61-744 Clamp Meter by Ideal Instruction Manual
- August 22, 2024
- IDEAL
600 AAC Clamp Meter
**Instruction Manual
61-744
61-746**
Register your product and access more information at
http://www.idlim.net/support/registration/
Read First: Safety Information
Understand and follow operating instructions carefully. Use the meter, test
leads and all accessories only as specified in this manual; otherwise, the
protection provided by the meter can be impaired.
WARNING
To avoid possible electric shock, personal injury or death, follow these
guidelines:
-
Do not use if meter appears damaged. Visually inspect the meter to ensure case and jaws are not cracked.
-
Inspect and replace test leads if insulation is damaged, metal is exposed, or probes are cracked. Pay particular attention to the insulation surrounding the connectors.
-
To preserve the safety rating of this product, use only test leads with a minimum rating of CAT III 600V. Do not use improvised connections that could present a safety hazard.
-
Note that the measurement category and voltage rating of combinations of the meter, the test leads, and the accessories is the lowest of the individual components.
-
Do not use meter if it operates abnormally as protection may be impaired.
-
Do not use during electrical storms or in wet weather.
-
Do not use around explosive gas, dust, vapor or in damp or wet environments.
Do not submerge or expose the meter to water and do not use if the meter has ever been exposed to water or other fluids. -
Do not apply more than the rated voltage or amperage.
-
Remove the test leads from the input jacks before measuring current.
-
Replace battery as soon as battery indicator appears to avoid false readings.
-
Remove the test leads from the meter prior to removing battery cover.
-
Do not use without the battery and battery cover properly installed.
-
Do not attempt to repair this unit as it has no user-serviceable parts.
-
Use the proper terminals, functions and range for your measurements.
-
Never ground yourself when taking electrical measurements.
-
Connect the black common lead to ground or neutral before applying the red test lead to potential voltage. Disconnect the red test lead from the voltage first.
-
Keep fingers behind the guard rings of the probe tips.
-
Hold the clamp behind the tactile barrier.
-
Voltages exceeding 30VAC or 60VDC pose a shock hazard so use caution.
-
Remove batteries before storage or if unit will not be used for longer than 1 month.
CAUTION
To protect yourself, think “Safety First”:
-
Comply with local and national safety codes.
-
Use appropriate personal protective equipment such as face shields, insulating gloves, insulating boots, and/or insulating mats.
-
Before each use:
– Perform a continuity test by touching the metal tips of the test leads together to verify the functionality of the battery and test leads.
– Use the 3 Point Safety Method. (1) Verify meter operation by measuring a known voltage. (2) Apply meter to circuit under test. (3) Return to the known live voltage again to ensure proper operation. -
Always work with a partner.
-
Remove the batteries for storage or if the meter will not be used for longer than one month. Battery leakage will compromise the safety of the meter and cause damage to internal components.
Features:
- Auto/manual ranging clamp meter
- Non-Contact Voltage (70-600VAC)
- Measures 600 AAC Current
- Measures AC/DC Voltage and Resistance
- Audible continuity
- Data hold
- Auto Power Off
- Low Battery Indicator
- Compact jaws for reaching into tight spaces
- Electronic overload protection on all ranges
- 61-744 model is averaging sensing, rms calibrated
- 61-746 model is true rms sensing.
Features
- Jaw Clamp
- Lever
- Function Dial
- Display (LCD)
- Volts and resistance (V-Ω) input terminal
- Common (COM) input terminal
- Non-Contact Voltage (NCV)
- Range ( )
- Data Hold
- Measuring Functions
- Tactile Barrier
Display Icons
- 4000 count display
- Units of measure
- Voltage
- Amperes
- Ohms
- Continuity
- AC measurement is selected
- DC measurement is selected
- Polarity indicator for DC
- Low battery indicator
- Range ( )
- Data hold
- APO – Auto Power Off
Symbols on the Unit
- Warning – read the instruction manual
- NCV – Non-Contact Voltage
- Cat III – 600V Safety category
Symbols on the Unit
| Risk of Danger. Important Information. See Manual.
---|---
| Hazardous voltage. Risk of electrical shock.
| Application around and removal from Hazardous Live conductors is permitted.
| AC (Alternating Current)
| DC (Direct Current)
| Earth Ground
CAT II| Measurement Category II applies to test and measuring circuits
connected directly to utilization points (socket outlets and similar points)
of the low-voltage installation
CAT III| Measurement Category III applies to measuring circuits connected to
the distribution part of the building’s low-voltage installation
CAT IV| Measurement Category IV applies to test and measuring circuits
connected at the source of the building’s low-voltage installation
Test Leads
OPERATION:
Non-contact voltage (NCV)
With the NCV tab on the tip of the clamp close to an AC voltage, press the NCV
button.
The NCV LED will light and the beeper will sound. The closer the NCV tab is to
AC voltage, the louder the beep. To differentiate between hot and neutral in
an outlet, insert the NCV tab into each slot in the outlet. The beeper will be
much ouder on the hot side of the outlet than the neutral. The test lead can
also be used to differentiate between the hot and neutral. Plug the red test
lead into the V/Ω input jack on the meter.
Press the NCV button and insert the probe tip into each slot of the outlet.
The beeper will only beep on the hot side of the outlet.
Auto/Manual Ranging Mode ( )
The meter defaults to auto ranging mode when powered on. In this mode, the
meter automatically selects the best range to display the measurement. By
pressing the Range ( ) button on the meter, the manual range mode will
override the auto ranging feature of the meter. A ( ) appears in the upper
left side of the display.
Continue pressing the Range button until the desired range is obtained. Use
this mode to lock in a specific range for repeated measurements. To return to
the auto ranging mode, either depress the Range button for greater than 1
second or turn the meter off and then back on again.
Data Hold Feature
Press the Hold button on the side of the meter to toggle in and out of the
data hold mode. “HOLD” appears in the upper left of the meter display when
data hold is active. Use the data hold feature to lock a measurement reading
on the display. Press the Hold button again to unlock the display and obtain a
real-time reading.
Auto Power Off (APO) Feature
The meter automatically powers itself down after about 10 minutes of no use. Press any button, and the meter will wake up and display the last reading taken before power down. This feature can be overridden by holding the Range ( ) button while turning the function switch from Off to any other position. When APO is defeated, the “APO” will be removed from the display. Turning the meter off will restore the APO default.
Measuring AC Current (Amps):
Measuring Voltage:
Measuring Resistance (Ohms):
- Verify the circuit is de-energized to obtain accurate measurements.
Verifying Continuity ( ):
- Verify the circuit is de-energized.
- The meter will sense the level of resistance and beep if the resistance is less than 25Ω to confirm that continuity is present.
Battery Replacement:
- Ensure test leads are disconnected from circuit or components.
- Remove test leads from input jacks on meter.
- Remove the two screws from the battery cap.
- Remove the battery cap.
- Replace batteries with two “AAA” batteries.
- Assemble the battery cap to the meter and re-tighten the screws.
Maintenance:
Switch off and disconnect the meter completely before carrying out any
maintenance.
Clean the case with a damp cloth and mild detergent. Do not use abrasives or
solvents.
Keep away from liquids and ensure the meter is completely dry before use.
Service and Replacement Parts:
This unit has no user-serviceable parts.
For replacement parts or to inquire about service information contact IDEAL
INDUSTRIES, INC. at 1-877-201-9005 or
visit our website www.idealindustries.com.
Specifications:
Display: 3-3/4 digit LCD with 4000 counts
Polarity: Automatic, positive implied, negative (-) polarity indication.
Overrange: “OL” indication is displayed.
Measure Rate: Samples 2 times per second, nominal.
Auto Power Off: Approximately after 10 minutes of non-use.
Battery Life: 400 hours continuous with Alkaline (61-744) 250 hours
continuous with Alkaline (61-746)
Low Battery Indication: The “ “ is displayed when battery voltage drops
below operating level.
Power Supply: (2) 1.5V “AAA” batteries (NEDA R03). Includes an isolated
battery compartment.
Accuracy: Stated accuracy at 23°C ±5°C, <75% R.H. Temperature 0.1 x
(specified accuracy) per °C,
Coefficient: (0°C to 18°C, 28°C to 50°C).
Altitude: 6561.7 ft. (2000m)
Operating Environment: 32°F to 122°F (0°C to 50°C) at < 70% R.H.
Storage Environment: -4°F to 140°F (-20°C to 60°C) at < 80% R.H.
Jaw Opening: Accepts a 1.50” (38mm) conductor
Dimensions: 8.0”H x 2.6”W x 1.5”D (203mm H x65mm W x37mm D)
Weight: 7.1 oz. (200g) including batteries
Accessories included: Carrying Case, Test Leads, (2) 1.5V “AAA”
batteries, operating instructions.
Safety: Complies with UL/IEC/EN: 61010-1, 61010-2-032, 61010-031
specifications, Cat III-600V.
Double Insulation
Instrument has been evaluated and complies with insulation category III
(overvoltage
category III). Pollution degree 2 in accordance with IEC-644. Indoor use.
Ranges & Accuracies:
AC Converter:
61-744 model is averaging sensing, rms calibrated
61-746 model is true rms sensing.
Accuracy:
Accuracy is specified as +/-(a percentage of the reading + a fixed amount) at
23°C±5°C (73.4°F ± 9°F), less than 75% relative humidity.
Temperature Coefficient: 0.1 times the applicable accuracy specification per degree C from 0°C to 18°C and 28°C to 50°C (32°F to 64°F and 82°F to 122°F)
Function| Range and Resolution| Accuracy| Overload
Protection
---|---|---|---
61-744 61-746
AC Current*| 40.00A//400.0A/600A (50Hz – 60Hz)| 1.7% + 6 digits| 1.7% + 10
digits| 600AAC
40.00A/400.0A/600A (60Hz – 400Hz)| 3.0% + 6 digits| 3.0% + 10 digits
AC Voltage| 400.0V (50Hz – 500Hz)| 1.2% + 5 digits| 1.2% + 8 digits| 600 VDC
or AC mis
600V (50Hz – 500Hz)| 1.5% + 5 digits| 1.5% + 8 digits
DC Voltage| 400.0V/600V| 0.5% + 2 digits| 600 VDC or AC rms
Resistance| 400.052/4.000k52/40.00kce 400.0k 52| 1.0% + 4 digits| 600 VDC or
AC rms
4.000MQ| 1.5% + 4 digits
40.00MQ| 3.0% + 5 digits
Continuity| Audible indication <25Q| N/A| 600 VDC or AC mis
Response time: 500ms
- Accuracy stated for crest factor ≤ 3
Input Impedance is 10MΩ.
Warranty Statement:
This tester is warranted to the original purchaser against defects in material
and workmanship for two years from the date of purchase. During this warranty
period, IDEAL INDUSTRIES, INC. will, at its option, replace or repair the
defective unit, subject to verification of the defect or malfunction. Your
original receipt from an authorized distributor of IDEAL INDUSTRIES, INC. is
your proof of purchase. Register your product at:
http://www.idlim.net/support/registration/
.
This warranty does not apply to defects resulting from abuse, neglect,
accident, unauthorized repair, alteration, or unreasonable use of the
instrument.
Any implied warranties arising out of the sale of an IDEAL product, including
but not limited to implied warranties of merchantability and fitness for a
particular purpose, are limited to the above. The manufacturer shall not be
liable for loss of use of the instrument or other incidental or consequential
damages, expenses, or economic loss, or for any claim or claims for such
damage, expenses or economic loss.
State laws vary, so the above limitations or exclusions may not apply to you.
This warranty gives you specific legal rights, and you may also have other
rights which vary from state to state.
IDEAL INDUSTRIES, INC.
Sycamore, IL 60178
Technical Hotline:877-201-9005
www.idealind.com
ND 6442-5 Made in Taiwan