seitron TM 00-M Electro Mechanical Room Thermostat Instructions
- June 3, 2024
- seitron
Table of Contents
TM 00-M Electro Mechanical
Room Thermostat
Instructions
Fig. 1 Aspect extérieur
OVERVIEW
Room thermostats with unipolar gas filled bellows and change over contacts, are suitable for commercial and industrial premises as well as for home installation both for heating and air conditioning.
TECHNICAL FEATURES
Regulation range: | 5°C .. 30°C |
---|---|
Differential: | Δt ≤1K |
Thermal gradient: | 1K / 15 min. |
Contact type: | SPDT (Change over) |
Contact rating: | TM001M: 16(2,5)A 250V~ |
TM002M: 16(2,5)A 250V~
TM003M: 10(1,5)A 250V~
TM004M: 10(1,5)A 250V~
Protection grade:| IP 30
Shock resistance:| IK 04
Type of action:| lB
Pollution degree:| 2
Class of protection against electric shock:| II
Rated impulsevoltage:| 4000V
Number of manual cycles:| 3000
Number of automatic cycles:| 100000
Max. cables cross section accepted by terminal blocks:| 4 mm ²
Ball pressure test temp.:| 75°C
Work temperature range:| 0°C .. 40°C
Stock temperature range:| -10°C .. +50°C
Humidity limits:| 20% .. 80% RH (non condensing)
Case:|
Cover – Knob:| 20% .. 80% RH (non condensing)
Base:| PA 6 V0
Grey (RAL 7001)
CLASSIFICATION UNDER REG. 2013.811.EC
Class: | I |
---|---|
Contribution to energy efficiency: | 1% |
WARRANTY
In the view of a constant development of their products, the manufacturer
reserves the right for changing technical data and features without prior
notice. The consumer is guaranteed against any lack of conformity according to
the European Directive 1999/44/EC as well as to the manufacturer’s document
about the warranty policy. The full text of warranty is available on request
from the seller.
NSTALLATION
WARNING
- To adjust properly room temperature, installthe thermostat far from heat sources,draughts or particularly cold walls (thermalbridges).
- The thermostat must be installed at approx.1,5 m from the floor and where thetemperature is close to the average roomtemperature.
- The appliance must be wired to the electricmains through a switch capable ofdisconnecting all poles compliant to thecurrent safety standards and with a contactseparation of at least 3 mm in all poles.
- Installation and electrical wirings of thisappliance must be made by qualifiedtechnicians and in compliance with thecurrent standards.
- Before wiring the appliance be sure to turnthe mains power off.
ELECTRICAL WIRINGS
|
---|---
|
|
WARNING!
The lamp which evidences operation must be powered with 230Vac. In case it is
used, it must be wired as shown in the diagram.
KNOB ROTATION LIMITATION
It is possible to limit the rotation range for the setpoin knob by following
these steps:
- Remove the knob;
- Pick up the plastic pins (X) parked at one side of the knob area and set them (Y) as in the example of Fig. 12.
In this example the rotation range (Z) is reduced as in the shown angle.
WEIGHT
TM001M0001AN 038911 250222
Documents / Resources
|
seitron TM 00-M Electro Mechanical Room
Thermostat
[pdf] Instructions
TM 00-M, Electro Mechanical Room Thermostat, Room Thermostat, Electro
Mechanical Thermostat, Thermostat, TM 00-M
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>