SOSEN Innovation HL3K-P1EU Single Phase Hybrid Inverter User Manual
- September 9, 2024
- SOSEN INNOVATION
Table of Contents
HL3K-P1EU Single Phase Hybrid Inverter
“`html
Specifications:
-
Model: SSA-HL3K/5K-P1EU
-
Type: Single Phase Hybrid Inverter
-
Functions: Inverter, Solar Charger, Battery Charger
-
Waveform: Pure Sine Wave
-
Input Voltage Range: Configurable
-
Battery Charging Current: Configurable
-
Charger Priority: Configurable
-
Protection Features: Overload, Over Temperature, Short
Circuit -
Additional Features: Auto Restart, Cold Start Function, LCD
Display
Product Usage Instructions:
1. Installation
Follow the steps below for proper installation:
-
Unpack the unit and inspect for any damages.
-
Prepare the unit for installation by removing the bottom
cover. -
Mount the unit securely in a suitable location.
-
Connect the battery, AC input/output, and PV input following
the provided guidelines. -
Complete the final assembly ensuring all connections are
secure. -
Establish communication connections as needed.
2. Operation
To operate the inverter:
-
Power ON/OFF using the designated switch.
-
Utilize the operation and display panel for monitoring and
control. -
Adjust settings through the function setting operation on the
LCD display. -
Understand battery equalization and fault/alarm descriptions
for troubleshooting.
3. Basic System Architecture
The system includes:
- Solar Charger
- Battery Charger
- Inverter
- LCD Display with Function Buttons
Frequently Asked Questions (FAQ):
Q: What is the main function of this inverter?
A: The main functions of this inverter include providing
uninterruptible power support through inverter, solar charger, and
battery charger capabilities.
Q: Can this inverter power motor-type appliances?
A: Yes, this inverter can power all kinds of appliances
including motor-type appliances such as tube lights, fans,
refrigerators, and air conditioners.
“`
User Manual
Single Phase Hybrid Inverter
SSA-HL3K/5K-P1EU
Please read this manual before use and follow its guidance. Keep this manual
for future reference.
CONTENTS
1. Declaration
1
1
2. Safety Precautions
1
3. Product Introduction
2
3.1 Product Features
3
3.2 Basic System Architecture
3
3.3 Appearance
3
4. Installation
5
4.1 Unpacking and Inspection
5
4.2 Preparation
6
4.3 Mounting the Unit
6
4.4 Battery Connection
7
4.5 AC Input/Output Connection
8
4.6 PV Connection
9
4.7 Final Assembly
11
4.8 Communication Connection
11
5. Operation
11
5.1 Power ON/OFF
11
5.2 Operation and Display Panel
12
5.3 Function Setting Operation
19
5.4 Battery Equalization Description
38
5.5 Fault and Alarm Description
39
6. Trouble Shooting
42
7. Technical Data sheet
43
Appendix:Parallel Operation Guide
44
1. Parallel Operation
44
1.1 Single-phase parallel operation
44
1.2 Three-phase parallel operation
46
2. Connection Precautions
51
2.1 PV connection/Solar Panel Connection
51
2.2 Parallel board connection
51
3. Parallel Operation
51
3.1 Single-phase parallel
51
3.2 Parallel as three-phase system( the function is not open)
53
1 Declaration
· The information in this user manual is subject to change due to product
updates or other reasons. This guide cannot replace the product labels or the
safety precautions in the user manual unless otherwise specified. All
descriptions here are for guidance only. · Before installations, read through
the quick installation guide. For additional information, please see the user
manual. · All installations should be performed by trained and knowledgeable
technicians who are familiar with local standards and safety regulations. ·
Use insulating tools and wear personal protective equipment when operating the
equipment to ensure personal safety. Wear anti-static gloves, cloths, and
wrist strips when touching electron devices to protect the inverter from
damage. · Strictly follow the installation, operation, and configuration
instructions in this manual. The manufacturer shall not be liable for
equipment damage or personal injury if you do not follow the instructions. For
more warranty details, please visit our website.
2 Safety Instructions
WARNING: This chapter contains important safety and operating instructions.
Read and keep this manual for future reference. 1. Before using the unit read
all instructions and cautionary markings on the unit, the batteries and all
appropriate sections of this manual. 2. CAUTION-To reduce risk of injury,
charge only deep-cycle lead acid type rechargeable batteries. Other types of
batteries may burst, causing personal injury and damage. 3. Do not disassemble
the unit Take it to a qualified service center when service or repair is
required. Incorrect re-assembly may result in a risk of electric shock or
fire. 4. To reduce risk of electric shock, disconnect all wiring before
attempting any maintenance or cleaning. Turning off the unit will not reduce
this risk. 5. CAUTION-Only qualified personnel can install this device with
battery. 6. NEVER charge a frozen battery. 7. For optimum operation of this
inverter/charger, please follow required spec to select appropriate cable
size. It’s very important to correctly operate this inverter/charger. 8. Be
very cautious when working with metal tools on or around batteries.A potential
risk exists to drop a tool to spark or short circuit batteries or other
electrical parts and could cause an explosion. 9. Please strictly follow
installation procedure when you want to disconnect AC or DC terminals, Please
refer to INSTALLATION section of this manual for the details 10. One piece of
150Afuse is provided as over-current protection for the battery supply. 11
.GROUNDING INSTRUCTIONS -This inverter/ charger should be connected to a
permanent grounder wiring system. Be sure to comply with local requirements
and regulation to install this inverter. 12. NEVER cause AC output and DC
input short circuited. Do NOT connect to the mains when DC input short
circuits. 13. WARNING!!! Only qualified service persons are able to service
this device. If errors still persist after following troubleshooting table,
please send this inverter/charger back to local dealer or service center for
maintenance.
1
3 Introduction
This is a multi-function Inverter/charger, combining functions of inverter,
solar charger and battery charger to offer uninterruptible power support with
portable size. Its comprehensive LCD display offers user-configurable and
easy-accessible button operation such as battery charging current, AC/solar
charger priority, and acceptable input voltage based on different
applications.
3.1 Features
Pure sine wave inverter Configurable input voltage range for home appliances
and personal computers via LCD setting Configurable battery charging current
based on applications via LCD setting Configurable AC/Solar Charger priority
via LCD setting Compatible to mains voltage or generator power Auto restart
while AC is recovering Overload/Over temperature/short circuit protection
Smart battery charger design for optimized battery performance Cold start
function
3.2 Basic System Architecture
The following illustration shows basic application for this
inverter/charger.lt also includes following devices to have a complete running
system: Generator or Utility PV modules Consult with your system integrator
for other possible system architectures depending on your requirements. This
inverter can power all kinds of appliances in home or environment,including
motor-type appliances such as tube light, fan, refrigerator and air
conditioner.
2
3.3 Product Overview
3.3.1 LCD Screen Four Function Buttons:
Three Function Buttons:
3.3.3 Back Panel
3.3.2 Product size
3
1
Input Breaker
2
AC Input
3
AC Output
4
Parallel Connection
5
Battery Input
6
PV Input
7
Power ON/ OFF Switch
BMS
8 USB/WIFI Communication Port 9 RS232 Communication Port 10 BMS/RS485/CAN
Communication Port 11 Battery Terminal Positive 12 Fan 13 Battery Terminal
Negative 14 Solar Panel Input
4
4.2 Preparation
Before connecting all please take off bottom cover by removing two screws as
shown below.
1 Input Breaker 2 AC Input
3 AC Output 4 COM Port 5 USB Communication Port 6 Battery Input
7 PV Input 8 Power ON/ OFF Switch
9 Fan 10 Battery Terminal Positive 11 Battery Terminal Negative 12 Solar Panel
Input
4 Installation
4.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the
package is damaged.
You should have received the following items inside of package: The unit x 1
User manual 1
5
4.3 Mounting the Unit
Consider the following points before selecting where to install: Do not mount
the inverter on flammable construction materials. Mount on a solid surface
Install this inverter at eye level in order to allow the LCD
display to be read at all times. For proper air circulation to dissipate heat,
allow a clearance
of approx. 20 cm to the side and approx. 50 cm above and below the unit. The
ambient temperature should be between and to ensure optimal operation. The
recommended installation position is to be adhered to the wall vertically. Be
sure to keep other objects and surfaces as shown in the diagram to guarantee
sufficient heat dissipation and to have
enough space for removing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing three screws. ·1,2 Use the M6*80mm expansion
bolts. ·3 Use the M4 or M5
6
4.4 Battery Connection
CAUTION: For safety operation and regulation compliance,it’s requested to
install a separate DC over-current protector or disconnect device between
battery and inverter.It I may not be requested to have a disconnect device in
some applications, however, it’s still requested to over-current protection
installed. Please refer to typical amperage in below table as required fuse or
breaker size.
WARNING! All wiring must be performed by be qualified personnel. WARNING! Ifs very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable and terminal size as below.
Recommended battery cable and terminal size:
Model
Typical Battery Wire Size
Amperage Capacity
SSA-HL3K-P1EU 132A SSA-HL5K-P1EU 109A
100AH 200AH
200AH
14AWG 28AWG 12AWG 26AWG
Cable (mm2)
22 9 38 28
Ring Terminal
Dimensions
D(mm)
L(mm)
6.4
33.2
6.4
29.2
6.4
39.2
6.4
33.2
Torque Value
2~3Nm
2~3Nm
please follow below steps to implement battery connection: 1 .Assemble battery ring terminal based on recommended battery cable and terminal size.
SSA-HL3K-P1
SSA-HL5K-P1
7
2. Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: # 2 Pozi Screwdriver
WARNING: Shock Hazard Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector.be sure positive( + ) must be connected to positive( + ) and negative( – ) must be connected to negative(-).
4.5 AC Input Output Connection CAUTION!! Before connecting to AC input power source, please Install a separate AC breaker between inverter and AC input power source. This will ensure the Inverter can be disconnected during maintenance and fully protected from over current of AC input. The recommended spec of breaker is 32Afor SSA-HL3K-P1EU and 50A for SSA-HL5K-P1EU CAUTION!! There are two terminal blocks with “IN” and ” OUT” markings. Please do NOT misconnect input and output connectors. WARNING!! All wiring must be performed by qualified personnel. WARNING!! It’s very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below. Suggested cable requirement for AC wires
Model SSA-HL3K-P1EU SSA-HL5K-P1EU
Gauge 10AWG 8AWG
Torque Value 1.2~1.6 Nm 1.4~1.6 Nm
Please follow below steps to implement AC input/ output connection Before making AC input/output connection be sure to open DC protector or disconnecter first. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N3 mm.
8
3. Insert AC input wires according to polarities indicated on terminal block
and tighten the terminal screws. Be
sure to connect PE protective conductor( )first.
Ground(yellow-green) LLINE(brown or black NNeutral (blue)
PV Module Wire Connection Please follow below steps to implement PV module connection 1. Remove insulation sleeve 10 mm for positive and negative conductors. 2.Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool 3.Fix wire cover to the inverter with supplied screws as shown in below chart
WARNING: Be sure that AC power source is disconnected before attempting to
hard wire it to the unit.
4.Make sure the wires are securely connected CAUTION: Appliances such as air
conditioner are required at least 2-3 minutes to restart because it’s required
to have enough time to balance refrigerant gas inside of circuits. If a power
shortage occurs and recovers in short time, it will cause damage to your
connected appliances. To prevent this kind of damage, please check
manufacturer of air conditioner if it’s equipped with time-delay function
before installation. Otherwise, this inverter/ charger will trig overload
fault and cut off output to protect your appliance but sometimes it still
causes internal damage to the air conditioner.
4.6PV Connection PV Connection(Only apply for the model with solar charger)CAUTION:Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules. WARNING! All wiring must be performed by a qualified personnel. WARNING! It’s very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
Typical Amperage 30A
Gauge 12AWG
Torque Value 1.4~1.6Nm
PV module selection: When choosing the right PV module, be sure to first consider the following requirements:The open circuit voltage (Voc) of the PY modules does not exceed the maximum PV array open circuit voltage of the inverter. The maximum supply voltage of the PV modules should be close to the optimal PV access voltage range of the inverter for best performance. If one PV module cannot meet this requirement, it is necessary to connect multiple PV modules in series.
9
4. Check correct polarity of wire from PV modules and PV input connectors.
Then,connect positive pole( +) of connection wire to positive pole( +) of PV
input connector. Connect negative pole (-)of connection wire to negative
pole(-) of PV input connector. Screw two wires tightly in clockwise direction.
Recommended tool: 4mm blade screwdriver.
10
4.7 Final Assembly
After connecting all wirings, please put bottom cover back by screwing two
screws as shown below.
4.8 Communication Connection 1.Please use supplied communication cable to
connect to inverter and PC. Insert bundled CD into a compute and follow on-
screen instruction to install the monitoring software. For the detailed
software operation, please check user manual of software inside of CD. 2.Wi-Fi
cloud communication(option): please use supplied communication cable to
connect to inverter and Wi-Fi module. Download APP and installed from APP
store, and Refer to “Wi-Fi Plug Quick Installation Guideline” to set up
network and registering. The inverter status would be shown by mobile phone
APP or web page of computer. 3.GPRS cloud communication(option): please use
supplied communication cable to connect to inverter and GPRS module, and then
applied external to GPRS module. Download APP and installed from APP store,
and Refer to” GPRS RTU Quick Installation Guideline” to set up network and
registering. The inverter status would be shown by mobile phone APP or web
page of computer.
5 Operation
5.1 Power ON/OFF Once the unit has been properly installed and the batteries
are connected well,simply press On/Off switch (located on the button of the
case)to turn on the unit.
11
5.1.1 Steps to start up Connect the battery that meets the requirements
(battery voltage needs to beyond 23V) or AC (AC needs to confirm the suitable
input range depend on the output mode), then you can start up the inverter. A
Mains power on Connect to normal AC power, press the switch, the system will
automatically turn on. If you set AC output power priority, after waiting for
a period of time, the panel will display AC mode that represents turn on the
machine successfully, then will enter the AC mode. When the normal mains power
is connected and press the power-on button then the system will automatically
power on. If it is set as AC output priority, after a period of time, the
panel will display the AC mode to indicate that the power-on is complete and
enter the AC mode. Battery boot Connect to battery, press the power-on button
to establish a working power source. The system will automatically turn on,
after waiting for a period of time, the panel will display battery mode that
represents turn on the machine successfully, then will enter the battery mode.
5.1.2 Shutdown steps When the system is in battery mode or AC mode output,
press the switch again, then the system will be turned off.
5.2 Operation and Display Panel
Four Function Buttons: The operation and display panel, shown in below chart,
is on the front panel of the inverter. It includes three indicators,four
function buttons and a LCD display, indicating the operating status and
input/output power information.
Three Function Buttons: The operation and display panel, shown in below chart,
is on the front panel of the inverter. It includes four indicators, three
function buttons and a LCD display, indicating the operating status and
input/output power information.
12
5.2.1 Buttons function Buttons
Function settings /ENTER Page turning / inquiry button
UP/DOWN
ESC
5.2.2 LED indicator functions Three Indicators:
Descriptions Function settings: Press the ENTER button on the display page for
more than 2 seconds to enter the function setting page. After entering, press
the ENTER button to turn the page and select the interface to be set.
Page turning: Press UP/DOWN on any page to turn the pages.
After setting up a single item, press ESC and then press UP/DOWN to select
other settings. Confirm and save settings: On the function settings page,
press ESC for 2 seconds, and then go back to the main interface and set to
save.
LED Indicator
AC/ INV CHG
Green Green
FAULT
Red
Messages Solid On Output is powered by utility in Line mode. Flashing Output is powered by battery or PV in battery mode. Solid On Battery is fully charged. Flashing Battery is charging. Solid On Fault occurs in the inverter. Flashing Warning condition occurs in the inverter.
Four Indicators:
Indicator lights LED-Y LED-Y LED-Y
LED-R
Name
Input light (Green)
Invert (Yellow)
Battery (Yellow)
Warning (Red)
Descriptions On: the AC is normal and enters the AC to work Flash: the AC is normal, but does not enter the AC to work Off: the AC is abnormal On: machine working in battery mode output Off: other states On: the battery is float charging Flash: battery charging off at constant voltage Off: other states On: inverter fault Flash: inverter has alarm Off: The inverter is normal
13
5.2.3 Inverter working state table corresponding to indicator lamp
Warning buzzer
Descriptions
Long beeping, continuous for 10 seconds then stop. Failure Mode
Stop after beeping for 3 seconds
Loss or recovery of PV/input voltage The main switch is on or off
Beep per second, continuous for 1 min then stop
All other alarms (battery low voltage alarm will only
beep in battery mode.)
5.2.4 Checking Parameter Operation Under normal circumstances, there are ten pages in the display. Press the query button UP/DOWN to draw a page for the display, and display information such as input-output voltage input-output rate, battery, PV electricity and electricity, negative and component versions, etc. If there is an alarm, a page of alarm information will be displayed, and if the inverter fails, a page of trouble code will be displayed. By default, the main panel displays the fault information. When the transformer has no fault or fault, the main page displays the voltage and rate information by default. Press UP/DOWN for more than 1 second, and LCD will enter polling mode display: automatically turn the page of display every 2 seconds, and long press UP/DOWN key again to exit polling mode.
Display page 1 (main display page): display the inverter input and output voltage, as shown in Figure 1-1.
Display Page 2: Display the input and output frequency of the inverter, as shown in Figure 1-2.
14
Display page 3: battery information, showing battery voltage and battery capacity and charging current, as shown in Figure 1-3.
Display page 7: Output Information shows the output voltage and output power, as shown in Figure 1-7
Display page 4: PV info.display PV voltage and PV charging amps, as shown in Figure1-4.
Display page 8: Output Information displays output voltage and load percentage, as shown in Figure 1-8.
Display page 5: PV info, display PV voltage and PV charging wattage, show as 1-5.
Display page 9: Software version displays the inverter system software version, as shown in Figure 1-9( Software Version VER 01)
Display page 6: Output Information shows the output voltage and output power, as shown in Figure 1-6.
Display page 10: The left side of the page information displays the total power generation, and the right side displays the current power generation, as shown in Figure 1-10,
15
16
Display page 11: Display information. n single unit mode, the LCD shows status of single unit mode both on the left and right sides.in parallel connect mode, the LCD shows the master slave relation on the left, shows the parallel status on the right. If parallel connect as three phases use, the LCD shows the phase position on the left shows the status on the right. Shown in Figure 1-12 (applicable to the inverter with parallel function)
Display page 15: lithium battery capacity; the upper left display is the rated capacity; the upper right display is the current capacity. When the BMS communication fails, the upper left and right upper displays are flashing ERR.
Display page 12: Lithium battery networking status; when the upper right display is a constant SIG, the battery pack is running in a single group; when it is displayed as a PAR constant, the battery pack is running in multiple series and parallel; when the display is PAR flashing, the battery pack is being established Multiple series and parallel state.
Display page 16: Lithium battery constant voltage point; the upper left display is the fixed letter CV; the upper right display is the BMS constant voltage charging point. When the BMS communication fails, the upper right displays a flashing ERR.
Display page 13: lithium battery voltage and current information; the upper left display is BMS battery voltage information; the upper right display is BMS battery current information. When the BMS communication fails, the upper left and right upper displays are flashing ERR.
Display page 17: Lithium battery failure alarm information; the upper left display is BMS alarm information; the upper right display is BMS failure information. When the BMS communication fails, the upper left and right upper displays are flashing ERR.
Display page 14: Lithium battery temperature, SOC; the upper left display is BMS temperature information; the upper right display is BMS SOC information. When the BMS communication fails, the upper left and right upper displays are flashing ERR.
17
18
5.3 Function setting operation Function setting operation:
The page for setting the exit function and setting as bellow:
· Long press “ENTER” button for more than 2 seconds, enter into function
setting mode. Press “Enter”
button to choose function, turn the page to you need to set, the corresponding
indicator will flash.
· Press ” Enter” button again, enter the function setting, you will see the
word of function you choose
lighting, on the left of word will occur numerical flashing, then you can
press” UP/DOWN ” button to use.
· After finish setting, press the enter button again, the data will be on
instead of flashing.
Long press ” ESC ” button for more than 2 seconds, the function will complete
setting. Return to function
setting, then back to main page. (If you don’t exit manually, after 30
seconds, it will be back to main page
automatically).
5.3.1 Output Voltage (OPU)
5.3.2 Output frequency Output frequency setting, the default value is 50Hz.
Function description: 50Hz or 60Hz can be adjusted, default value is 50Hz.
Setting conditions: All states can be set. In battery mode, the setting will
take effect when the Inverter is restarted next time; in mains mode, it will
take effect immediately. After the setting is completed, after switching back
to battery mode, 5.3.3 Output priority settings
· The default output voltage is 230V, 208V, 220V, 230V, 240V can be set, all
working conditions can be set,
and it will take effect immediately.
· Press the function setting key “ENTER” key for more than 2 seconds to enter
the function setting page,
press the query key “UP/DOWN” key for 0.1 to 2 seconds to select the function,
after turning the page to the output voltage PU setting page, the word OPU
flashes.
· Press the “ENTER” key for 0.1 to 2 seconds to enter the setting page of the
output voltage OPU. At this
time, the word OPU is long on, and the value flashes to the right of the word
OPU. Press the query key “UP/DOWN” key for 0.1 to 2 seconds to select
different output voltage values, the available voltage values are 208V, 220V,
230V, 240V. By default, the output voltage is 230V, and the settings are saved
in real time.
· After turning the page to the desired output voltage value, press the
“ENTER” key for 0.1-2 seconds, the
output voltage PU setting is completed, and the value on the right side of the
OPU will be long on and no longer flashing.
· Press the “ESC” key for more than 0.1 to 2 seconds, the function will be set
successfully, exit the function
setting page, and return to the main display page (or do not operate, and
automatically jump back to the main display page after waiting for up to 30S).
Note:When the output voltage is set to 208V, the output needs to be derated to
90%.
19
Function description: Set the inverter output priority. Setting conditions:
All states can be set, and they will take effect immediately after setting.
Note: There are three options for output priority, the default is GRD: mains
output priority; the second is PU(PV): photovoltaic output priority; the third
is PBG: PV first, battery second, mains third output: 5.3.4 Output Mode
Settings (MOD)
20
Setting conditions: All states can be set and take effect immediately.
Explanation: There are two options for AC output mode, the default is APP:
Appliance which is used for home appliances; the second is UPS mode, which is
used for computers and other equipment. The switching time is typically 10ms.
5.3.5 Charging priority settings (CHP)
Function description: Set the inverter charging priority. Setting conditions:
All states can be set and take effect immediately. Explanation: There are four
options for charging priority, the default is PNG (PV and Grid): PV and Grid
are charged at the same time; the second is OPV (Only PV): only photovoltaic
charging the third is GRD (Grid): mains charging priority The fourth is PV PV
priority charging. 5.3.6 Mains charging current (RCC)
Function description: Set the maximum charging current of the inverter mains.
Setting conditions: All states can be set. Explanation: RCC: Grid Charge
Current, the default setting of the maximum charging current of the mains is
40A, and the setting range is [2,120A] (for SSA-HL3K-P1EU Version) RCC: Grid
Charge Current, the default setting of the maximum charging current of the
mains is 30A, and the setting range is [1,80A] (for SSA-HL5K-P1EU Version)
21
5.3.7 Maximum charging current (MCC)
Function description: Set the maximum charging current value of the inverter.
Setting conditions: All states can be set. Explanation: MCC: Maximum Charge
Current, the maximum charging current refers to the maximum value of the PV
and mains charging current. HL3K-P1EU Version is
2/10/20/30/40/50/60/70/80/90/100/110/120A optional ; HL5K-P1EU version is
2/10/20/30/40/50/60/70/80A optional ; 5. 3. 8 Menu Front (MDF)
Function description: Return to the main interface settings. Setting
conditions: All states can be set. Explanation: The default setting is ON. In
the function setting operation, when it is set to ON, if the page is not in
the first interface (P1) at this time, it will return to the first interface
after 1 minute; if it is set to OFF, if the page is not in the first interface
(P1) at this time, the LCD will Always stay on this interface. 5.3.9 Overload
restart setting (LrS)
Function description: Overload restart setting. Setting conditions: All states
can be set. Explanation: Overload restart is set to ON by default.
22
5.3.10 Over temperature restart setting (TrS)
The default setting is OFF, the function is not turned on; when it is set to ON, in battery mode, if the load is lower than 25W, the system will temporarily stop the output, and then continue to output. If the load is higher than 35W, the system will resume continuous normal output. 5.3.13 Overload convert to bypass setting (OLG)
Function description: Over-temperature restart settings. Setting conditions:
All states can be set. Explanation: The default setting for over-temperature
restart is ON. 5.3.11 Main input power failure alarm setting (MIP)
Function description: Mains or PV loss alarm long beep setting Setting
conditions: All states can be set, the default is ON, and the mains or PV loss
alarm will beep for a while. Can be set to OFF. (All modes can be set)
Explanation: MIP:Main input cut warning The default setting is ON, after the
main input detection is lost, the buzzer will sound for 3s; when it is set to
OFF, after the main input is lost, the buzzer will not sound constantly.
5.3.12 Power Saving Mode (PWS)
Function description: Set whether the inverter enables low power consumption
mode (energy saving mode). Setting conditions: All states can be set.
Explanation: PWS: Power Saving
23
Function description: When overload in the battery mode, set whether to switch
to the mains mode (bypass mode) immediately. Setting conditions: All states
can be set. Explanation: OLG:Over load to Bypass The default setting is OFF,
the function is not enabled; when it is set to ON, under the condition of PV
priority output with load, if overloaded, the system will immediately transfer
to bypass (mains output, namely bypass mode). 5.3.14 Silent mode setting
Function description: Set whether the buzzer beeps or not. Setting conditions:
All states can be set. Explanation: MUE Mute The default setting is OFF, and
the function is not turned on; when it is set to ON, the buzzer does not sound
under any circumstances, such as alarms, faults, etc. All modes can be set and
function normally, pictures cannot be displayed. 5.3.15 Battery mode to mains
mode voltage point
24
Function description: When the battery and mains exists at the same time, the
battery will be transferred to the mains when it is discharged to a certain
voltage to ensure that the battery will not be empty. Setting conditions: All
states can be set, and the output priority should be set in PV or PBG modes.
Explanation: BTG: Back To Grid When the battery definition mode is CUS
(customer set type) mode: The default setting of SSA-HL3K-P1EU model is 23v,
and the settable range is [22,26] The default setting of SSA-HL5K-P1EU model
is 46V, and the settable range is[44,52] When the battery definition mode is
AGM (lead-acid battery type), FLD (water injection battery type)mode: SSA-
HL3K-P1EU model default setting is 23V, and the settable range is [22, 26].
The default setting SSA-HL5K-P1EU model is 46V, and the settable range is [44,
52] When the battery definition mode is LIB (lithium battery type) mode: The
default setting of SSA-HL3K-P1EU model is 23.8v, and the settable range is
[20,25] The default setting of SSA-HL5K-P1EU model is 47.6V, and the settable
range is [40,50] 5.3.16 Switch back to battery mode voltage point(BTB)
Figure 1-33 Setting of battery voltage point when mains switch back to battery
mode
Function description: After the battery is turned off at low voltage, it needs
to reach a certain battery voltage value before it can be restarted in battery
mode. Setting conditions: All states can be set. Explanation: BTB: Back To
Battery SSA-HL3K-P1EU model is set to 26V by default SSA-HL5K-P1EU model is
set to 52V by default. When set to FUL, the battery will charge until it is
fully charged before restarting in battery mode. When the battery definition
mode is CUS (customer set type) mode: The default setting of SSA-HL3K-P1EU
model is 26V, and the settable range is [24, 29] (when the setting value Vbtb>
26V, the voltage point of switching back to battery mode remains at26V) , and
the output priority is set to photovoltaic (PV priority output Or photovoltaic
battery mains PBG output if it is not in battery mode at this time, if the
battery voltage is higher than 26V, the system will switch back to battery
mode. The default setting of SSA-HL5K-P1EU model is 54V, and the settable
range is [48,58] (the logic is the same as above) When the battery definition
mode is AGM (lead-acid battery type), FLD(water injection battery type)mode:
SSA-HL3K-P1EU model default Set to 26v, the settable range is [24, 29] (the
logic is the same as above). SSA-HL5K-P1EU model default setting is 52V, the
settable range is (48, 58] (the logic is the same as above)
25
The battery definition mode is LIB (lithium battery type) mode: The default
setting of SSA-HL3K-P1EU model is 27 .2V, and the settable range is [23,29]
the logic is the same as above). The default setting of SSA-HL5K-P1EU model is
54.4V, and the settable range is [46,58] the logic is the same as above).
5.3.17 Battery mode setting
Figure 1-34 Battery mode setting page Function description: battery type
setting function Setting conditions:All states can be set.Explanation:
BAT:Battery Type Four battery type settings: the default setting is AGM (lead-
acid battery); the second is FLD (water injection battery); the third is LIB
(lithium battery); the fourth is Cus (customer setting type). 5.3.18 Battery
low voltage point
26
Function description: Low voltage alarm point setting. Setting conditions: All
states can be set. Explanation: bAL: battery Low The battery definition mode
cannot be set when the battery definition mode is AGM (lead-acid battery type)
or FLD (water-filled battery type) mode. SSA-HL3K-P1EU model is set to 21.6V
by default. SSA-HL5K-P1EU model is set to 44V by default. The battery low
voltage point can be modified when the battery type is set to CUS (customer
set type) SSA-HL3K-P1EU model is set to 22v by default, and the settable range
is [21,27] SSA-HL5K-P1EU model is set to 44V by default, and the settable
range is [42,54] When the battery type is set to LlB (lithium battery type),
the battery low voltage point can be modified. The default setting of SSA-
HL3K-P1EU model is 23.8V, the settable range is [20.6, 25] The default setting
of SSA-HL5K-P1EU model is 47.6V, and the settable range is [41.2, 50] 5.3.19
Battery low voltage cut off point
Figure 1-36 Battery low voltage cut off point setting page
Function description: Battery low voltage shutdown point setting function.
Setting conditions: All states can be set. Explanation: bAU: battery Under The
battery definition mode cannot be set when the battery definition mode is AGM
(lead-acid battery type) or FLD (water-filled battery type) mode. SSA-HL3K-
P1EU model is set to 21V by default. SSA-HL5K-P1EU model is set to 42V by
default. The battery shutdown point can be modified when the battery type is
set to CUS (customer set type)The default setting of SSA-HL3K-P1EU model is
21V, and the setting range is [20.24] The default setting of SSA-HL5K-P1EU is
42V, and the settable range is [40,48] The battery shutdown point can be
modified when the battery type is set to LlB (lithium battery type) SSA-HL3K-
P1EU model is set to 23V by default, and the settable range is [20,24] The
default setting of SSA-HL5K-P1EU model is 46V, and the setting range is [40,
48] 27
5.3.20 Constant voltage mode voltage point setting (bCV)
Figure 1-37 Constant voltage mode voltage point setting page
Function description: Constant voltage point setting function Setting
conditions: All states can be set Explanation: bCV : battery Constant Voltage
The battery definition mode cannot be set when the battery definition mode is
AGM (lead-acid battery type) or FLD (water-filled battery type) mode The
default setting of SSA-HL3K-P1EU model is 28.2V (AGM) 29 (FLD) The default
setting of SSA-HL5K-P1EU mode is 56.4V (AGM),58V(FLD) The constant voltage
charging point can be modified when the battery type is set to CUS (customer
set type). The default setting of SSA-HL3K-P1EU model is 28.2, and the setting
range is [24,29] The constant voltage point voltage needs to be higher than
the floating point voltage. The default setting of SSA-HL5K-P1EU model is
56.4, and the settable range is [48,60] The constant voltage point voltage
needs to be higher than the floating point voltage. The constant voltage
charging point can be modified when the battery type is set to LlB (lithium
battery type). The default setting of SSA-HL3K-P1EU model is 28.2, and the
setting range is [25,29] The constant voltage point voltage needs to be higher
than the floating point voltage. The default setting of SSA-HL5K-P1EU model is
56.4, and the setting range is [48,60] The constant voltage point voltage
needs to be higher than the floating point voltage.
5.3.21 Floating charge mode voltage point setting (bFL)
Function description: Float voltage point setting function Setting conditions:
All states can be set. Explanation: bFL : battery Float
28
The battery definition mode cannot be set when the battery definition mode is
AGM (lead-acid battery type) or FLD (water-filled battery type) mode The
default setting of SSA-HL3K-P1EU model is 27V The default setting of SSA-HL5K-
P1EU model is 54V Set the battery type to cUS (customer set type) to modify
the battery floating point. The default setting of SSA-HL3K-P1EU model is
27.6V, and the setting range is [26.6, 27.8] The constant voltage point
voltage needs to be higher than the floating point voltage. The default
setting of SSA-HL5K-P1EU model is 54V, and the setting range is [48, 60] The
constant voltage point voltage needs to be higher than the floating point
voltage. The constant voltage charging point can be modified when the battery
type is set to LlB (lithium battery type). The default setting of SSA-HL3K-
P1EU model is 27 .6V, and the setting range is [24,28] The constant voltage
point voltage needs to be higher than the floating point voltage. The default
setting of SSA-HL5K-P1EU model is 55.2V, and the settable range is [50,58] The
constant voltage point voltage needs to be higher than the floating point
voltage.
5.3.22 Mains low voltage point setting (LLV)
5.3.23 Mains high voltage protecting point setting (LHV)
Figure 1-40 Mains high voltage protecting point setting page in APP mode
Function description: Set the mains high voltage protection point.Setting
conditions: The inverter is in APP mode, and all states can be
set.Explanation: LHV:Line High Voltage In inverter mode (output mode: MOD
needs to be set to APP), the mains high voltage point setting. the default
setting is 264V, and the setting range is [264,280]. 5.3.24 Low power
discharging time setting (LWD)
Figure 1-39 Mains low voltage point setting page in APP mode
Function description: Set the mains low voltage protection point. Setting
conditions: The inverter is in APP and UPS mode, all states can be set
Explanation: LLV: Line Low Voltage In inverter mode (output mode: MOD needs to
be set to APP), the low-voltage point of mains is set. the default setting is
154V, and the setting range is [90, 154). (Output mode: MOD needs to be set to
UPS), the low-voltage point setting of mains, the default setting is 185V, and
the setting range is [170,200].
29
Figure 1-41 Low power discharging time setting page Function description: Low
power discharge protection function, when in battery mode, under a low load,
the discharge of unlimited time will make the battery empty and affect the
battery life.When the inverter is in the low power discharge setting time, the
low voltage shutdown point of the SSA-HL3K-P1EU model battery will increase to
22V.SSA-HL5K-P1EU model battery low voltage shutdown point will be raised to
44V. Setting conditions: All states of the inverter can be set in APP mode
Explanation: LWD : Low Watt Discharge In inverter mode, the low power
discharge time setting, the default is 8 (8 hours), the setting range is[1,8]
In battery mode, after the continuous discharge time exceeds 8 hours and the
battery shutdown point has not been reached, the battery voltage shutdown
point will be modified to 11V number of battery cells, and the system will
alarm for 1 minute when the battery continues to discharge to1V number of
battery cells.Then shut down again. When the battery voltage exceeds 13.2V*
the number of battery cells exceeds 30s, the battery discharge time will be
reset.
30
5.3.25 Inverter soft start setting (SRE)
Figure 1-42 Inverter soft start setting page Function description: When the
setting is ON, the inverter output gradually increases from 0 to the target
voltage point,This function is very suitable for the motor and the loads with
motor. When the setting is OFF, the inverter output is directly increased from
0 to the target voltage point. Setting conditions: at all states can be set.
Explanation: SRE: Soft Relay Enable The default setting is OFF, and the output
switch will not be closed until the inverter voltage rises to the rated
output, f set to On, the output switch will be closed before the inverter
starts boosting 5.3.26 Reset factory settings(STD)
Figure 1-43 Default value settings page Function description: Restore all
setting to factory settings. Setting conditions: It can be set in mains mode
and Standby (no output but screen on state). It cannot be set when the battery
mode. Explanation: STD :Set Default Before the setting, this interface is
displayed as OFF. When it is set to ON, the system will restore to factory
settings. After the setting is completed, this interface will display 0FF
again. 5.3.27 Parallel Mode Settings(MOD)
Function description: Setting parallel working mode. Setting conditions: Mains
Mode and Standby ( Standby: No output but screen turn on) can be set It cannot
be set in battery mode.
31
Explanation: MOD:Operation mode. The default set is SIG (single mode)
Standalone mode, it can be set as PAR (parallel mode)Single-phase parallel
mode, P1 (R phase mode), 3P2 (S phase mode), 3P3 (T phase mode) When using the
parallel function, first connect the parallel system in the correct way, and
then set the parallel mode of each machine correctly. If there is a machine
set to SIG in the parallel system.the machine reports fault 24. If there are
machines set to 3P1, 3P2, 3P3 in the parallel system, all machines must be set
to one of these three modes, and at least one machine exists in each mode
otherwise all the machines set to these three modes must be set to one of the
three modes. The machine reports fault 24. Mains mode and standby mode can be
set and take effect immediately, but cannot be set in battery mode and cannot
be displayed in pictures 5.3.28 Missing battery alarm (SBA)
Figure 1-45 Missing battery alarm page Function description: Set turn on no
battery alarm Setting conditions: Can be set in all states Explanation:
SBA:Set battery alarm. Default is OFF If it is set to OFF, when the battery is
not connected, there will be no battery-missing, low-battery,and under-battery
alarms 5.3.29 Equalization Mode (EQM)
Figure 1-46 Equalization Mode Settings Page Function description: Setting
whether the inverter turn on equalization mode Setting conditions: Can be set
in all states Explanation: EQM:Equalization Mode The default setting is OFF,
the function is not turned on; if it is set to ON, the controller will start
to enter the equalization phase when the set equalization interval (battery
equalization period) is reached during the float charging stage, or the
equalization is activated immediately.
32
5.3.30 Equalization voltage point setting (EQV)
Figure 1-47 Equalization voltage point setting page Function description:
Equilibrium voltage point setting function Setting conditions: Can be set in
all states Explanation: bCV:Equalization Voltage Can be set in all states SSA-
HL3K-P1EU The default setting is 29 .2, and the settable range is [25, 31.5]
SSA-HL5K-P1EU The default setting is 58.4, and the settable range is [48, 60].
5.3.31 Equalization charging time setting (EQT)
Figure 1-48 Equalization charging time setting(page) Function description:
Equalization charging time setting Setting conditions: Can be set in all
states Explanation: EQT:Equalization Time During the equalization phase, the
controller will charge the cells as much as possible until the cell voltage
rises to the cell equalization voltage. Then use constant voltage regulation
to maintain the battery voltage to maintain the battery balance voltage. The
cells will remain in the equalization phase until the set cell equalization
time is reached.The default setting is 60 minutes, the settable range is
159001, and the increment is 5 minutes each time. 5.3.32 Equalization Delay
Time Settings (EQO)
Figure 1-49 Equalization Delay Time Settings Page
33
Function description: Equalization Delay Time Settings Setting conditions: Can
be set in all states Explanation: EQT: Equalization Time out In the
equalization stage, when the cell equalization time expires and the cell
voltage does not rise to the cell equalization voltage point, the charge
controller will extend the cell equalization time until the cell voltage
reaches the cell equalization voltage. When the battery balancing delay
setting ends, the battery voltage is still lower than the battery balancing
voltage, the charge controller will stop balancing and return to the floating
charge stage.The default setting is 120 minutes, the settable range is
(5,9001, and the increment is 5 minutes each time. 5.3.33 Equalization
interval setting (EQI)
Figure 1-50 Equalization interval setting Function description: Equalization
interval setting Setting conditions: Can be set in all states Explanation
EQl:Equalization interval When the battery connection is detected during the
float phase with the equalization mode turned on, the controller will start to
enter the equalization phase when the set equalization interval (cell
equalization period)is reached. The default setting is 30 days, the settable
range is [1,90], and the increment of each setting is 1 day 5.3.34 Turn on
equalization settings immediately
Figure 1-51 Turn on equalization settings immediately Function description:
Turn on equalization settings immediately Setting conditions: Can be set in
all states Explanation: EQN:Equalization Now The default setting is OFF, the
function is not turned on; when it is set to ON, in the float charging stage
when the balance mode is turned on and the battery connection is detected, the
balance charging is activated immediately, and the controller will start to
enter the balance stage.
34
5.3.35 (GTl) Grid-connected inverter function
Figure 1-52 The grid-connected inverter function setting page Function
description: Set whether the inverter is connected to the grid in PV priority
mains mode or PBG mains mode. Set conditions: All states can be set.
Explanation: GTl:Grid Tie Invert The default setting is OFF, and the function
is not enabled; When set to ON, the inverter tracks the maximum power point,
and the excess energy is fed into the mains.After the function is turned on,
if a communication abnormality occurs, an alarm 56 is generated and the
inverter no longer determines the operation logic according to the BMS
information. 5.3.36 Battery Dual Output Low Voltage Shutdown Point(DBV)
Figure 1-53 Battery dual output low voltage shutdown point page Function
description: When enabled, the secondary output of the inverter is enabled by
default After entering the battery mode, when the battery voltage is lower
than the set point, the secondary output is turned off When the battery
voltage is higher than the set value + 1V/cell again, the secondary output is
turned on. Setting conditions: All states can be set. Explanation: DBV: Dual
output battery mode cut-off voltage The default setting of SSA-HL3K-P1EU is
24V, and the setting range is [22,32] The default setting of SSA-HL5K-P1EU is
48V, and the setting range is [44,60] When the set point is higher than the
constant voltage charging (CV) point- 1V/knot, the constant voltage charging
point is used as the recovery voltage. *This function needs to be used in
conjunction with the dual output auxiliary board. 5.3.37 Battery Dual Output
Duration (DBT)
Figure 1-54 Battery dual output low voltage shutdown point page
35
Function description: When enabled, the secondary output of the inverter is
enabled by default After entering the battery mode, when the battery discharge
time reaches the set point, the secondary output will be turned off. Setting
conditions: all states can be set. Explanation:DBT:Dual output battery mode
cut-off time The default setting is OFF, the function is not enabled, the
setting range is [5,890], and the unit is minute When it is set to FUL, the
output time of the secondary output is not limited.This function needs to be
used in conjunction with the dual output auxiliary board. 5.3.38 BMS
communication function (BMS)
Figure 1-55 BMS management function setting page Function description: Set
whether the inverter communicates with the lithium battery BMS Setting
conditions:All states can be set. Explanation: BMS:Battery Manage System The
default setting is OFF, and the function is not enabled; when it is set to ON,
the inverter communicates with the lithium battery BMS through the central
control board and obtains battery information.After the function is enabled,
if a communication abnormality occurs, an alarm 56 will be generated.and the
inverter will no longer determine the operation logic based on the BMS
information.This function needs to be used in conjunction with the central
control board.When the central control board is not connected, this option
page is blocked 5.3.39 Low SOC shutdown function (SBU)
Figure 1-56 Low SOC shutdown function setting page Function description: Set
the inverter to shut down when the SOC is low Setting conditions: All states
can be set.Explanation: BSU:Battery SOC (capacity) under lock The default
setting is 20, and the settable range is [5,50]. In battery mode, when the SOC
of the lithium battery reaches the set value, it will shut down and alarm 68
will be issued at the same time, and the alarm 68 will be cleared when it
returns to the set value + 5%. When in standby mode, it will switch to battery
mode only when it reaches the set value + 10%, and it will alarm 69 if it is
not reached. After the function is turned on, when the SOC of the lithium
battery reaches the set value + 5%, the alarm 69 will be issued, and the alarm
69 will be cleared when it returns to the set value + 10%. It can be set to
OFF,At this time, the inverter will no longer perform shutdown, startup, and
alarm operations according to the SOC situation. After the function is enabled
if a communication abnormality occurs. the inverter no longer determines the
operation logic based on the SOC information, and clears the relevant alarm.
36
This function needs to be used in conjunction with the central control board When the central control board is not connected, this option page is blocked 5.3.40 High SOC to battery function (STB)
Figure 1-57 Low SOC to mains function setting page Function description: Set
the SOC value of the inverter to battery mode Setting conditions:All states
can be set.Explanation: STG:Battery OC turn to battery mode. The default
setting is 90, and the settable range is [10,100]. PBG priority mains normal
mains modes witch to battery mode when the lithium battery SOC reaches the set
value, After it is turned on, the inverter will switch to battery mode only
when the SOC is higher than the set point and the battery voltage is higher
than the voltage point for switching back to battery mode (see 1.4.2.15).it
can be set to OFF. At this time, the inverter will no longer switch from mains
mode to battery mode according to the SOC. After the function is enabled, if a
communication abnormality occurs, the inverter no longer determines the
operation logic based on the SOC information, and clears the relevant
alarm.This function needs to be used in conjunction with the central control
board.When the central control board is not connected, this option page is
blocked 5.3.41 Low SOC transfer function (STG)
5.4 Battery Equalization Description Equalization function is added into charge controller, lt reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it’s recommended to equalize battery periodically. How to Apply Equalization Function You must enable battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in device by either one of following methods: 1. Setting equalization interval in program 35. 2. Active equalization immediately in program 36 When to Equalize in stage, when the setting equalization interval( battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.
Figure 1-58 Low SOC to mains function setting page Function description: Set
the SOC value of the inverter to the mains mode. Setting conditions: All
states can be set. Explanation: STG:Battery SOC turn to grid mode. The default
setting is 50, and the settable range is [10,90]. PBG priority Mains normal
battery mode Switch to mains mode when the lithium battery SOC reaches the set
value. After it is turned on, when the SOC is lower than the set point or the
battery voltage is lower than the return-to-mains voltage point (see
1.4.2.14), the inverter will switch to the mains mode.it can be set to OFF. At
this time, the inverter will no longer switch from battery mode to mains mode
according to the SOC. After the function is enabled, if a communication
abnormality occurs, the inverter no longer determines the operation logic
based on the SOC information, and clears the relevant alarm.When this setting
is higher than the STB point, STB and STG will not take effect after the next
time they take effect. This function needs to be used in conjunction with the
central control board. When the central control board is not connected, this
option page is blocked.
37
- Equalize charging time and timeout In Equalize stage, the controller will supply power to charge battery as much as possible until battery voltage raises to battery equalization voltage.Then,constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.
38
However, in Equalize stage, when battery equalized time is expired and battery
voltage doesn’t rise to battery equalization voltage point, the charge
controller will extend the battery equalized time until battery voltage
achieves battery equalization voltage. lf battery voltage is still lower than
battery equalization voltage when battery equalized timeout setting is over,
the charge controller will stop equalization and return to float stage
5.5 Fault and alarm description
Figure 1-58 Fault and warning icons Function description: The alarm code ALA
flashes and the buzzer beeps once for 1s and stops after 1 minute. The fault
indicator code is always on, the buzzer beeps for 10 seconds and then stops.
After the fault is stopped and the fault is eliminated, Then try to restart
the inverter, If the restart fails for three times, it will continue to be in
the fault state.The fault and alarm LCD display is as shown in the figure
above, the fault icon in the fault mode is always on, and the alarm icon in
the alarm state flashes. Kindly contact the manufacturer to eliminate the
abnormal condition according to the fault information.
39
5.5.1 Faults Descriptions
Fault: The inverter enters the fault mode, the red LED light is always on and the LCD displays the fault code.
Fault Code Descriptions
Fault code
English meaning
Recovering conditions
Alarm warning
1
Bus soft start fail
Unrecoverable
Fault
2
Bus high
Unrecoverable
Fault
3
Bus low
Unrecoverable
Fault
4
Battery Over Current
Unrecoverable
Fault
5
Over temperature
Unrecoverable
Fault
Recoverable
6
Battery high
Not charging: 29V (high voltage point -2V);
Fault
Charging: high voltage point -2V
7
Bus soft Fault
Unrecoverable
Fault
8
Bus short Fault
Unrecoverable
Fault
9
INV soft Fault
Unrecoverable
Fault
10
INV over voltage
Unrecoverable
Fault
11
INV under voltage
Unrecoverable
Fault
12
INV short circuit
Unrecoverable
Fault
13
Negative power
Unrecoverable
Fault
14
Overload fault
Unrecoverable
Fault
15
Model Fault
Unrecoverable
Fault
16
No boot loader
Unrecoverable
Fault
17
Panel Flash Fault
Recoverable after Flash
Fault
19
Same Serial
Unrecoverable
Fault
20
CAN Fault
Unrecoverable
Fault
21
BAT Volt Different
Unrecoverable
Fault
Line Volt 22
Different
Unrecoverable
Fault
23
Line Freq Different
Unrecoverable
Fault
Output Config 24
Different
Recover when set to stand-alone operation or meet the three-phase
operation setting conditions
Fault
25
Output Syn Loss
Unrecoverable
Fault
Close the BMS communication function,or
26
BMS Fault
Fault
BMS failure recovery
40
5.5.2 Warning Descriptions * Alarm: The red LED flashes, and the LCD displays an alarm code, the inverter does not enter the failure mode.
Alarm code descriptions
Code English meaning
Inverter action
Recovering conditions
Warning
50
Battery not connected Alarm, no charging
Battery voltage N10V*n
Alarm
Auto-restart when battery voltage more then
Alarm, battery low voltage
51
Low battery shutdown
(10V+0.2V)*N, N for numbers of battery serial Alarm
shutdown or unable to boot
group.
52
Battery low
Warning, battery not charging Recoverable (action point + 0.2v/piece)
Alarm
Alarm, low battery shutdown or
53
Battery charge short
Unrecoverable
no engine startup
Alarm
54
Low watt discharge
Warning
Recoverable (battery voltage higher than 13. 2V/cell)
Alarm
Recoverable MPPT non charging:
55
Over charge
Alarm, no charging
29V (high voltage point – 2V);
Alarm
MPPT charging: high voltage point – 2V
56
BMS Loss
Alarm, lock standby mode
recoverable
Alarm
57
Over temperature
Alarm, no charging
The temperature sensor of PFC or INV is lower than 90°C
Alarm
58
Fan lock
Alarm, If one fan fails, the other fan rotates at full speed
Recoverable
Alarm
59
EEPROM fail
Alarm
Unrecoverable
Alarm
60
Overload warning
Alarm, no charging
Reduce the load lower than 97%
Alarm
Abnormal generator
Alarm, keep working in battery
61
Recoverable
waveform
mode
Alarm
Weak energy from PV
Turn off the PV output and
62
(For 5KVA high PV
charging
voltage type)
recover after 10 mins
Alarm
Synchronization signal
Switch to stand-alone mode recovery
63
Alarm, switch to failure mode
fail
Disconnect Troubleshooting Recovery
Alarm
Parallel configuration
64
Alarm, switch to standby mode Resume when three-phase setting is correct
Alarm
incompatible
41
Code 65 66 67 68 69
English meaning
Parallel version incompatible
Inverter action Alarm, switch to standby mode
Parallel Communication Fault
Alarm, switch to standby mode
Parallel Line Differ
Warning
SOC Under SOC Low
Alarm, switch to standby mode
Alarm, f it is in standby mode, it will remain in standby mode and not
turn on
Recovering conditions
Warning
Restore when all machine versions in a parallel system are compatible with each other In the parallel system, it is detected that the slave machine is connected and then recovered, and it is set to stand-alone mode to recover Recover when it detects that the mains voltage and frequency errors of each machine are reasonable Turn off the low SOC shutdown function, or turn off the BMS communication function, or recover when the SOC returns to the set value + 5% Turn off the low SOC shutdown function, or turn off the BMS communication function, or recover when the SOC returns to the set value + 10%
Alarm Alarm Alarm Alarm Alarm
6 TROUBLE SHOOTING
Problem
LCD/LED/Buzzer
Unit shuts down
LCD/LEDs and buzzer will
automatically during
be active for 3 seconds
startup process
and then complete off.
No response after power on.
No indication
Input voltage is displayed as on the LCD and green LED is flashing
Mains exist but the unit works in battery mode.
Green LED is flashing
When the unit is turned on, internal relay is switched on and off repeatedly.
Green LED is flashing
LCD display and LEDs are flashing
Explanation Possible cause The battery voltage is too low (<1.91v/Cell) The
battery voltage is far too low. (<1.4V/Cell) Internal fuse tripped.
Input protector is tripped
Insufficient quality of AC power. (Shore or Generator)
Set” SBU “as the priority of output source
Battery is disconnected
42
What to do
Recharge battery Replace battery
1. Contact repair center for replacing the fuse. 2. Recharge battery
3.Replace battery
Check if AC breaker is tripped and AC wiring is connected well.
1. Check if AC wires are too thin and/or too long. 2. Check if generator (if
applied) is working well or if input voltage range setting is correct. (UPS to
Appliance) Change output source priority to Utility first.
Check if battery wires are connected well.
7.Technical Data sheet
Model
Product Type
Battery Type
Voltage ( range)
Battery
Nominal battery voltage
Discharge Current (maximum continuous)
Charge Current (maximum continuous)
MAX.PV Input Power
MPPT Tracking Range
Best voltage
Vmax PV (absolute maximum)
PV Input
PV input operating voltage range
Full power MPPT voltage range
Maximum operating PV input current
Isc PV (absolute maximum)
Max. inverter back feed current to the array
Voltage (nominal)
AC Input
Current (maximum continuous)
Frequency (nominal)
Voltage (nominal)
Current(maximum continuous)
AC Output
Frequency (nominal ) Power(maximum continuous)
Power factor range
Maximum output overcurrent protection
Operating Temperature
General Parameter
Humidity Storage Temperature
Altitude
Noise
43
SSA-HL3K-P1EU
SSA-HL5K-P1EU
Off-grid Single Phase Hybrid Inverter
lithium /Lead-acid
21-30.2 d.c.V
42-56.4 d.c.V
24 d.c.V
48 d.c.V
125 d.c.A
104 d.c.A
120 d.c.A
80 d.c.A
4000W
5500W
120-500Vd.c.
120-500Vd.c.
300-400Vd.c.
300-400Vd.c.
500 d.c.V
500 d.c.V
120-430 d.c.V
120-430 d.c.V
120-430 d.c.V
120-430 d.c.V
12 d.c.A
18 d.c.A
18 d.c.A
27 d.c.A
/
/
220/230 a.c.V
220/230 a.c.V
40 a.c.A
40 a.c.A
50/60 Hz
50/60 Hz
220/230 a.c.V
220/230 a.c.V
13.6 a.c.A
22.7 a.c.A
50/60 Hz
50/60 Hz
3000 VA
5000 VA
1.0 leading to 1.0 lagging
20A200ms
34A200ms
-10 – +50output power linely derating to 80% when exceed +40 to +50
20%-95%(Non-condensing)
-10 – 60
Not Over 1000m, Derating over 1000m,
Max 4000m. Refer to IEC62040
50dBA
Display and communication
Model Size Weight LCD Display RS232 Communication Port Parallel Connect Interface Operating
SSA-HL3K-P1EU
SSA-HL5K-P1EU
472.5313116mm
8.8kg
Display Running Mode/Loads/Input/Output etc.
Baud Rate2400
Lithium Battery BMS Communication Card. Dry Contact
Without Parallel Connect
With Parallel
Appendix:Parallel Operation Guide
Parallel operation Note: Before paralleling, each machine needs to calibrate
the inverter output voltage, DC component, and battery voltage. In theory, The
more accurate the calibration, the better, but at least meet the inverter
output voltage and battery voltage calibration deviation within ±0.3V, DC
component calibration within ±50 mV.
The shutdown state, that is, the standby state, refers to the state in which
the inverter has no output, but the LCD screen is on.
The method of entering standby state: when the switch is closed, quickly turn
on and then immediately (1 second) turn off, then the inverter enters the
standby state.
1. Single-phase parallel operation Two inverters in parallel System
Connection
44
Communication Connection
1.1.2 Three inverters in parallel System Connection
1.2 Three-phase parallel operation
1.2.1 One inverter per phase: System Connection
Communication Connection
Communication Connection
Multiple single-phase parallel systems can follow the extended wiring method of 2 single-phase parallels to three single-phase parallels0
45
46
1.2.2 Two inverters for the first phase, only one inverter for the remaining phases: System Connection
1.2.3 Two inverters for the first and second phases, and one inverter for the third phase System Connection
Communication Connection
Communication Connection
1.2.4 Three inverters for the first phase, only one inverter for the othertwo
phases System Connection
47
48
Communication Connection 1.2.5 Two inverters per phase:System Connection
Communication Connection
49
1.2.6 Three inverters for the first phase, two inverters for the second phase,
and one inverter for the third phase:System Connection
Communication Connection
1.2.7 Four inverters for the first phase and one inverter for the othertwo
phases: System Connection
50
Communication Connection
2.Connection Precautions 2.1 PV connection/Solar Panel Connection Each
inverter is connected to the solar panel separately, and the PVs of each
inverter cannot be wired in parallel. 2.2 Parallel board connection Note: In
each set of parallel systems, select the two sets of machines with the
farthest distance and short-circuit the positions A of the parallel board with
jumper caps.
Make sure all circuit breakers in the load side line are open And each neutral
line (N line) of the inverter is connected together, and the live line (L
line) at the load side should also be connected together. Step 2-1: Close the
battery breaker (between inverter and battery) then quickly make the inverter
switch from power ON to OFF. Step 2-2: You will have 30 seconds to setting in
LCD panel,
if LCD panel off,just repeat the Step 2-1,then step2-2. Step 2-3: Go into
Inverter setting mode and set “PAR” in program 27 on the LCD. Then turn off
all inverters. Note: When setting on the LCD, the power-ON switch must be
turned off. Otherwise, settings cannot be made and AC input breaker is not
allow to close.
3.LCD Setup and Display For the parallel setting operation, refer to the main
manual – function setting operation, item 27 parallel mode setting. 3.1
Single-phase parallel Step 1: Before commissioning, please check the following
requirements:ls the wiring correct?
51
Notice: Automatic identification of primary and secondary inverters in the
system Step 3: Close the AC circuit breakers of all lines in the AC input,
keep the rocker switch not closed, and wake up the parallel system. There are
instructions on the next page of P9 on the LCD display interface, as shown in
Figure 4.1.1. It is best to have all inverters connected to mains at the same
time. If not, it will show fault 23 or 22. Step 4: If there are no more fault
alarms and the indicating interface is normal, the parallel system is fully
installed. Step 5: Close the circuit breaker on the load side. Turn on the
system and start supplying power to the load.
52
3.2 Parallel as three-phase system (the function is not open) Step 1: Before
commissioning, please check the following requirements: Is the wiring correct?
Make sure that all circuit breakers on the load side are disconnected, and the
neutral wires (N/neutral) of each inverter are connected together, the live
wires (L wires) on the load side of the same phase are connected together, and
the different phases are connected together. The live wires (L wires) are not
connected together. Confirm that the output inverter voltage of each machine,
the DC component and the battery voltage are all successfully calibrated. Step
2: Wake up the inverter to put it into shutdown state, Step 2-1: Close the
battery breaker (between inverter and battery) then quickly make the
inverter switch from power ON to OFF.
Step 2-2: You will have 30 seconds to setting in LCD panel,
if LCD panel off,just repeat the Step 2-1,then step2-2.
then use program 27 on the LCD to configure each Inverter as 3P1, 3P2, 3P3 in
turn. When using the LCD for program setting, the power-on switch must be
turned off. Otherwise, settings cannot be made and AC input breaker is not
allow to close.
Figure 4.1.2
Note 1: To avoid overloading, it is best to let the whole system operate
normally before closing the circuit breaker on the load side. Note 2: There is
a switching time for this power supply system. Power outages may occur for
critical equipment with high power requirements.
Step 3: Turn on the AC circuit breakers for all lines in the AC input. If an AC connection is detected and matches the device settings, the system is working properly. Otherwise, The system will display an alarm or fault, and will not operate in mains mode. Step 4: Close the AC circuit breakers of all lines in the AC input, keep the rocker switch not closed, and wake up the parallel system. There are instructions on the next page of P9 on the LCD display interface, as shown in Figure 4.1.2, which means three-phase power supply System installation is complete. Step 5: Please close the circuit breakers of all power lines on the load side, close the rocker switch, and the system will start supplying power to the load.
53
54
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>