ElektroBalt BA-T031 NH Fuse Switch Disconnector Instruction Manual

August 16, 2024
ElektroBalt

ElektroBalt BA-T031 NH Fuse Switch Disconnector

Specifications:

  • Product Name: NH-fuse-switch-disconnector
  • Model: BA-T031
  • Size: 00
  • Design: 3-pole
  • Mounting: Busbar mounting on 60 mm system

Product Usage Instructions

Safety Information:

Warning: Hazardous voltage! Can cause electrical shock and burns. Disconnect power before proceeding with any work on this equipment.

Advice: The product described in this operating manual may be installed only by electrotechnically qualified personnel. Laymen must not install or operate because they cannot foresee the possible consequences of their actions.

Installation:

Assembling: Insert the fuse-link, switch-on the device.

Busbar Mounting: Securely mount the product on the busbar system using appropriate tools and following the provided guidelines.

Usage:
Attention: Only apply fuse-links with silver-plated contacts or silver- plated solid-links to ensure proper functionality.

FAQ:

Q: Who can install the product?
A: The product may only be installed by electrotechnically qualified personnel. Laymen should not attempt installation due to safety concerns.

Q: What type of fuse-links should be used?
A: Only apply fuse-links with silver-plated contacts or silver-plated solid-links as recommended for optimal performance.

Operating

NH-fuse-switch-disconnector
Size 00, 3-pole design, busbar mounting

Warning

  • Hazardous voltage!
  • Can cause electrical shock and burns.
  • Disconnect power before proceeding with any work on this equipment.

Advice

The product described in this operating manual may be installed only by electrotechnically qualified personnel.

“Laymen” must not install or operate because they cannot foresee the possible consequences of their actions.

Disassembling

Assembling (1),Insert of fuse-link (2), Switch-on (3)

Attention!
Only apply fuse-links with silverplated contacts or silver-plated solid-links.

Terminal at topside

Accessory (B): Lock-out contact cover;
(C): Micro-switch for indication of switch-position

Accessory (E): Locking device
Sealing (1)

Accessory

Further accessories and installation instructions you will find at our website

Dimensions [mm]

T i p/Type NH00
According to standard DIN EN 60947-3
For NH fuse-links acc. to DIN VDE 0636-2 Velikost

Size

| 000/00
Rated operational voltage| Ue| V| AC690 DC250
Rated operational current 1)| Ie| A| 160
Conv. free air thermal current with fuse-links1)| Ith| A| 160
Rated insulation voltage| Ui| V| AC800
Rated impulse withstand voltage| Uimp| kV| 8
Utilization category|

|

| AC-23B (400V/160A) AC-22B (500V/160A) AC-21B (690V/160A) DC-22B (250V/160A)
Rated short-time withstand current| Icw| kA| 5/1s
Max. permis. power loss per fuse-link| Pa| W| 12
Rated conditional short-cirquit current| Iq| kA| 120 (500V)

100 (690V)

60439 zu beachten/In case of mounting of several units in low voltage switchgear-combinations, please consider rated diversity factors acc. to EN 60439.

Further technical data you will find at our website.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals