Air Management Supply RXRX-LKG01, MXRX-LKG01 Louver Panels Installation Guide

August 20, 2024
Air Management Supply

Air Management Supply RXRX-LKG01, MXRX-LKG01 Louver Panels

INSTALLATION INSTRUCTIONS

KIT   MODEL: RXRX-LKG01 / MXRX-LKG01 LOUVER PANELS
FOR UNIT MODELS: : GEG & ACG 15-25T UNITS

Recognize this symbol as an indication of Important Safety Information!

WARNING

THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT, AND OPERATION OF THIS KIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION, ADJUSTMENT, OR OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE, OR MAINTENANCE, AND POSSIBLY RESULT IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH.

PARTS LIST

PART DESCRIPTION Part # Qty
Louver Panel 10-107707-27HT 3
Screws – Blunt Tip – 3/8” 63-42109-03 3
Screws – Sharp Tip – 5/8” 63-22338-11 21

REQUIRED TOOLS/SUPPLIES

A. Box Cutter (to open packaging)
B. Scratch Awl
C. Nut Drivers:

  • 3/8”
  • 5/8”

WARNING

BEFORE BEGINNING ANY MODIFICATION, BE SURE MAIN DISCONNECT SWITCH IS IN THE “OFF” POSOTION.
FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH. TAG DISCONNECT WITH A SUITABLE WARNING LABEL.

INSTALLATION PROCEDURE FOR KIT

  1. Remove louver panels and mounting screws from package.

  2. Place each lover panel onto the unit. Insert the blunt tip screws along the vertical sides first to retain panel in place; 1 screw per panel.
    NOTE: DO NOT USE SHARP TIP SCREWS HERE; RISK OF COIL DAMAGE!

  3. Insert the sharp tip scres to finish securing the panels; 7 screws per panel.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals