Danfoss R290 Fan Cooled Condensing Units for Propane Instructions
- August 20, 2024
- Danfoss
Table of Contents
Danfoss R290 Fan Cooled Condensing Units for Propane Instructions
This instruction applies to fan-cooled condensing units for the refrigerant
R290 (or similar inflammable gases).
During service only the refrigerant type stated on the condensing unit must be
used.
-
1. **Version**
For solder connection, has a helium/dry air holding charge and is designed for use in refrigeration systems with capillary tube.
-
Refrigerant charging
With regard to evacuation and charging an condensing unit is to be treated as a compressor. Refrigerant charging must take place from a charging board not contaminated with refrigerants containing chlorine. No valves or flare connections of any kind must be used.
The condensing unit must be hermetically sealed, i.e. all connections must be
soldered. After charging all solderings/connections are to be checked for
leaks with a leak detector.
Keep away flammables from the condensing unit.
3. **Installation**
Install the condensing unit in the foreseen location.
Prepare the tube connections from the evaporator.
Use a drier with 3Å molecular sieves suitable for R290.
Use only dry and clean components and avoid moisture entering the system.
The system components must not contain any chlorine, mineral oil or other oily
substances.
4. **Electrical connections**
Fit the terminal board cover.
Pressure switches and thermostats must also be mounted in an IP64 or higher
classified box.
Keep away flammables from the electrical equipment.
5. **Safety rules**
Follow the information given in:
EN/IEC 60335-2-89 or similar.
6. **Maximum refrigerant charges R290**
Units without receiver
The maximum charging amount must not exceed 150 g.
It is recommended to charge only the amount necessary for the operation of the
refrigeration system.
The charging amount must be adapted to suit each system type.
The condensing temperature must not exceed 55°C for stationary operation and
65°C for peak load.
7. **Cold start**
The compressor must be allowed to assume a temperature higher than 10°C before
it is started for the first time. This will prevent possible start problems
caused by too high oil viscosity.
At lower temperatures some tripping of the winding protector may be expected
until the viscosity of the oil becomes reduced.
8. **Winding Protector**
(only Applied for 119-3993)
The compressors have a built-in winding protector. If the winding protector
cuts out while the compressor is cold it may take approx. 5 minutes for the
protector to reset. If the winding protector cuts out while the compressor is
hot (compressor housing above 80°C) up to 45 minutes may pass before the
protector resets.
The winding temperature must never exceed 130°C.
9. **Checking the winding protector**
In the event of compressor failure a check must be made by resistance measurement directly on the current lead-in to find out whether the fault is due to motor damage or simply a winding protector trip.
10. **Location of the winding protector in the electrical circuit. (only Applied for 119-3993)
**
11: Run winding
12: Start winding
14: Winding protector
If resistance measuring or a test lamp shows that there is a connection
through the motor windings from point R to point S, but a bro circuit between
points R and C or S and C, indicates that the winding protector has cut out
Therefore, wait for the protector to reset.
11. Service instructions
When emptying a defective system the refrigerant must be collected without
mixing other refrigerants. Evacuation must take place until a vacuum of 1 mbar
or lower is r Blow through the refrigeration system with dry nitrogen.
The drier must always be replaced when a system is opened.
Service on these installations must only be done by expert installers with
thorough knowledge of inflammable gases like e.g. propane.
See also Installation .
12. Approvals
The following approvals must be obtained through authorised institutes like
Nemko, Demko, BEAB, LCJE, UL etc. Among others EN 60 335-2-24, IEC 60335-2-89,
IEC 60079-15, UL 60335-1 and UL 60335-2-89.
Literature is also available on our internet homepage:
www.danfoss.com/en/products/dcs/condensing-units/condensing-
units/
13. Warnings
Electrical connections
1A: Run Winding
1B: Start winding
1C: Start relay
1D: Winding protector
1E: Start capacitor
1F: Bleeder resistance
1G: Run capacitor
1H: Thermostat
1J: Fan
1K: Pressure control
1L: PTC
Danfoss A/S
Climate Solutions ● danfoss.com ●+45 7488 2222
Any information, including, but not limited to information on selection of
product, its application or use, product design, weight, dimensions, capacity
or any other technical data in product manuals, catalogues descriptions,
advertisements, etc. and whether made available in writing, orally,
electronically, online or via download, shall be considered informative, and
is only binding if and to the extent, explicit reference is made in a
quotation or order confirmation. Danfoss cannot accept any responsibility for
possible errors in catalogues, brochures, videos and other material. Danfoss
reserves the right to alter its products without notice. This also applies to
products ordered but not delivered provided that such alterations can be made
without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/S or Danfoss group
companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All
rights reserved.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>