Altech Corp PSC-151 Series Power Supplies Owner’s Manual
- August 6, 2024
- Altech Corp
Table of Contents
Altech Corp PSC-151 Series Power Supplies
Specifications
- Model: PSC-151 Series
- Type: Type Approved
- Energy Saver: Yes
- DC Voltage:
- PSC-15124: 24V
- PSC-15148: 48V
- Rated Current:
- PSC-15124: 6.3A
- PSC-15148: 3.2A
Product Usage Instructions
Installation Guidelines
Ensure installation clearance of 40mm from top, 20mm from bottom, and 5mm
from the left and right side when loaded with full power permanently. For
adjacent heat sources, maintain a 15mm clearance.
Output Voltage Adjustment
}The voltage adjustment range is between 29-33V for PSC-15124 and 56-65V
for PSC-15148. Use caution when adjusting to prevent overloading or
underpowering connected devices.
Protection Features:
The power supply has various protection mechanisms:
- Constant current limiting at 150% rated power or in case of a short circuit.
- Automatic shutdown if the output voltage drops to 40% of the rating.
- Latch-off mode for protection against overvoltage.
- Automatic recovery after temperature decrease for overtemperature protection.
Maintenance and Safety
Regularly check for proper functioning of the power supply. Ensure that the
system meets safety standards and follows the installation guidelines to
prevent any hazards.
FAQ
-
Q: What should I do if the power supply shuts down due to protection mechanisms?
A: If the power supply shuts down due to protection mechanisms, allow it to cool down before re-powering on. If the issue persists after multiple shutdowns, consult the user manual for further instructions. -
Q: Can the power supply be used in equipment that requires EMC compliance?
A: Yes, the power supply can be used in equipment that requires EMC compliance. Ensure that the final equipment still meets EMC directives after installing the power supply.
PSC-151 Series
Features
- Universal AC input (88-264V AC)
- Installed on DIN rail TS-35 / 7.5 or 15
- Built-in active PFC function, PF > 0.95
- 150% peak load capability
- 100% full load burn-in test
- Protection: SCP, OLP, OVP, OTP
- Two selectable peak load modes
- Built-in DC OK Relay contact
- Built-in Remote ON / OFF function
- 3 years warranty
- UL 508
OUTPUT
- Cat. No. PSC-15124 PSC-15148
- DC VOLTAGE 24V 48V
- RATED CURRENT 6.3A 3.2A
- CURRENT RANGE 0~6.3A 0~3.2A
- RATED POWER 150W 150W
- PEAK CURRENT 9.45A 4.8A
- PEAK POWER 225W (3sec.)
- 3 seconds or 20% duty cycle max. and the average output power should not exceed the rate power.
- RIPPLE & NOISE (max) 240mVp-p 480mVp-p
- Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
- VOLTAGE ADJ. RANGE -2% ~ +8% -2% ~ +8%
- VOLTAGE TOLERANCE ±1.0% ±1.0%
- Tolerance: includes set up tolerance, line regulation and load regulation.
- LINE REGULATION ±0.5% ±0.5%
- LOAD REGULATION ±1.0% ±1.0%
- SETUP, RISE TIME 700ms, 30ms / 230VAC / 115VAC at full load
- HOLD UP TIME (Typ.) 16ms / 230VAC; 16ms / 115VAC at full load
INPUT
- VOLTAGE RANGE 88 ~ 264VAC; 124 ~ 373VDC
- Derating may apply in low input voltage. Please check the derating curve for more details.
- FREQUENCY RANGE 47 ~ 63Hz
- POWER FACTOR(Typ.) 0.9 / 230VAC; 0.98 / 115VAC at full load
- EFFICIENCY (Typ.) 87% 87%
- AC CURRENT (Typ.) 2.6A / 115VAC; 1.3A / 230VAC
- INRUSH CURRENT (Typ.) 33A / 115VAC; 65A / 230VAC
- LEAKAGE CURRENT <1mA/ 240VAC
PROTECTION
- OVERLOAD Normally works within 105% ~ 150% rated output power for more than 3sec and then shutdown
- O/P voltage with outo-recovery, > 150% rated power or short circuit is constant current limiting, if o/p drop to 40% rating output voltage then shutdown and auto-recover 5 time, if faul condition not remove in this 5 time, the system well be shutdown and re-power on to recover.
- OVER VOLTAGE 29 ~ 33V 56 ~ 65V
- Protection type: Latch-off mode, repower on to recover.
- OVER TEMPERATURE 95 ±5°C (TSW: detect on heatsink of power diode)
- Protection type: Shut down o/p voltage, recovers automatically after temperature goes down
ENVIRONMENT
- WORKING TEMP. -10 ~ +70°C (Refer to derating curve)
- Installation clearance: 40mm from top, 20mm from bottom, 5mm from the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
- WORKING HUMIDITY 20 ~ 95% RH non-condensing
- STORAGE TEMP. / HUMIDITY -40 ~ +85°C, 10 ~ 95% RH
- TEMP. COEFFICIENT ±0.03% / °C (0 ~ 50°C)
- VIBRATION 10 ~ 500Hz, 2G 10min. / 1cycle, 60min. each along X, Y, Z axes
SAFETY & EMC
- SAFETY STANDARDS UL 508 / TUV EN 60950-1
- WITHSTAND VOLTAGE I/P-O/P: 4242VDC, I/P-FG: 2121VDC, O/P-FG: 707VDC, O/P-DC OK: 707VDC
- ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG: >100M Ohms / 500VDC / 25°C / 70% RH
- EMI CONDUCTION & RADIATION EN55022 (CISPR22) Class B
- HARMONIC CURRENT EN61000-3-2, -3
- EMS IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN55024; EN61000-6-2; (EN50082-2);
- EN61204-3; heavy industry level; criteria A, MEET SEMI F47
- The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed that is still meets EMC directives.
OTHERS
- DC OK RELAY. CONTACT RATINGS (max) 60VDC / 0.3A, 30VDC / 1A, 30VAC / 0.5A resistive load
- MTBF 62.7K HRS (MIL-HDBK-217F)
- DIMENSION 55.5×125.2×99.8 mm (WxHxD)
- PACKING 0.9kg; 12pcs / 12.8kg
- COOLING Free air convection
All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature.
Mechanical Drawings
Block Diagram
DC OK Relay Contact
Contact Close | When the output voltage reaches the adjusted output voltage. |
---|---|
Contact Open | When the output voltage drop below 45% rated output voltage. |
Contact Ratings(max.) | 30V/1A resistive load |
Peak Load SW1 ON (Mode1) Default setting
T-peak presents while the unit is working within 110%~150%Rating output
power. See curve ” B ” for the variation in T-peak between output current and
holdup time. If T-peak is more than the time setting in curve “B”, the output
current will drop to the constant current limit (I-normal) that is 105% rating
power, meanwhile, I- normal and T-normal will be presenting. See curve “A” for
the timing back to I-Peak of T-normal and this Mode can use for easy 2-stage
battery charger.
Peak Load SW2 OFF (Mode2)
T-peak presents while the unit is working within 110%~150%Rating output power.
See curve ” B ” for the variation in T-peak between output current and holdup
time. If T-peak is more than the time setting in curve “B”, the output current
will be shut down for 3~4 sec, then auto-recovery.
Remote ON/OFF
The PS U can be turned ON/OF F by us ing the “Remote Control” function.
SW2 | INH+(3 PIN)/ INH-(4 PIN) | Output Status |
---|---|---|
OFF | SW ON (>2.5V) | ENABLE |
OFF | SW OFF (<0.8V) | DISABLE |
ON | SW ON (>2.5V) | DISABLE |
ON | SW OFF (<0.8V) | ENABLE |
Derating Curve
Output derating VS input voltage
Altech Corp.® , 35 Royal Road , Flemington, NJ 08822-6000 , Phone (908)806-9400 , FAX (908)806-9490
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>