BEKO TECHNOLOGIES BDL Compact 10-437 Intelligent Paperless Recorder Installation Guide
- September 7, 2024
- BEKO TECHNOLOGIES
Table of Contents
BDL Compact 10-437 Intelligent Paperless Recorder
“`html
Specifications
-
Product Name: Modbus Installation and Operating Instructions
Intelligent Paperless Recorder BDL Compact 10-437 -
Device Type: BDL Compact
-
Baud Rates: 1200, 2400, 4800, 9600, 19200, 38400 bps
-
Device Address Range: 1 to 247
-
Electrical Interface: RS485, 2 wire (Internal Connector
X4.1) -
Protocol: Modbus RTU
-
Supported Function Codes: 3 (Read Holding Register), 16 (Write
Multiple Register)
Product Usage Instructions
1. Safety Instructions
Please ensure that this manual corresponds with the specific
device type you are using.
Warnings:
-
Be cautious of supply voltage to avoid electric shock.
-
Avoid operating parameters that fall outside the specified
limits to prevent dangers to individuals and equipment. -
Proper installation and maintenance are crucial to prevent
malfunctions that can affect measurement accuracy.
2. Instructions
2.1 Definitions and Abbreviations
Definitions:
-
CRC: Cyclic Redundancy Check
-
Modbus Client: Device requesting data or actions from a Modbus
server -
Modbus Server: Device providing data or actions to Modbus
clients -
Modbus Address: Unique identifier for Modbus devices on a
network -
PDU: Protocol Data Unit
-
ADU: Application Data Unit
-
MBAP: Modbus Application Protocol
-
RS485: Standard for serial communication
-
Ethernet: Network communication standard
2.2 References
References:
-
MODBUS over Serial Line Specification and Implementation Guide
V1.02 – modbus.org 2006 Dec 20 -
MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1b – modbus.org
2006 Dec 28 -
MODBUS Messaging on TCP/IP Implementation Guide V1.0b – 2006
Oct 34 -
BDL Compact Operation Manual
Frequently Asked Questions (FAQ)
Q: What should I do if I encounter a malfunction with the BDL
Compact?
A: In case of a malfunction, ensure that the
device is correctly installed and maintained. Refer to the
operation manual for troubleshooting steps. If issues persist,
contact customer support for assistance.
“`
EN English
Modbus Installation and operating instructure intelligent paperless recorder
BDL Compact
10-437
METPOINT®BDL Compact
Daisychain setup
Table of contents
1. Saftey instructions ……………………………………………………………………………………………………………3
2. Instructions ……………………………………………………………………………………………………………………..4 2.1
Definitionandabbreviation…………………………………………………………………………………………4 2.2 References
…………………………………………………………………………………………………………………4
3. TechnichaldataBDLCompact……………………………………………………………………………………………5 3.1
BDLCompactMODBUSRTUspecification …………………………………………………………………..5 3.2
BDLCompactMODBUS/TCPSpecification ………………………………………………………………….5 3.3
GeneralModbusInformation ………………………………………………………………………………………5 3.3.1
Serialtransmissionmodes(RTU) ………………………………………………………………………..6 3.3.2
Ethernettransmissionmodes…………………………………………………………………………….6
4. Installation ………………………………………………………………………………………………………………………7 4.1
RS485buswiring(ModbusRTU)Connectiondiagramconnector,,E”……………………………7 4.2
EthernetconnectionforModbus/TCP ………………………………………………………………………….8
5. ModbusRTUcommunicationsettings………………………………………………………………………………..8 5.1
AccessingandchangingModbussettings …………………………………………………………………….8
6. ModbusTCPcommunicationsettings …………………………………………………………………………….. 10
7. Modbusaddressingmodel……………………………………………………………………………………………… 10 7.1
FunctionCode3(Readholdingregister) …………………………………………………………………… 11 7.2
Functioncode16(Writemultipleregisters)………………………………………………………………. 11
8. Modbusholdingregister ……………………………………………………………………………………………….. 12 8.1
BasicValuesRegister ………………………………………………………………………………………………. 12 8.2
RegisterChannelValues ………………………………………………………………………………………….. 13 8.3
Valuesregister ……………………………………………………………………………………………………….. 14 8.4 StatusRegister
……………………………………………………………………………………………………….. 17 8.4.1 Register Values Channel 1 …
4………………………………………………………………………………………..17 8.4.2 Status register Values 5 …
8…………………………………………………………………………………………….18 8.5 Channeldescription
………………………………………………………………………………………………… 20 8.6
AlarmSettings………………………………………………………………………………………………………… 23 8.7 Valueextended
………………………………………………………………………………………………………. 24 8.8 Dataformattest
……………………………………………………………………………………………………… 26 8.9 DataBitdescription
………………………………………………………………………………………………… 26 8.10
UserUnits…………………………………………………………………………………………………………….. 28
9. Appendix ……………………………………………………………………………………………………………………… 31 9.1 APPENDIXA-
Exceptioncodes ………………………………………………………………………………… 31
2 | 32
Daisychain setup
METPOINT®BDL Compact
1. Saftey instructions
Please check whether this manual corresponds with the device type.
Please attend to all notes indicated in this instruction manual. It contains
essential information which has to be followed during installation, operation
and maintenance. Therefore this instruction manual has to be read
categorically by the technician as well as by the responsible user/qualified
personnel before installation, initiation and maintenance. This instruction
manual has to be available at any time at the operation site of the
BDL.Compact Regional and national regulations respectively, have to be
observed in addition to this instruction manual if necessary. In case of any
obscurities or questions with regard to this manual or the instrument please
contact manufacturer.
Warning Supply voltage! Contact with supply voltage carrying non-insulated
parts may cause an electric shock with injury and death.
Measures: · Note all applicable regulations for electrical installations (e.
g. VDE 0100)! · Carry out maintenance only in strainless state! · All electric
works are only allowed to be carried out by authorized qualified personnel
Warning Inadmissible operating parameters! Undercutting and exceeding
respectively of limit values may cause danger to persons and material and may
lead to functional and operational disturbances.
Measures: · Make sure that the BDL Compact is only operated within the
admissible limit values indicated on the type
label. · Strict observance of the performance data of the BDL Compact in
connection with the application. · Do not exceed the admissible storage and
transportation temperature.
Further safety instructions: · Attention should also be paid to the applicable
national regulations and safety instructions during
installation and operation. · The BDL Compact is not allowed to be used in
explosive areas. Additional remarks: · Do not overheat the instrument!
Warning Malfunctions at the BDL Compact! Faulty installation and insufficient
maintenance may lead to malfunctions of the BDL Compact which may affect the
measuring results and which may lead to misinterpretations.
3 | 32
METPOINT®BDL Compact
Daisychain setup
2. Instructions
This manual is intended to provide instructions for the installation and use
of the BDL Compact MODBUS function. The BDL Compact MODBUS function can let
the MODBUS client device to read out the online measurement values. This
manual is not intended to be a complete tutorial on the MODBUS RTU protocol,
and it is assumed the end user already has a general working knowledge of
MODBUS RTU Communications, especially in respect of client station
configuration and operation. However an overview is included in the following
section to explain some of the fundamental aspects of the protocol.
2.1 Definitionandabbreviation
CRC
Modbus client
Modbus server Modbus Address
PDU ADU MBAP RS485 Ethernet
Cyclic Redundancy Check Used for error–checking in MODBUS RTU. See appendix A MODBUS device, which is able to access data in one or more connected MODBUS servers A MODBUS device, which is able to respond to requests from a single MODBUS client Throughout this document the following notation is used to address MODBUS RTU registers see chapter 8 Addressing: Holding Register 1009 is addressed in messages by 1008 MODBUS protocol data unit MODBUS application data unit MODBUS application protocol Refers to the 2–wire communication standard defined by EIA/TIA-485. (Physical layer)
2.2 References
1. MODBUS over Serial Line Specification and Implementation Guide V1.02
modbus.org 2006 Dec 20 2. MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1b
modbus.org 2006 Dec 28 3. MODBUS Messaging on TCP/IP implementation Guide
V1.0b 2006 Oct 34 4. BDL Compact operation manual
4 | 32
Daisychain setup
METPOINT®BDL Compact
3. TechnichaldataBDLCompact
3.1 BDLCompactMODBUSRTUspecification
Device type Baud Rates Device address range Electrical Interface Protocol
Supported function code
Broadcast Standard
Server 1200, 2400, 4800, 9600, 19200, 38400 bps 1 … 247 RS485, 2 wire (Internal Connector X4.1) RTU 3 read holding register 16 write multiple register No Modbus over serial line V1.02
3.2 BDLCompactMODBUS/TCPSpecification
Device type Device address range Electrical Interface Protocol IP address Port
Supported function code
Standard
Server 1 … 247 Ethernet, RJ45 MODBUS/TCP Obtained from DHCP or static 502 3 read holding register 16 write multiple register Modbus Messaging on TCP/IP Implementation Guide V1.0b
3.3 GeneralModbusInformation
The BDL Compact Modbus module complies with the Modbus serial line protocol
[Reference 1]. Among other things this implies a client-server protocol at
level 2 of the OSI model. One node (the client) issues explicit commands to
one of the ,,server”-nodes and processes responses. server nodes will not
transmit data without a request from the client node, and do not communicate
with other servers. Modbus is a mono client system, which means that only one
client can be connected at the time.
5 | 32
METPOINT®BDL Compact
Daisychain setup
3.3.1 Serialtransmissionmodes(RTU)
The BDL Compact Modbus mode support only one serial transmission modes; the
RTU mode. The transmission mode defines the bit contents of message fields
transmitted serially on the line. It determines how information is packed into
the message fields and decoded.The transmission mode and serial port
parameters must be the same for all devices on a Modbus serial line.
RTU mode Modbus Application Data Unit (ADU) frame is shown below, and is valid for both requests and responses.
Client Address
Function code
Data
1 byte
1 byte
0 … 252 byte(s)
Table1
Further details of the Modbus protocol can be found in Reference 1 and 2.
CRC
2 bytes
3.3.2 Ethernettransmissionmodes
The BDL Compact Modbus mode supports the Modbus/TCP only The transmission mode
defines the bit contents of message fields transmitted serially on the line.
It determines how information is packed into the message fields and decoded.
The transmission mode and serial port parameters must be the same for all
devices on a Modbus serial line.
Modbus/TCP mode Modbus Application Data Unit (ADU) frame is shown below, and
is valid for both requests and responses
Modbus/TCP MBAP Header
Transaction Protocol
Id
Id
Length
2 byte
2 byte
2 byte
Table 2
Unit Id
1 byte
PDU Function
Code
1 byte
Data
0 … 252 byte (s)
6 | 32
Daisychain setup
METPOINT®BDL Compact
4. Installation 4.1 RS485buswiring(ModbusRTU)Connectiondiagramconnector,,E”
123456
Common RS485 (B) RS485 (A) Common RS485 (B) RS485 (A)
A
B
Common
R T
Server 1
R T
Server n
Client
T R
123456
A B
Common
R T
Server n
Common RS485 (B) RS485 (A) Common RS485 (B) RS485 (A)
BDLc Ethernet Board plug ,,E”
Bus cable:
Only cables according to the recommendations of EIA 485 standard should be
used. A maximum of 64 devices may be connected to one segment. The bus cable
must be laid at a distance of at least 20 cm from other cables. It should be
laid in a separate, conductive, and earthed cable trunking. It must be ensured
that no potential differences occur between the individual devices on the bus.
Cable specification:
Impedance: Cable capacity: Cable diameter: Cross section: Loop resistance
Screening:
135 -165 Ohm @ 3 to 20 Mhz < 30 pF/m > 0.64 mm > 0.34 mm2, conforms to AWG 22 < 110 Ohm per km Cu shielding braid or shielding braid and shielding foil
7 | 32
METPOINT®BDL Compact
Daisychain setup
4.2 EthernetconnectionforModbus/TCP
For easy Ethernet cable connection to your network an ordinary RJ45 Ethernet
cable connection is provided.
Cable: An Ethernet cable with category 5 or better is to be used.
5. ModbusRTUcommunicationsettings
Before communication with the client, baudrate, address, and framing must be
defined
5.1 AccessingandchangingModbussettings
First step: Main menu Settings Device settings Modbus settings
The settings are all protected by a password! Inputs and changes have to be confirmed by pressing OK in general!
Enter Password
Factory settings for password at the time of delivery: 0000 (4 times zero).
If required, the password can be changed in the Password settings.
The new password must be entered two times in a row and in each case confirmed
with OK.
If an incorrect password is entered there appears Enter password or New
password repeat in red font.
If you can’t remember the password, please use Master password in order to
enter a new password.
Remark:
The Master password is supplied together with the instrument’s documentation.
8 | 32
Daisychain setup
METPOINT®BDL Compact
MainmenuSettingsDevicesettingsModbussettings
Here please define your communication parameters.
Modbus Id, Baudrate,Stopbits,Parity, Term and Bias
Enable the RTU Modbus by activation of the enable Modbus button. Confirm the changes by pressing the button Apply
Remark: Only in case of changes the button Apply appears else to go back with button Back
By pressing the button Set to Default the default values will be defined.
Default values: Baudrate:
19200 bps
Parity:
even
Stopbits
1
In case the BDL Compact is at the bus end (last server in the bus) then the Modbus have to be terminated. This is done for the BDL Compact by SW by activation of the Term and Bias Button
Note:
ItisrecommendedNOTtousethedefaultaddressinamulti-
servernetwork.Itisofgreatimportance
toensureatthetimeoftheprocedureofdeviceaddressing,thatthereisnottwodeviceswiththesame
address.Insuchacase,anabnormalbehaviorofthewholeserialbuscanoccur,theclientbeingtheninthe
impossibilitytocommunicatewithallpresentsonthebus.
9 | 32
METPOINT®BDL Compact
6. ModbusTCPcommunicationsettings
Daisychain setup
By communication via Modbus TCP the Modbus Id have to be set only and confirmed by pressing Apply button
7. Modbusaddressingmodel
The BDL Compact RS485 Modbus allows read/write access according chapter 8 Not
defined registers are not accessible / not supported.
ByteOrder:
The size of each Modbus-register is 2 Byte. For a 32 bit value two
Modbusregister will be read out by the BDL Compact. Accordingly for a 16bit
Value only one register is read.
Out formats of BDL Compact: Single word
18 =>
HByte 00
LByte 12
29235175522=>
Double word HWord HByte
AE
LByte 41
LWord HByte
56
LByte 52
Data Order 1. Byte 2. Byte Data Order
1.Byte
2.Byte
12
00
56
52
For verification of a correct dataformat please read out register 64000 or 64002.
3.Byte AE
4.Byte 41
Result should be.
Register 64000: Long Integer Value =1000000
Register 64002: Float
Value = 1000000.0
10 | 32
Daisychain setup
METPOINT®BDL Compact
7.1 FunctionCode3(Readholdingregister)
General exceptions: · Requesting less than 1 or more than 125 registers =>
Exception 3 (Illegal data value) · Requesting more than max. message size (27
registers) => Exception 2(Illegal data address) · Requesting data out of
defined range of registers chapter 8 => Exception 2 (Illegal data address)
Application exceptions: · Application errors => Exception 4 (server device
error)
Holes/register alignment: · The read command always returns data if no
exception is given. Bad Start/end alignment will result in
only parts of the data item being read.
7.2 Functioncode16(Writemultipleregisters)
In general only status register (register 2001 2064) are writable.
General exceptions: · Writing less than 1 or more than 63 registers =>
Exception 3 (Illegal data value) · If ByteCount is not exactly 2 times
NoOfRegisters => Exception 3 (Illegal data value) · Exceeding max. message
size (27 registers) => Exception 2 (Illegal data address) · Writing data out
of defined register range chapter 8 =>Exception 2 (Illegal data address)
Application exceptions: · Application errors => Exception 4 (server device
error) · Application errors include writing to ReadOnIy holding registers
Holes / register alignment: · If start-address is not the start of a mapped
holding register => Exception 2 (Illegal data address) · Writing to holes is
allowed (ie ignored – and no exception occurs) — except for the condition
described
above
11 | 32
METPOINT®BDL Compact
Daisychain setup
8. Modbusholdingregister
8.1 BasicValuesRegister
Modbus Modbus No.of Data Register Address Byte Type
1
0
4 Dword
3
2
8 String
7
6
4 Dword
Description
Serial Number HostName HardwareVersion
Default Setting
0 0 0
9
8
4 Dword Softwareversion
0
11
10
8 Byte(6) MAC Adress
0
15
14
4 Dword Calibration Date
0
17
16
4 Dword Runtime Counter
0
19
18
4 Dword Timet
0
21
20
16 String Brand Name
0
29
28
2 Word Modbus ID
0
30
29
2 Word free
0
31
30
4 Dword MbRTU Rx
0
Packets OK
33
32
4 Dword MbRTU Tx
0
Packets
35
34
4 Dword MbRTU CRC
0
Errors
37
36
4 Dword MbRtu Parity
0
Errors
Read Write
R R R
R
R
R R R R R R R
R
R
Comment
sprintf(str,”%u.%02u”, hw>>16,hw&0xffff); sprintf(str,”%u.%02u”,
sw>>16,sw&0xffff); Upper 2 bytes are zero Unix Time Value in seconds Unix Time
Modbus ID free valid RTU telegrams received RTU telegrams transmitted CRC
Errors
R Parity Errors
12 | 32
Daisychain setup
METPOINT®BDL Compact
8.2 RegisterChannelValues
Important: When reading SF xx sensors, the following points must be observed:
·
TheregisterassignmentforSFxxsensorsvaluesdiffersfromtheregisterassignmentofothersensors
andparameters. ·
Consumptionvalue(s)forSFxxsensorsarealwaysintegervaluesI4(32b),contrarytothetable.
Arrangement SF xxStandard (w/o pressure)
1st value 3rd value 5th value 8th value
Example for channel 1:
Channel Value A1 Value A1 Value A1 Value A1
Value 1 3 5 8
Register Register 1000 (Flow) Register 1004 (Consumtion) Register 1200 (Temperature) Register 1206 (Velocity)
13 | 32
METPOINT®BDL Compact
Daisychain setup
8.3 Valuesregister
Modbus Register
1001 1003 1005 1007 1009 1011 1013 1015 1017 1019 1021 1023 1025 1027 1029
1031 1033 1035 1037 1039 1041 1043
Modbus Address
1000 1002 1004 1006 1008 1010 1012 1014 1016 1018 1020 1022 1024 1026 1028
1030 1032 1034 1036 1038 1040 1042
No.of Byte
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
Data Type
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Description
Channel A1 1st value
Channel A1 2nd value Channel A1 3rd value Channel A1 4th value Channel A2 1st
value Channel A2 2nd value Channel A2 3rd value Channel A2 4th value Channel
B1 1st value Channel B1 2nd value Channel B1 3rd value Channel B1 4th value
Channel B2 1st value Channel B2 2nd value Channel B2 3rd value Channel B2 4th
value Channel V1 1st value Channel V1 2nd value Channel V1 3rd value Channel
V1 4th value Channel V2 1st value Channel V2 2nd value
Default Setting
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Read Write
R R R R R R R R R R R R R R R R R R R R R R
Comment
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
14 | 32
Daisychain setup
METPOINT®BDL Compact
Modbus Register
1045 1047 1049 1051 1053 1055 1057 1059 1061 1063 1201 1203 1205 1207 1209
1211 1213 1215 1217 1219 1221 1223 1225
Modbus Address
1044 1046 1048 1050 1052 1054 1056 1058 1060 1062 1200 1202 1204 1206 1208
1210 1212 1214 1216 1218 1220 1222 1224
No.of Byte
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
Data Type
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Description
Channel V2 3rd value
Channel V2 4th value
Channel V3 1st value
Channel V3 2nd value
Channel V3 3rd value
Channel V3 4th value
Channel V4 1st value
Channel V4 2nd value
Channel V4 3rd value
Channel V4 4th value
Channel A1 5th value
Channel A1 6th value
Channel A1 7th value
Channel A1 8th value
Channel A2 5th value
Channel A2 6th value
Channel A2 7th value
Channel A2 8th value
Channel B1 5th value
Channel B1 6th value
Channel B1 7th value
Channel B1 8th value
Channel B2 5th value
Default Setting
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Read Write
R R R R R R R R R R R R R R R R R R R R R R R
Comment
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value *1)
15 | 32
METPOINT®BDL Compact
Daisychain setup
Modbus Register
1227 1229 1231 1233 1235 1237 1239 1241 1243 1245 1247 1249 1251 1253 1255
1257 1259 1261 1263
Modbus Address
1226 1228 1230 1232 1234 1236 1238 1240 1242 1244 1246 1248 1250 1252 1254
1256 1258 1260 1262
No.of Byte
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
Data Type
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Float/ Dword
Description
Channel B2 6th value
Channel B2 7th value
Channel B2 8th value
Channel V1 5th value
Channel V1 6th value
Channel V1 7th value
Channel V1 8th value
Channel V2 5th value
Channel V2 6th value
Channel V2 7th value
Channel V2 8th value
Channel V3 5th value
Channel V3 6th value
Channel V3 7th value
Channel V3 8th value
Channel V4 5th value
Channel V4 6th value
Channel V4 7th value
Channel V4 8th value
Default Setting
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Read Write
R R R R R R R R R R R R R R R R R R R
Comment
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value 1)
BDL Compact Data Value *1)
16 | 32
Daisychain setup
METPOINT®BDL Compact
8.4 StatusRegister
8.4.1 RegisterValuesChannel1…4
Modbus Register
2001
Modbus No.of Address Byte
2000
2
Data Type
word
2002
2001
2
word
2003
2002
2
word
2004
2003
2
word
2005 2006 2007
2004
2
word
2005
2
word
2006
2
word
2008
2007
2
word
2009
2008
2
word
2010
2009
2
word
2011
2010
2
word
2012
2011
2
word
2013
2012
2
word
2014
2013
2
word
2015 2016 2017
2014
2
word
2015
2
word
2016
2
word
2018
2017
2
word
2019
2018
2
word
2020
2019
2
word
Description
Channel A1 Value 1 Status
Channel A1 Value 2 Status
Channel A1 Value 3 Status
Channel A1 Value 4 Status
Channel A2 Value 1 Status
Channel A2 Value 2 Status
Channel A2 Value 3 Status
Channel A2 Value 4 Status
Channel B1 Value 1 Status
Channel B1 Value 2 Status
Channel B1 Value 3 Status
Channel B1 Value 4 Status
Channel B2 Value 1 Status
Channel B2 Value 2 Status
Channel B2 Value 3 Status
Channel B2 Value 4 Status
Channel V1 Value 1 Status
Channel V1 Value 2 Status
Channel V1 Value 3 Status
Channel V1 Value 4 Status
Default Setting
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Read Write
R/W R/W R/W R/W
R R R R R R R R R R R R R R R R
Comment
Status 2) Status 2) Status 2) Status 2) Status 2) Status 2) Status 2)
Status 2) Status 2) Status 2) Status 2) Status 2) Status 2) Status 2)
Status 2) Status 2) Status 2) Status 2) Status 2) Status 2)
17 | 32
METPOINT®BDL Compact
Daisychain setup
Modbus Register
2021
Modbus No.of Address Byte
2020
2
Data Type
word
2022
2021
2
word
2023
2022
2
word
2024
2023
2
word
2025
2024
2
word
2026 2027
2025
2
word
2026
2
word
2028 2029
2027
2
word
2028
2
word
2030
2029
2
word
2031
2030
2
word
2032
2031
2
word
Description
Channel V2 Value 5 Status
Channel V2 Value 6 Status
Channel V2 Value 7 Status
Channel V2 Value 8 Status
Channel V3 Value 5 Status
Channel V3 Value 6 Status
Channel V3 Value 7 Status
Channel V3 Value 8 Status
Channel V4 Value 5 Status
Channel V4 Value 6 Status
Channel V4 Value 7 Status
Channel V4 Value 8 Status
Default Setting
0 0 0 0 0 0 0 0 0 0 0 0
Read Write
R R R R R R R R R R R R
Comment
Status 2) Status 2) Status 2) Status 2) Status 2) Status 2) Status 2)
Status 2) Status 2) Status 2) Status 2) Status 2)
8.4.2 StatusregisterValues5…8
Modbus Modbus No.of Data Register Address Byte Type
2101
2100
2
word
2012
2101
2
word
2103
2012
2
word
2104
2103
2
word
2105
2104
2
word
2106
2105
2
word
Description
Channel A1 Value 5 Status
Channel A1 Value 6 Status
Channel A1 Value 7 Status
Channel A1 Value 8 Status
Channel A2 Value 5 Status
Channel A2 Value 6 Status
Default Setting
0 0 0 0 0 0
Read Write
R R R R R R
Comment
Status 2) Status 2) Status 2) Status 2) Status 2) Status 2)
18 | 32
Daisychain setup
METPOINT®BDL Compact
Modbus Register
2107
Modbus No.of Address Byte
2106
2
Data Type
word
2108 2109 2110
2107 2108 2109
2
word
2
word
2
word
2111
2110
2
word
2112
2111
2
word
2113
2112
2
word
2114
2113
2
word
2115
2114
2
word
2116
2115
2
word
2117
2116
2
word
2118 2119 2120
2117 2118 2119
2
word
2
word
2
word
2121
2120
2
word
2122
2121
2
word
2123
2122
2
word
2124
2123
2
word
2125
2124
2
word
2126
2125
2
word
2127
2126
2
word
Description
Channel A2 Value 7 Status
Channel A2 Value 8 Status
Channel B1 Value 5 Status
Channel B1 Value 6 Status
Channel B1 Value 7 Status
Channel B1 Value 8 Status
Channel B2 Value 5 Status
Channel B2 Value 6 Status
Channel B2 Value 7 Status
Channel B2 Value 8 Status
Channel V1 Value 5 Status
Channel V1 Value 6 Status
Channel V1 Value 7 Status
Channel V1 Value 8 Status
Channel A1 Value 1 Status
Channel A1 Value 2 Status
Channel A1 Value 3 Status
Channel A1 Value 4 Status
Channel A2 Value 1 Status
Channel A2 Value 2 Status
Channel A2 Value 3 Status
Default Setting
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Read Write
R R R R R R R R R R R R R R R/W R/W R/W R R R R
Comment
Status 2) Status 2) Status 2) Status 2) Status 2) Status 2) Status 2)
Status 2) Status 2) Status 2) Status 2) Status 2) Status 2) Status 2)
Status 2) Status 2) Status 2) Status 2) Status 2) Status 2) Status *2)
19 | 32
METPOINT®BDL Compact
Daisychain setup
Modbus Modbus No.of Data Register Address Byte Type
2128
2127
2
word
2129
2128
2
word
2130
2129
2
word
2131
2130
2
word
2132
2131
2
word
Description
Channel A2 Value 4 Status
Channel A3 Value 1 Status
Channel A3 Value 2 Status
Channel A3 Value 3 Status
Channel A3 Value 4 Status
Default Setting
0 0 0 0 0
Read Write
R R R R R
Comment
Status 2) Status 2) Status 2) Status 2) Status *2)
8.5 Channeldescription
Modbus Register
3001 3002 3014 3015 3016 3017 3018 3019 3020 3021 3033 3034 3046 3047 3048
Modbus No.of Data Address Byte Type
3000
2
word
3001 3013
24 string
2
word
3014
2
word
3015
2
word
3016
2
word
3017
2
word
3018 3019
2
word
2
word
3020
2
word
3032
2
word
3033 3045
24 string
2
word
3046
2
word
3047
2
word
Description
Channel A1 sensor type Channel Name name/unit index value 1 name/unit index
value 2 name/unit index value 3 name/unit index value 4 name/unit index value
5 name/unit index value 6 name/unit index value 7 name/unit index value 8
Channel A2 sensor type Channel Name name/unit index value 1 name/unit index
value 2 name/unit index value 3
Default Setting
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Read Write
R
Comment
Sensor Type *3)
R
Sensor Name *4)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R
Sensor Type *3)
R
Sensor Name *4)
R Value description *5)
R Value description *5)
R Value description *5)
20 | 32
Daisychain setup
METPOINT®BDL Compact
Modbus Register
3049 3050 3051 3052 3053 3065 3066 3078 3079 3080 3081 3082 3083 3084 3085
3097 3098 3110 3111 3112 3113 3114 3115 3116
Modbus No.of Data Address Byte Type
3048
2
word
3049
2
word
3050
2
word
3051
2
word
3052
2
word
3064
3065 3077
2
word
24 string
2
word
3078 3079
2
word
2
word
3080
2
word
3081
2
word
3082
2
word
3083
2
word
3084 3096
2
word
2
word
3097 3009
24 string
2
word
3110
2
word
3111
2
word
3112
2
word
3113
2
word
3114
2
word
3115
2
word
Description
name/unit index value 4
name/unit index value 5
name/unit index value 6
name/unit index value 7
name/unit index value 8
Channel B1 sensor type
Channel Name
name/unit index value 1
name/unit index value 2
name/unit index value 3
name/unit index value 4
name/unit index value 5
name/unit index value 6
name/unit index value 7
name/unit index value 8
Channel B2 sensor type
Channel Name
name/unit index value 1
name/unit index value 2
name/unit index value 3
name/unit index value 4
name/unit index value 5
name/unit index value 6
name/unit index value 7
Default Setting
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Read Write
Comment
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R
Sensor Type *3)
R
Sensor Name *4)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R
Sensor Type *3)
R
Sensor Name *4)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
21 | 32
METPOINT®BDL Compact
Daisychain setup
Modbus Register
3117 3129 3130 3142 3143 3149 3145 3146 3147 3148 3149 3161 3162 3174 3175
3176 3177 3178 3179 3180 3181 3193 3194 3206
Modbus No.of Data Address Byte Type
3116
2
word
3128
3129 3141
2
word
24 string
2
word
3142
2
word
3143
3149
2
word
3145
2
word
3146
2
word
3147
2
word
3148
2
word
3160
2
word
3161 3173
24 string
2
word
3174
2
word
3175 3176
2
word
2
word
3177
2
word
3178
2
word
3179
2
word
3180
3292
3293 3205
2
word
2
word
24 string
2
word
Description
name/unit index value 8 Channel V1 sensor type Channel Name
name/unit index value 1
name/unit index value 2
name/unit index value 3
name/unit index value 4
name/unit index value 5
name/unit index value 6
name/unit index value 7
name/unit index value 8 Channel V2 sensor type Channel Name
name/unit index value 1
name/unit index value 2
name/unit index value 3
name/unit index value 4
name/unit index value 5
name/unit index value 6
name/unit index value 7
name/unit index value 8 Channel V3 sensor type Channel Name
name/unit index value 1
Default Setting
0 0 0 0 0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Read Write
Comment
R Value description *5)
R
Sensor Type *3)
R
Sensor Name *4)
R Value description *5)
R Value description *5)
Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R
Sensor Type *3)
R
Sensor Name *4)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R
Sensor Type *3)
R
Sensor Name *4)
R Value description *5)
22 | 32
Daisychain setup
METPOINT®BDL Compact
Modbus Register
3207 3208 3209 3210 3211 3112 3113 3225 3226 3238 3239 3240 3241 3242 3243
3244 3245
Modbus No.of Data Address Byte Type
3206
2
word
3207
2
word
3208 3209
2
word
2
word
3210
2
word
3211
2
word
3112
2
word
3224
2
word
3225 3237
24 string
2
word
3238
2
word
3239
2
word
3240
2
word
3241
2
word
3242
2
word
3243
2
word
3244
2
word
Description
name/unit index value 2
name/unit index value 3
name/unit index value 4
name/unit index value 5
name/unit index value 6
name/unit index value 7
name/unit index value 8 Channel V4 sensor type Channel Name
name/unit index value 1
name/unit index value 2
name/unit index value 3
name/unit index value 4
name/unit index value 5
name/unit index value 6
name/unit index value 7
name/unit index value 8
Default Setting
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Read Write
Comment
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R
Sensor Type *3)
R
Sensor Name *4)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
R Value description *5)
8.6 AlarmSettings
Modbus Register
4001
4002 4003
4005
Modbus No.of Data Address Byte Type
4000
2
word
4001 4002
2
word
4
float
4004
4
float
Description
Channel / Value Relais
upper warning value
Hysteresis for above
Default Setting
0
0 0
0
Read Write
Comment
R Alarmsettings #1 *6)
R
relais setting *7)
R
R
23 | 32
METPOINT®BDL Compact
Daisychain setup
Modbus Register
4007 4009 4011 4013 4015 4017 4019 4021 4022 4023 4025 4027 4029 4031 4033
4035 4037 4039
Modbus No.of Data Address Byte Type
4006
4
float
4008
4
float
4010
4
float
4012
4
float
4014
4
float
4016
4018 4020
4
float
4
float
2
word
4021 4022
2
word
4
float
4024 4026 4028
4
float
4
float
4
float
4030
4
float
4032
4
float
4034 4036 4038
4
float
4
float
4
float
Description
upper alarm value
Hysteresis for above
lower warning value
Hysteresis for above
lower alarm value
Hysteresis for above
Reserved
Channel / Value
Relais
upper warning value
Hysteresis for above
upper alarm value
Hysteresis for above
lower warning value
Hysteresis for above
lower alarm value
Hysteresis for above
Reserved
Default Setting
0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0
Read Write
R R R R R R
Comment
R Alarmsettings #1 *6)
R
relais setting *7)
R
R
R
R
R
R
R
R
8.7 Valueextended
Modbus Register
10001
Modbus No.of Data Address Byte Type
10000
12 string
10007
10006
6
string
10010
10009
2
word
Description
A1a Value Name long A1a Value Name short A1a Value Resolution
Default Read Setting Write
0
R
0
R
0
R
Comment
string max. 10 character
string max. 3 character 0 … 5
24 | 32
Daisychain setup
METPOINT®BDL Compact
Modbus Register
10011 10026
10032
10035 10036 10051
10057 10060 10061 10076
10082
10085 10086 10101
10107
10110
10111 10126
10132
10135 10136 10151
10157 10160 10161 10176
Modbus Address
10010 10025
No.of Byte
30 12
Data Type
free string
10031
6
string
10034
2
word
10035 10050
10056
10059
30
free
12 string
6
string
2
word
10060 10075
30
free
12 string
10081
6
string
10084
2
word
10085 10100
30
free
12 string
10106 10109
6
string
2
word
10110 10125
10131
30
free
12 string
6
string
10134
2
word
10135 10150
30
free
12 string
10156
6
string
10159
10160 10175
2
word
30
free
12 string
Description
A1a future use A1b Value Name long A1b Value Name short A1b Value Resolution
A1b future use A1c Value Name long A1c Value Name short A1c Value Resolution
A1c future use A1d Value Name long A1d Value Name short A1d Value Resolution
A1d future use A1e Value Name long A1e Value Name short A1e Value Resolution
A1e future use A1f Value Name long A1f Value Name short A1f Value Resolution
A1f future use A1g Value Name long A1g Value Name short A1g Value Resolution
A1g future use A1h Value Name long
Default Setting
0 0
0
0
0 0
0
0
0 0
0
0
0 0
0
0
0 0
0
0
0 0
0
0
0 0
Read Write
R R
R
R
R R
R
R
R R
R
R
R R
R
R
R R
R
R
R R
R
R
R R
Comment
string max. 10 character
string max. 3 character 0 … 5
string max. 10 character
string max. 3 character 0 … 5
string max. 10 character
string max. 3 character 0 … 5
string max. 10 character
string max. 3 character 0 … 5
string max. 10 character
string max. 3 character 0..5
string max. 10 character
string max. 3 character 0 … 5
string max. 10 character
25 | 32
METPOINT®BDL Compact
Daisychain setup
Modbus Register
10182
10185
10186 10201 10401 10601 10801 11001 11201 11401 11601 11801 12001 12201 12401
12601 12801 13001
Modbus No.of Data Address Byte Type
10181
6
string
10184
2
word
10185
30
free
10200 8*25 xxx
10400 825 xxx 10600 825 xxx
10800 8*25 xxx
11000 8*25 xxx
11200 8*25 xxx
11400 825 xxx 11600 825 xxx
11800 8*25 xxx
12000 8*25 xxx
12200 8*25 xxx
12400 825 xxx 12600 825 xxx
12800 8*25 xxx
13000 8*25 xxx
Description
A1h Value Name short A1h Value Resolution A1h future use Channel A2 Channel A3
Channel A4 Channel B1 Channel B2 Channel B3 Channel B4 Channel C1 Channel C2
Channel C3 Channel C4 Channel V1 Channel V2 Channel V3 Channel V4
Default Setting
0
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Read Write
R
R
Comment
string max. 3 character 0 … 5
R R similar to channel A1 R similar to channel A1 R similar to channel A1 R similar to channel A1 R similar to channel A1 R similar to channel A1 R similar to channel A1 R similar to channel A1 R similar to channel A1 R similar to channel A1 R similar to channel A1 R similar to channel A1 R similar to channel A1 R similar to channel A1 R similar to channel A1
8.8 Dataformattest
Modbus Register
64001
Modbus No.of Data Address Byte Type
64000
2
Dword
64003
64002
2
float
Description
1000000 1000000.0
Default Read Setting Write
x
R
x
R
Comment
format test for Dword
format test for float
8.9 DataBitdescription
*1)
DataValue
Format (Dword / Float) depends on Value Description Bit 15
see below *5)
Position of Dezimal Point depends on Value Descrition Bit 14 … 12 see below *5)
26 | 32
Daisychain setup
METPOINT®BDL Compact
*2)
Data status
Write1tothesebits Bit
clears Status
Bit
Bit
Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit
*3)
SensorType
Bit
Bit
15
Sensor changed
14
Sensor setting changed
13
Sensor Alarm settings
changed
12
Sensor name changed
11
Lower Alarm active
10
Lower Warning active
9
Upper Alarm active
8
Upper Warning active
7
tbd
6
Channel Error
5
Value Error
4
out of range
3
Stopped
2
UVP status
1
OCP status
0
Channel Disconnected
15 … 8 7 … 0
Sensor Basic type Sensor Subtype
different sensor mayor parameter changed Alarm settings changed
minor change
Value status Value status Value status Value status Value status Value status
Value status Value status
0 … 255 0 = no sensor 0 … 255
*4)
ChannelName
Name coding in UTF8 (max. 24 Byte)
*5)
Valuedescription
Bit
15
1 = Dword , 0 = float
0,1
Bit
14 … 12 position of dezimal point
0 … 7
Bit
11 … 7
index of value name
0 … 31
Bit
6 … 0
index of unit name
0 … 127 0 = value not used
*6)
AlarmChannel/Value
Bit
11
Bit
10
Bit
9
Bit
8
Bit
7
Bit
6 … 4
Bit
3 … 0
lower Alarm used lower Warning used upper Alarm used upper Warning used Alarm used (valid) Value Nr Channel
0 … 7 0 … 11
Alarm settings used
27 | 32
METPOINT®BDL Compact
*7)
AlarmRelias
Bit
15
Bit
14
Bit
13
Bit
12
Bit
11
Bit
10
Bit
9
Bit
8
Bit
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit
1
Bit
0
Lower alarm Relais 2 used Lower alarm Relais 1 used
Lower warning Relais 2 used Lower warning Relais 1 used
Upper alarm Relais 2 used Upper alarm Relais 1 used
Upper warning Relais 2 used Upper warning Relais 1 used
Daisychain setup
8.10 UserUnits
Modbus Modbus No.of Register Address Byte
14001
14000
10
Data Type
string
14009
14008
10
string
14017
14016
10
string
14025
14024
10
string
14033
14032
10
string
14041
14040
10
string
14049
14048
10
string
14057
14056
10
string
14065
14064
10
string
14073
14072
10
string
14081
14080
10
string
Description
Unit Name 1 Unit Name 2 Unit Name 3 Unit Name 4 Unit Name 5 Unit Name 6 Unit
Name 7 Unit Name 8 Unit Name 9 Unit Name 10 Unit Name 11
Default Setting
°C °F %RH °Ctd °Ftd mg/kg mg/m³ g/kg g/m³ m/s Ft/min
Read Write
R R R R R R R R R R R
Comment
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
28 | 32
Daisychain setup
METPOINT®BDL Compact
Modbus Modbus No.of Register Address Byte
14089
14088
10
Data Type
string
14097
14096
10
string
14105
14104
10
string
14113
14112
10
string
14121
12120
10
string
14129
14128
10
string
14137
14136
10
string
14145
14144
10
string
14153
14152
10
string
14161
14160
10
string
14169
14168
10
string
14177
14176
10
string
14185
14184
10
string
14193
14192
10
string
14201
14200
10
string
14209
14208
10
string
14217
14216
10
string
14225
14224
10
string
14233
14232
10
string
14241
14240
10
string
14249
14248
10
string
14257
14256
10
string
14265
14264
10
string
Description
Unit Name 12 Unit Name 13 Unit Name 14 Unit Name 15 Unit Name 16 Unit Name 17
Unit Name 18 Unit Name 19 Unit Name 20 Unit Name 21 Unit Name 22 Unit Name 23
Unit Name 24 Unit Name 25 Unit Name 26 Unit Name 27 Unit Name 28 Unit Name 29
Unit Name 30 Unit Name 31 Unit Name 32 Unit Name 33 Unit Name 34
Default Setting
Nm/s Nft/min
m³/h m³/min ltr/min
ltr/s cfm Nm³/h Nm³/min Nl/min Nl/min Ncfm m³ ltr cf Nm³ Nltr Ncf ppm atm°C
atm°F pa hpa
Read Write
R R R R R R R R R R R R R R R R R R R R R R R
Comment
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
29 | 32
METPOINT®BDL Compact
Daisychain setup
Modbus Modbus No.of Register Address Byte
14273
14272
10
Data Type
string
14281 14289 14297
14280
10
14288
10
14296
10
string string string
14305
14304
10
string
14313
14312
10
string
14321 14329 14337
14320
10
14328
10
14336
10
string string string
14345
14344
10
string
14353 14361 14369 14377
14352
10
14360
10
14368
10
14376
10
string string string string
14385
14384
10
string
14393
14392
10
string
14401
14400
10
string
14409
14408
10
string
14417
14416
10
string
14425
14424
10
string
14433
14432
10
string
14441
14440
10
string
14449
14448
10
string
Description
Unit Name 35 Unit Name 36 Unit Name 37 Unit Name 38 Unit Name 39 Unit Name 40
Unit Name 41 Unit Name 42 Unit Name 43 Unit Name 44 Unit Name 45 Unit Name 46
Unit Name 47 Unit Name 48 Unit Name 49 Unit Name 50 Unit Name 51 Unit Name 52
Unit Name 53 Unit Name 54 Unit Name 55 Unit Name 56 Unit Name 57
Default Setting
kpa Mpa mbar bar psi mV
V V kV mA A kg/s kg Ø m³/h Ø l/h Ø kg/h Ø cf/h kg/h kg/min Hz % kW
Read Write
R R R R R R R R R R R R R R R R R R R R R R R
Comment
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
30 | 32
Daisychain setup
METPOINT®BDL Compact
Modbus Modbus No.of Register Address Byte
14457
14456
10
Data Type
string
14465
14464
10
string
14473
14472
10
string
14481
14480
10
string
14489
14488
10
string
14497
14496
10
string
15505
15504
10
string
Description
Unit Name 58 Unit Name 59 Unit Name 60 Unit Name 61 Unit Name 62 Unit Name 63
Unit Name 64
Default Setting
kWh PCS kVA kVAr
cts/m³
Read Write
R R R R R R R
Comment
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
UTF8 string (max. 10 character)
9. Appendix
9.1 APPENDIXA-Exceptioncodes
The BDL Modbus uses the following exception codes when responding to the client
ExceptionCode
Exceptionname
0x01
Illegal function
0x02
Illegal data address
0x03
Illegal data value
0x04
server device failure
0x05 0x06
Acknowledge server device busy
31 | 32
BEKO TECHNOLOGIES GmbH
Im Taubental 7 D – 41468 Neuss Tel. +49 2131 988 0 Fax +49 2131 988 900 info
@beko-technologies.com service-eu@beko-technologies.com
DE
BEKO TECHNOLOGIES LTD.
Unit 11-12 Moons Park Burnt Meadow Road North Moons Moat Redditch, Worcs, B98
9PA Tel. +44 1527 575 778 info@beko-technologies.co.uk
GB
BEKO TECHNOLOGIES S.à.r.l.
Zone Industrielle 1 Rue des Frères Rémy F – 57200 Sarreguemines Tél. +33 387
283 800 info@beko-technologies.fr service@beko-technologies.fr
FR
BEKO TECHNOLOGIES B.V.
Veenen 12 NL – 4703 RB Roosendaal Tel. +31 165 320 300 benelux@beko-
technologies.com service-bnl@beko-technologies.com
NL
BEKO TECHNOLOGIES (Shanghai) Co. Ltd.
Rm.715 Building C, VANTONE Center
No.333 Suhong Rd.Minhang District
201106 Shanghai
Tel. +86 (21) 50815885
info.cn@beko-technologies.cn
service1@beko.cn
CN
BEKO TECHNOLOGIES s.r.o.
Na Pankraci 58 CZ – 140 00 Praha 4 Tel. +420 24 14 14 717 /
+420 24 14 09 333 info@beko-technologies.cz
CZ
BEKO Tecnológica España S.L.
Torruella i Urpina 37-42, nave 6 E – 08758 Cervelló Tel. +34 93 632 76 68
Mobil +34 610 780 639 info.es@beko-technologies.es
ES
BEKO TECHNOLOGIES LIMITED
Room 2608B, Skyline Tower, No. 39 Wang Kwong Road Kwoloon Bay Kwoloon, Hong
Kong Tel. +852 2321 0192 Raymond.Low@beko-technologies.com
HK
BEKO TECHNOLOGIES INDIA Pvt. Ltd.
Plot No.43/1 CIEEP Gandhi Nagar
Balanagar Hyderabad
IN – 500 037
Tel. +91 40 23080275 /
+91 40 23081107
Madhusudan.Masur@bekoindia.com service@bekoindia.com
IN
BEKO TECHNOLOGIES S.r.l
Via Peano 86/88
I – 10040 Leinì (TO)
Tel. +39 011 4500 576
Fax +39 0114 500 578
info.it@beko-technologies.com
service.it@beko-technologies.com
IT
BEKO TECHNOLOGIES K.K
KEIHIN THINK Building 8 Floor
1-1 Minamiwatarida-machi
Kawasaki-ku, Kawasaki-shi
JP – 210-0855
Tel. +81 44 328 76 01
info@beko-technologies.jp
JP
BEKO TECHNOLOGIES Sp. z o.o.
ul. Paska 73 PL – 00-834 Warszawa Tel. +48 22 314 75 40 info.pl@beko-
technologies.pl
PL
BEKO TECHNOLOGIES S. de R.L. de C.
BEKO Technologies, S de R.L. de C.V. Blvd. Vito Alessio Robles 4602 Bodega 10
Zona Industrial
Saltillo, Coahuila, 25107
Mexico
Tel. +52(844) 218-1979 informacion@beko-technologies.com
MX
BEKO TECHNOLOGIES, CORP.
900 Great Southwest Pkwy SW Atlanta, GA 30336 USA Tel. +1 404 924-6900
beko@bekousa.com
US
www.beko-technologies.com
References