Schneider 4 Pole Residual Current Circuit Breaker
“`html
Specifications
-
Control Mode: Electromagnetic
-
Supply Terminals Voltage Range: DC12V
-
Power Input Voltage Range: DC max.1W(standby)
max.20W(action) -
Supply Voltage Tolerance: AC 220V(50-60Hz)
-10%;+10% -
Supply Voltage Tolerance: AC max.1VA(standby)
max.20VA(action) -10%;+10% -
Supply Indication: Red LED
-
Action Time: 1s
-
Auto Reclosing Times: 3
-
Auto Reclosing Interval Time:
10s-60s-300s -
Mechanical Life: 10000 cycles
-
Electrical Life (AC1): 4000 cycles
-
Operating Temperature: -20 to +55°C (-4 to
131°F) -
Storage Temperature: -35 to +75°C (-22 to
158°F) -
Mounting/DIN Rail: EN/IEC 60715
-
Protection Degree: IP20
-
Operating Position: Any
-
Overvoltage Category: III
-
Pollution Degree: Any
-
Dimensions Weight: Not specified
Product Usage Instructions
Installation and Use
Cooperate with RCCB according to the circuit diagram
provided.
Closing Lock
Note: When checking the circuit, the RCCB cannot close when the
lock function is activated.
Status Indicator
The work status is indicated by the LED on the device. Ensure
the LED is functioning properly for monitoring.
Action Time and Reclosing
The device has an action time of 1 second and can perform auto
reclosing up to 3 times with intervals of 10s, 60s, and 300s.
Ensure the settings are configured according to requirements.
Mechanical and Electrical Life
The device has a mechanical life of 10000 cycles and an
electrical life (AC1) of 4000 cycles. Regular maintenance checks
are recommended to ensure longevity.
Operating Temperature and Mounting
The device can operate within a temperature range of -20 to
+55°C (-4 to 131°F). Mount the device on a suitable DIN rail
according to EN/IEC standards for secure installation.
Frequently Asked Questions (FAQ)
What is the purpose of the manual/automatic selector
switch?
The manual/automatic selector switch allows users to choose
between manual or automatic operation modes based on their
preference or specific requirements.
How does the double locking function work?
The device features a mechanical/electronic double locking
function to ensure secure operation. When activated, it provides
added safety by preventing unauthorized access or tampering.
How can I match this device with other accessories?
The device can be easily matched with other accessories by
following the provided guidelines or consulting the user manual for
compatibility and proper integration.
“`
RCCB SMART ACCESSORIES USER MANUEL
Thank you for choosing Floatless Level Switch Control Relay. Please read this
manual before installaton, operation and maintenance.
Applications Can be widely used in power grid terminal line, such as meter
box, new energy circuit management, PV solar control box, smart electricity,
smart home, new energy vehicle charging pile, and so on. Function Features –
It can be matched with circuit breaker/leakage protection switch and
automatically reclose when RCCB trips unexpectedly, No need for manual
closing, reduce the cost of manual maintenance, and eliminate faults in time
to improve ef ficiency. – Built in 3 reclosing times, continuous closing
failure within 15 minutes can
send alarm through auxiliary contact. – With manual / automatic selector
switch. – With mechanical / electronic double locking function. – The shaft
transmission mode is more stable and reliable. – Can match other accessories.
– Work status is indicated by LED. – 1-MODULE.
TECHNICAL PARAMETERS
Control mode
Supply termnals Voltage range Power nput Voltage range Supply voltage
tolerance Power nput Supply voltage tolerance Supply ndcaton Acton tme Auto
reclosng tmes Auto reclosng nterval tme Reset the closng tmes Mechancal lfe
Electrcal lfe(AC1) Operatng temperature Storage temperature Mountng/DIN ral
Protecton degree Operatng poston Overvoltage cathegory Polluton degree
Dmensons Weght
Auto Reclosng A1-A2 DC12V
DC max.1W(standby) max.20W(acton) AC 220V(50-60Hz) -10%;+10%
AC max.1VA(standby) max.20VA(acton) -10%;+10% red LED 1s 3 10s-60s-300s
No trp or manual reset wthn 15 mnutes after successful closng 10000 4000
-20 to +55-4 to 131 -35 to +75-22 to 158
Dn ral EN/IEC 60715 IP20 any
sold wre max.1×2.5or 2×1.5/wth sleeve max.1×2.5(AWG 12) 82×18×78mm 80g
Mode
Electromagnetc
Type(wave form of the earth leakage sensed)
B
Rated current In
25,40,63,80A
Poles
2P,4P
Rated voltage Ue Insulaton voltage U
2P 240V~, 4P 415V~ 500V
Rated frequency
50/60Hz
Rated resdual operaton current(In)
30, 100, 300mA
Rated resdual makng and breakng capacty(Im) 500(In=2540A) 630(In=63A)
Short-crcut current Inc= Ic
10,000A
SCPD fuse
Break tme under In Rated mpulse wthstand voltage(1.5/50) Ump Delectrc test voltage at nd.Freq. for 1mn
0.1s 4000V 2.5kV
Electrcal lfe
2,000 Cycles
Mechancal lfe Contact poston ndcator Protecton degree Ambent temperature(wth daly average35 ) Storage temperature Termnal connecton type Termnal sze top/bottom for cable
4,000 Cycles Yes IP20 -5 ~+40 -25~+70 Cable/Pn-type busbar/U-type busbar 35mm2 18-3AWG
Termnal sze top/bottom for cable Tghtenng torque Mountng
35mm2 18-3AWG 2.5Nm 22In-lbs On DIN ral EN60715(35mm) by means of fast clp devce
Connecton
From top and bottom
Status ndcator Mode selecton Closng lock
PWR RD
AUTO MAUN
LOCK
Test Monthly
N1 T
N2
40A I n0.03A 230V~ t0.1s
Im=I m=500A Inc=I c=6000A
IEC 61008 EN 61008
RCCB Operaton handle
WIRING DIAGRAM VTRA-RC/S
A1 A2 COM NC 1234 AC220V AUX
TRIPPING CURRENT RANGE
Laggng Angle 0° 90°
135°
Alternatve Current Senstve
In0.01A 0.35InI1.4In 0.25InI1.4In 0.11InI1.4In
Pulsatng drect current senstve
In0.01A 0.35InI2In 0.25InI2In 0.11InI2In
Surge current proof
B class Tripping is ensured for sinusoidal AC residual currents pulsed DC residual currents, alternating residual sinusoidal currents up to 1000Hz, pulsating direct residual currents and for smooth direct residual currents, whether applied suddenly or increasing slowly.
They react to AC and pulsating DC fault current which reach 0 or almost 0 within one time period of the mains frequency.
RCCB’s surge capacity. Not tripping at standardized 8/20 s surge-current waves acc.to VDE 0432 Part 2 with surge current values of up to 250A.
CIRCUIT DIAGRAM
2P
4P
INSTALLATION AND USE
Cooperate wth RCCB 2
1
Closng lock
Note: When checkng the crcut, the RCCB can not close when the lock functon s actvated.
1 3
Accessores nstallng
Accessores ARD
RCCB
AUTO MAUN AUTO MAUN
PWR
AUTO mode, the auto reclosng functon s enable.
MAUN mode,the auto reclosng functon s dsable.RCCB can only be opened and
closed ma.nually
When powered on, the green ndcator wll flash for 2 seconds to wat for the
power supply to stablze. Then the green ndcator lght wll stay on f When RCCB
fals to trp, the red ndcator lght wll be on. Note that red durng auto reclosng
delayThe color wll flash. After the delay, t wll swtch on automatcally and the
green lght wll be on.
35 45 82
FUNCTIONS DIAGRAM
LED:PWR Trp tmes
AUX RCCB(Auto)
1
1
2
3
4
OIO
I
OI
O
I
O
I
O
Tr
10s
15mn
10s 15mn 60s 15mn
300s 15mn
Reset the closng tmes Tr:Power delay=2s.
VTRA-RC/S has automatic closing function,The closing logic is shown in the
figure below:
AUTO MODE
AUTO MAUN
PWR
ON
OFF LOCK
10s 15mn
OFF
ON
300s
ON
OFF
15mn
OFF 60s
ON 15mn
AUX
Note: if the closing times and delay time need to be customized, please
contact our company.
CONNECTION
L N
A1 A2 COM NC 1234
AC220V AUX
Alarm lamp
PWR RD AUTO MAUN
LOCK
Test Monthly
N1 T
N2
40A I n0.03A 230V~ t0.1s
Im=I m=500A Inc=I c=6000A
IEC 61008 EN 61008
C25 ON
13
400V~ OFF
3000
24
IEC 60898-1
C16 230V~
ON 1
OFF 3000 2 IEC 60898-1
C16 230V~
ON 1
OFF 3000 2 IEC 60898-1
LOAD
LOAD
LOAD
COMMON FAULTS
Fault descrpton
Resolvent
1. Please confirm whether the power supply voltage s normal.
1 Unable to close or open. 2. Please confirm whether the workng mode s set n
AUTO mode. 3. Please confirm the buckle of the electrc operaton mechansm and
RCCB.
2 Trp mmedately after closng.
1. Please check the crcut to confirm whether there s overload / short crcut /
leakage fault at the lower end of RCCB.
2. Whether the crcut breaker s damaged or not, and whether t s slpped.
DIMENSIONS(mm)
PWR RD
AUTO MAUN
LOCK
53
2P
49.5 78
88
4P
Test Monthly Test Monthly
PWR RD
AUTO MAUN
LOCK
N1 T
N2
40A I n0.03A 230V~ t0.1s
Im=I m=500A Inc=I c=6000A
IEC 61008 EN 61008
PWR RD
AUTO MAUN
N135 T
N246
40A I n0.03A 230V~ t0.1s
Im=I m=500A Inc=I c=6000A
LOCK
IEC 61008 EN 61008