, it will increase in 1 hour
increments. (For example, press 5 times to get 2.5h, and press 10 times to get
5h,) The timer will revert to 0.0 after 24. 2. Cancel either function by
setting its timer to 0.0h.
TIMER ON & OFF setting(example) Keep in mind that the time periods you set for both functions refer to hours after the current time.
xn
xn
1 sec
Timer starts
O N /OFF
M OD E
FA N
TEM P
LEEP
SCHUOTR T TIMER ON
Unit turns
ON
Unit turns
OFF
Current time 1PM
2:00PM 3:00PM 3:30PM
2.5 hours later 5 hours later
4PM
5PM
6PM
O N /OFF
M OD E
FA N
TEM P
LEEP
SCHUOTR T TIMER ON
Example: If current timer is 1:00PM, to set the timer as above steps, the unit will turn on 2.5h later (3:30PM) and turn off at 6:00PM.
43
How to Use Advanced Functions
Swing function Press Swing button
Swing
2s Swing
The horizontal louver will swing up and down automatically when pressing Swing
button. Press again to make it stop.
Airflow direction
Keep pressing this button more than 2 seconds, the vertical louver swing function is activated. (Model dependent)
Swing
If continue to press the SWING button, five different airflow directions can be set. The louver can be move at a certain range each time you press the button. Press the button until the direction you prefer is reached.
NOTE: When the unit is off, press and hold MODE and SWING buttons together for one second, the louver will open for a certain angle, which makes it very convenient for cleaning. Press and hold MODE and SWING buttons together for one second to reset the louver(some units only).
LED DISPLAY
5s
LED
LED
Press this button more
than 5 seconds(some units)
Press this button to turn on and turn off the display on the indoor unit.
Keep pressing this button more than 5 seconds, the indoor unit will display the actual room temperature. Press more than 5 seconds again will revert back to display the setting temperature.
Lifting panel function
3s
3s
Press together Mode button and ” ” button at the same time more than 3 seconds to activate this function, and the remote controller displays “F2″.When setting the panel status, press the ” ” or ” ” buttons of the remote controller to control the rise or fall of the grille, and press any other button to exit the setting.
44
ECO/GEAR function
Press X-ECO button to enter the energy efficient mode in a sequence of
following: ECO GEAR(75%) GEAR(50%) Previous setting mode ECO…… Note: This
function is only available under COOL mode.
ECO operation: Under cooling mode, press this button, the remote controller
will adjust the temperature automatically to 24OC/75OF, fan speed of Auto to
save energy (only when the set temperature is less than 24 OC/75OF). If the
set temperature is above 24OC/75OF, press the ECO button, the fan speed will
change to Auto, the set temperature will remain unchanged. NOTE: Pressing the
ECO button, or modifying the mode or adjusting the set temperature to less
than 24O C/75O F will stop ECO operation. Under ECO operation, the set
tmeperature should be 24OC/75OF or above, it may result in insufficient
cooling. If you feel uncomfortable, just press the ECO button again to stop
it. GEAR operation: Press the ECO/GEAR button to enter the GEAR operation as
following: 75%(up to 75% electrial energy consumption)
50%(up to 50% electrial energy consumption)
Previous setting mode. Under GEAR operation, the display on the remote
controller will alternage between electical energy consumption and set
temperature.
BREEZE AWAY
This feature avoids direct air flow blowing on the body and makes you feel
indulging in silky coolness. NTOE: This feature is available under cool,Fan
and Dry mode only.
Silence function
2s Keep pressing Fan button for more than 2 seconds to activate/disable
Silence function(some units). Due to low frequency operation of compressor, it
may result in insufficient cooling and heating capacity. Press ON/OFF, Mode,
Sleep, JETCOOL or Clean button while operating will cancel silence function.
45
FP function
Press this button 2 times during one second under HEAT Mode and setting
temperature of 16 OC/60OF or 20 OC/68O F(for model RG10L10(2HS)/BGEF only).
2
The unit will operate at high fan speed (while compressor on) with temperature
automatically set to 8 C/46 F.
Note: This function is for heat pump air conditioner only. Press this button 2
times during one second under HEAT Mode and setting temperature of 16 C/60 F
or 20 C/68 F(for model RG10L10(2HS)/BGEF) to activate FP function.Press
On/Off, Sleep, Mode, Fan and Temp. button while operating will cancel this
function.
LOCK function
5s
+ Boost
5s
Humidity
Press together Boost button and Humidity button at the same time more than 5 seconds to activate Lock function. All buttons will not response except pressing these two buttons for two seconds again to disable locking.
BOOST Function
Boost
When you select Boost feature in COOL mode, the unit will blow cool air with strongest wind setting to jump-start the cooling process. When you select Boost feature in HEAT mode, for units with Electric heat elements, the Electric HEATER will activate and jump-start the heating process.
46
SET function
SET
OK
Press the SET button to enter the function setting, then press SET button or
TEMP or TEMP button to select the desired function. The selected symbol will
flash on the display area, press the OK button to confirm.
To cancel the selected function, just perform the same procedures as above.
Press the SET button to scroll through operation functions as follows:
Active clean ( )J Fresh( ) J Sleep( )J Follow Me( ) J AP mode( )J
Active clean ( )….
[]: Model dependent
Active clean function( ) (some units) : The Active Clean Technology washes
away dust, mold, and grease that may cause odors when it adheres to the heat
exchanger by automatically freezing and then rapidly thawing the frost. When
this function is turned on, the indoor unit display window appears “CL”, after
20 to 45 minutes, the unit will turn off automatically and cancel CLEAN
function.
FRESH function( ) (some units) : WIonhieznert/hPelaFsRmEaSDHusfut
nCcotilolenctisori(nditeiapteendd, itnhge. on models) is energized and will
help to remove pollen and impurities from the air
Sleep function( ) :
eTnheergSyLEusEePwfuhnilcetiyoonuisslueseepd(atonddedcorne,atsneeed the same
temperature settings to stay comfortable). This function can only be
aFcUotriSvtEahteRe,ddSevMtiaaAilr,NesmUeeoAtLe,.,scleoenptroolp. eration,, in
Follow me function( ) :
The FOLLOW ME function enables the remote control to measure the temperature
at its current location and send this signal to the air conditioner every 3
minutes interval. When using AUTO, COOL or HEAT modes, measuring ambient
temperature from the remote control(instead of from the indoor unit itself)
will enable the air conditioner to optimize the temperature around you and
ensure maximum comfort.
NOTE: Press and hold Boost button for seven seconds to start/stop memory
feature of Follow Me function.
If the memory feature is activated, On ,,
displays for 3 seconds on the screen.
If the memory feature is stopped, Of ,,
displays for 3 seconds on the screen. While the memory feature is activated,
press the ON/OFF button, shift the mode or power failure will not cancel the
Follow me function.
AP function( )(some units) :
, ,,
,, ,,
Note: The SLEEP function is not available in FAN or DRY mode.
Choose AP mode to do wireless network configuration. For some units, it doesn’t work by pressing the SET button. To enter the AP mode, continuously press the LED button seven times in 10 seconds.
47
CARE AND MAINTENANCE
BEFORE CLEANING OR MAINTENANCE
REMEMBER TO DISCONNECT THE POWER BEFORE CLEANING OR MAINTENANCE, EXCEPT FOR
CLEANING AIR FILTER. TURN THE CURCUIT BREAKER OF THE INDOOR UNIT TO OFF IS NOT
A KIND OF POWER DISCONNECTION. · Contact an authorized service technician for
repair or maintenance. Improper repair and
maintenance may cause water leakage, electrical shock, or fire, and may void
your warranty. · DO NOT substitute a blown fuse with a higher or lower
amperage rating fuse, as this may cause
circuit damage or an electrical fire. · Make sure the drain hose is set up
according to the instructions. Failure to do so could cause
leakage and result in personal property damage, fire and electric shock. ·
Make sure that all wires are connected properly. Failure to connect wires
according to
instructions can result in electrical shock or fire.
CAUTION
· Only use a soft, dry cloth to wipe the unit clean. If the unit is especially
dirty, you can use a clothsoaked in warm water to wipe it clean.
· Do not use chemicals or chemically treated cloths to clean the unit. · Do
not use benzene, paint thinner,polishing powder or other solvents to clean the
unit. They can
cause the plastic surface to crack or deform. · Do not use water hotter than
40°C (104°F) to clean the front panel. This can cause the panel
to deform or become discolored. · DO NOT wash the unit under running water.
Doing so creates an electrical hazard. Clean the unit
using a damp, lint-free cloth and neutral detergent. Dry the unit with a dry,
lint-free cloth.
WARNING: DO NOT REMOVE OR CLEAN THE FILTER BY YOURSELF
Removing and cleaning the filter can be dangerous. Removal and maintenance
must be performed by a certified technician.
Cleaning Your Indoor Unit(Air Filter)
The filter prevents dust and other particles from entering the indoor unit.
Dust buildup can reduce the efficiency of the air conditioner. For optimum
efficiency, clean the air filter every two weeks or more frequently if you
live in a dusty area. Replace the filter with a new one if it’s heavily
clogged and cannot be cleaned. NOTE: In households with animals, you will have
to periodically wipe down the grille to prevent animal hair blocking airflow.
Model A
1. In the stand-by mode, press the “MODE” and “DOWN” buttons on the remote
controller a the same time for 3 seconds, the remote controller enters the
panel-setting state, the remote controller displays “F2”.
2.Then press “DOWN” button on the remote controller, the air grille
automatically goes down. When it stops, pick up the air filter.
a. Hold the upper edge of the filter with both hands. Gently turn and lift
until the upper edge is free from the wire rope.
b. Lift the filter and move it forward slightly until the filter is separated
from the 4 wire ropes.
c. Move the filter to the right until it is separated from the air grille ,
and then the filter can be taken out.
a b
c
48
Model B 1. Press the circular positon to open the two
screw covers, then remove the two screws.
Screw Cover 2. Hold and open the air grille, then take out the
air filter.
air filter 3. Clean the air filter
Dusts will accumulate on the filter along with the unit operation, and need to
be removed from the filter,or the unit would not function effectively. Clean
the filter every two weeks when you use the unit regularly. Clean the air
filter with a vacuum cleaner or water. a. The air intake side should face up
when using
a vacuum cleaner.
CAUTION
· Do not dry out the air filter under direct sunshine or with fire.
· The air filter should be installed before the unit body installation.
4. Re-install the air filter. 5. Press “UP” button on the remote controller
to reset the air grille. (Applicable to model A) Re-install the air grille by
fixing the two screws and close the two screw covers. (Applicable to model B)
CAUTION
· Before changing the filter or cleaning, turn off the unit .
· When removing filter, do not touch metal parts in the unit. The sharp metal
edges can hurt you.
· Do not use water to clean the inside of the indoor unit. This can destroy
insulation and cause electrical shock.
· Do not expose filter to direct sunlight when drying. This can shrink the
filter.
· Any maintenance and cleaning of outdoor unit should be performed by an
authorized dealer or a licensed service provider.
· Any unit repairs should be performed by an authorized dealer or a licensed
service provider.
· When the air grille is rising, please do not hinder the grille from rising
with your hands or other objects. Please do not pull the wire rope, if
necessary, please contact the local customer service team.
b. The air intake side should face down when using clean water.
For excessive dusts, use a soft brush and natural detergent to clean it and dry in a cool place.
49
Maintenance your AC.
Maintenance Long Periods of Non-Use
If you plan not to use your air conditioner for an extended period of time, do
the following:
Maintenance Pre-Season Inspection
After long periods of non-use, or before periods of frequent use, do the
following:
Clean all filters
Turn on FAN function until unit dries out completely
Check for damaged wires Clean all filters
Check for leaks
Turn off the unit and disconnect the power
Remove batteries from remote control
Make sure nothing is blocking all air inlets and outlets
Replace batteries
50
TROUBLESHOOTING
CAUTION
If any of the following conditions occurs, turn off your unit immediately! ·
The power cord is damaged or abnormally warm · You smell a burning odor · The
unit emits loud or abnormal sounds · A power fuse blows or the circuit breaker
frequently trips · Water or other objects fall into or out of the unit DO NOT
ATTEMPT TO FIX THESE YOURSELF! CONTACT AN AUTHORIZED SERVICE PROVIDER
IMMEDIATELY
Common Issues
The following problems are not a malfunction and in most situations will not require repairs.
Issue
Unit does not turn on when pressing ON/OFF button
Possible Causes
The Unit has a 3-minute protection feature that prevents the unit from
overloading. The unit cannot be restarted within three minutes of being turned
off.
Cooling and Heating Models: If the Operation light and PRE-DEF (Pre-heating/
Defrost) indicators are lit up, the outdoor temperature is too cold and the
unit’s anti-cold wind is activated in order to defrost the unit. In Cooling-
only Models: If the “Fan Only” indicator is lit up, the outdoor temperature is
too cold and the unit’s anti-freeze protection is activated in order to
defrost the unit.
The unit changes from COOL/HEAT mode to FAN mode
The indoor unit emits white mist Both the indoor and outdoor units emit white
mist
The unit may change its setting to prevent frost from forming on the unit.
Once the temperature increases, the unit will start operating in the
previously selected mode again. The set temperature has been reached, at which
point the unit turns off the compressor. The unit will continue operating when
the temperature fluctuates again.
In humid regions, a large temperature difference between the room’s air and
the conditioned air can cause white mist.
When the unit restarts in HEAT mode after defrosting, white mist may be
emitted due to moisture generated from the defrosting process.
The indoor unit makes noises
A squeaking sound is heard when the system is OFF or in COOL mode. The noise
is also heard when the drain pump (optional) is in operation.
A squeaking sound may occur after running the unit in HEAT mode due to
expansion and contraction of the unit’s plastic parts.
Both the indoor unit and outdoor unit make noises
Low hissing sound during operation: This is normal and is caused by
refrigerant gas flowing through both indoor and outdoor units.
Low hissing sound when the system starts, has just stopped running, or is
defrosting: This noise is normal and is caused by the refrigerant gas stopping
or changing direction.
Squeaking sound: Normal expansion and contraction of plastic and metal parts caused by temperature changes during operation can cause squeaking noises.
51
Issue
Possible Causes
The outdoor unit makes noises
The unit will make different sounds based on its current operating mode.
Dust is emitted from The unit may accumulate dust during extended periods of non-use, which will be
either the indoor or emitted when the unit is turned on. This can be mitigated by covering the unit during
outdoor unit
long periods of inactivity.
The unit emits a bad odor
The unit may absorb odors from the environment (such as furniture, cooking,
cigarettes, etc.) which will be emitted during operations.
The unit’s filters have become moldy and should be cleaned.
The fan of the outdoor unit does not operate During operation, the fan speed is controlled to optimize product operation.
NOTE
If problem persists, contact a local dealer or your nearest customer service
center. Provide
them with a detailed description of the unit malfunction as well as your model
number.
Troubleshooting
When troubles occur, please check the following points before contacting a repair company.
Problem
Possible Causes
Solution
Temperature setting may be higher than ambient room temperature
Lower the temperature setting
Poor Cooling Performance
The heat exchanger on the indoor or outdoor unit is dirty
The air filter is dirty
The air inlet or outlet of either unit is blocked Doors and windows are open
Excessive heat is generated by sunlight Too many sources of heat in the room
(people, computers, electronics, etc.) Low refrigerant due to leak or long-
term use
Clean the affected heat exchanger
Remove the filter and clean it according to instructions Turn the unit off,
remove the obstruction and turn it back on Make sure that all doors and
windows are closed while operating the unit Close windows and curtains during
periods of high heat or bright sunshine
Reduce amount of heat sources
Check for leaks, re-seal if necessary and top off refrigerant
52
Problem
The unit is not working
Possible Causes Power failure The power is turned off The fuse is burned out
Solution Wait for the power to be restored Turn on the power Replace the fuse
The Unit’s 3-minute protection Wait three minutes after restarting
has been activated
the unit
Timer is activated
Turn timer off
There’s too much or too little refrigerant in the system
Check for leaks and recharge the system with refrigerant.
The unit starts and stops frequently
Poor heating performance
Incompressible gas or moisture has entered the system.
System circuit is blocked
Evacuate and recharge the system with refrigerant
Determine which circuit is blocked and replace the malfunctioning piece of
equipment
The compressor is broken
The voltage is too high or too low
Cold air is entering through doors and windows
Low refrigerant due to leak or long-term use
Replace the compressor
Install a manostat to regulate the voltage
Make sure that all doors and windows are closed during use
Check for leaks, re-seal if necessary and top off refrigerant
53
TRADEMARKS, COPYRIGHTS AND LEGAL STATEMENT
logo, word marks, trade name, trade dress and all versions thereof are
valuable assets of Midea Group and/or its affiliates (“Midea”), to which Midea
owns trademarks, copyrights and other intellectual property rights, and all
goodwill derived from using any part of an Midea trademark. Use of Midea
trademark for commercial purposes without the prior written consent of Midea
may constitute trademark infringement or unfair competition in violation of
relevant laws.
This manual is created by Midea and Midea reserves all copyrights thereof. No
entity or individual may use, duplicate, modify, distribute in whole or in
part this manual, or bundle or sell with other products without the prior
written consent of Midea.
All the described functions and instructions were up to date at the time of
printing this manual. However, the actual product may vary due to improved
functions and designs.
DISPOSAL AND RECYCLING
Important instructions for environment(European Disposal Guidelines)
Compliance with the WEEE Directive and Disposing of the Waster Product: This
product complies with EU WEEE Directive (2012/19/EU). This product bears a
classification symbol for waster electrical and electronic equipment (WEEE).
This symbol indicates that this product shall not be disposed with other
household wastes at the end of its service life. Used device must be returned
to official collection point for recycling of electrical electronic devices.
To find these collection systems please contact to your local authorities or
retailer where the product was purchased. Each household performs important
role in recovering and recycling of old appliance. Appropriate disposal of
used appliance helps prevent potential negative consequences for the
environment and human health.
54
DATA PROTECTION NOTICE
For the provision of the services agreed with the customer, we agree to comply
without restriction with all stipulations of applicable data protection law,
in line with agreed countries within which services to the customer will be
delivered, as well as, where applicable, the EU General Data Protection
Regulation (GDPR). Generally, our data processing is to fulfil our obligation
under contract with you and for product safety reasons, to safeguard your
rights in connection with warranty and product registration questions. In some
cases, but only if appropriate data protection is ensured, personal data might
be transferred to recipients located outside of the European Economic Area.
Further information are provided on request. You can contact our Data
Protection Officer via MideaDPO@midea.com. To exercise your rights such as
right to object your personal date being processed for direct marketing
purposes, please contact us via MideaDPO@midea.com. To find further
information, please follow the QR Code.
55
The design and specifications are subject to change without prior notice for product improvement. Consult with the sales agency or manufacturer for details. Any updates to the manual will be uploaded to the service website, please check for the latest version.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>