PREFACE

This SERVICE MANUAL provides various service information, including the mechanical and electrical parts etc. This room air conditioner was manufactured and assembled under a strict quality control system.
The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit

1.1 SAFETY PRECAUTIONS

  1. When servicing the unit, set the ROTARY SWITCH or POWER SWITCH to OFF and unplug the power cord.

  2. Observe the original lead dress.
    If a short circuit is found, replace all parts which have been overheated or damaged by the short circuit.

  3. After servicing the unit, make an insulation resistance test to protect the customer from being exposed to shock hazards

1.2 INSULATION RESISTANCE TEST

  1. Unplug the power cord and connect a jumper between 2 pins (black and white).
  2. The grounding conductor (green or green & yellow) is to be open.
  3. Measure the resistance value with an ohm meter between the jumpered lead and each exposed metallic part on the equipment at all the positions (except OFF or O) of the ROTARY SWITCH.
  4. The value should be over 1MΩ

1.3 SPECIFICATIONS
1.3.3 FOR R1801H

MODELS
ITEMS| R1801H| R1803H| REMARK
---|---|---|---
POWER SUPPLY| 10.208/ 230V. 60Hz|
COOLING| CAPACITY (Btu/h)| 17,500/ 18,000|
INPUT (W)| 1,940!2,000| 1.800/1,850|
RUNNING CURRENT (A)| 9.6/ 9.0| 9.0/8.3|
E.E.R. (BtuIW.h)| 9.0| 10.|
HEATING| CAPACITY (Btu/h)| 9,800/ 12,000|
INPUT (W)| 3,100/3,670|
RUNNING CURRENT (A)| 15.0/ 16.0|
OPERATING TEMPERA- TURF| COOLING| INDOOR (‘C)| 26.7 (DB) 19.4 (WB)|
OUTDOOR (‘C)| 35 (DB) 23.9 (WB)|
HEATING| INDOOR (t)| 21.1 (DB) 15.6 (WB)|
OUTDOOR (°C)| 8.3 (DB) 6.1 (WB)|
REFRIGERANT (R-22| CHARGE(g)| 740 (26.1 OZ)| 750(26.5 OZ)|
EVAPORATOR| 3 ROW 15 STACKS| 3 ROW 18 STACKS| LOUVF_REDFN TYPE
CONDENSER| 2 ROW 19 STACKS, L-BENDED TYPE
FAN, INDOOR| BLOWER|
FAN, OUTDOOR| PROPELLER TYPE FAN WITH SLINGER-RING|
FAN SPEEDS (FAN/COOLING/HEATING)| 1/2/2|
FAN MOTOR| 6 POLES|
OPERATION CONTROL| ROTARY SWITCH|
ROOM TEMP. CONTROL| THERMOSTAT|
AIR DIRECTION CONTROL| VERTICAL LOUVER (RIGHT & LEFT)|
HORIZONTAL LOUVER (UP & DOWN)|
CONSTRUCTION| SLIDE IN-OUT CHASSIS|
ELECTRIC HEATER| 3.5 KW. 230V|
PROTECTOR| COMPRESSOR| INTERNAL OVERLOAD PROTECTOR|
FAN MOTOR| INTERANL THERMAL PROTECTOR|
ELECTRIC HEATER| FUSE LINK. BIMETAL THERMOSTAT|
POWER CORD| 1.6m (3 WIRE WITH GROUDING)|
ATTACHMENT PLUG (CORD-CONNECTED TYPE)|
DRAIN SYSTEM| DRAIN PIPE OR SPLASHED BY FAN SLINGER|
NET WEIGHT (lbs/kg)| 123/ 56|
OUTSIDE DIMENSION
(WxHxD)| (inch)| 26 x 1622/32 x 269/to|
(mm)| 660 x 428 x 675|

NOTE: Please refer to Label Quality on the product since this specification may be changed for improving performance

1.4 FEATURES

  • Designed for cooling only.
  • Powerful and quiet cooling.
  • Slide-in and slide-out chassis for the simple installation and service.
  • Reversible inlet grille
  • Side air-intake, side cooled-air discharge.
  • Built in adjustable THERMOSTAT.
  • Washable one-touch filter.
  • Compact size

1.5 CONTROL LOCATIONS
1.5.1 COOLING ONLY MODEL
VENTILATION
The ventilation lever must be in the CLOSE position in order to maintain the best cooling conditions. When a fresh air is necessary in the room, set the ventilation lever to the OPEN position.
The damper is opened and room air is exhausted.
NOTE: Before using the ventilation feature, make the lever, as shown. First, pull down part to horizontal line with part .

THERMOSTAT
Thermostat will automatically control the temperature of the room. Select the higher number for the lower temperature of the room. The temperature is selected by positioning the knob to the desired position.
The 5 or 6 position is a normal setting for average conditions.

• OPERATION
OFF : Turns the air conditioner off.
MED FAN : Permits the medium fan speed operation without cooling.
LOW FAN : Permits the low fan speed operation without cooling.
HIGH COOL: Permits cooling with the high fan speed operation.
MED COOL : Permits cooling with the medium fan speed operation.
LOW COOL: Permits cooling with the low fan speed operation

• AUTO SWING
ON : Air swing is operated while OPERATION knob is set to the COOL position.
OFF :Stops the operation of air swing.

1.5.2 COOLING AND HEATING MODEL
• CAUTION
When the air conditioner has been performing its cooling operation and is turned off or set to the fan position, wait at least 3 minutes before resetting to the cooling operation again

THERMOSTAT
Turn the thermostat control to the desired setting. The centrol position is a normal setting for average conditions. You can change this setting, if necessary, in accordance with your temperature preference.
The thermostat automatically controls cooling or heating, but the fan runs continuously whenever the air conditioner is in operation. If the room is too warm, turn the thermostat control clockwise. If the room is too cool, turn the themostat control anticlockwise.

OPERATION
OFF ( ) :Turns the air conditioner off.
FAN ( ) : Permits the low fan speed operation without cooling (heating).
LOW COOL ( ) : Permits cooling with the low fan speed operation.
HIGH COOL( ) : Permits cooling with the high fan speed operation.
LOW HEAT ( ) : Permits heating with the low fan speed operation.
HIGH HEAT ( ) : Permits heating with the high fan speed operation.

• AUTO SWING
ON : Starts the operation of air swing.
OFF : Stops the operation of air swing.
• Before you turn the unit off, please press the Auto Swing switch to off

A slight heat odor may come from the unit when first switching to HEAT after the cooling season is over. This odor, caused by fine dust particles on the heater, will disappear quickly.

1.5.3 COOLING ONLY MODEL WITH TOUCH TYPE

Precaution: The Remote Control unit will not function properly if strong light strikes the sensor window of the air conditioner or if there are obstacles between the Remote Control unit and the air conditioner

  1. POWER BUTTON
    Operation starts, when this button is pressed and stops when you press the button again.

  2. OPERATION MODE SELECTION BUTTON
    Select Cooling, or Fan or Dehumidification(Dry) mode with button. (Dry mode is not to all models.)

  3. ON/OFF TIMER BUTTON
    Set the time of starting and stopping operation. The timer is set by 1 hour.

  4. FAN SPEED SELECTOR
    Select the fan speed in three steps.
    – High [F3] ➔ Low[F1] ➔ Med[F2]➔ High[F3]… .

  5. ROOM TEMPERATURE SETTING BUTTON
    Control the room temperature within a range of 60°F to 86°F by 1°F.

  6. ENERGY SAVER
    The fan stops when the compressor stops cooling.
    Approximately every 3 minutes the fan will turn on and check the room air to determine if cooling is needed.

  7. AUTO SWING BUTTON
    Control the horizontal air direction by air swing system

DISASSEMBLY INSTRUCTIONS

— Before the following disassembly, POWER SWITCH is set to OFF and disconnected the power cord

2.1 MECHANICAL PARTS
2.1.1 FRONT GRILLE

  1. Open the inlet grille upward or downward.
  2. Remove the screw which fastens the front grille.
  3. Pull the front grille from the right side.
  4. Remove the front grille. (See Fig. 1)
  5. Re-install the component by referring to the removal procedure.
    NOTE: Mark ∆ of inlet grille means opening direction.

2.1.2 CABINET

  1. After disassembling the FRONT GRILLE, remove the screws which fasten the cabinet at both sides.
    Keep these for later use.

  2. Remove the two screws which fasten the cabinet at back. (See Fig. 2)

  3. Pull the base pan forward

2.1.3 CONTROL BOX

  1. Remove the front grille. (Refer to section 2.1.1)
  2. Pull the base pan forward so that you can remove the 2 screws which fasten the cover control at the right side. (See Fig. 3)
  3. Remove the 3 screws which fasten the control box. (See Fig. 3)
  4. Discharge the capacitor by placing a 20,000 ohm resistor across the capacitor terminals.
  5. Disconnect two wire housings in the control box.
  6. Pull the control box forward completely.
  7. Re-install the components by referring to the removal procedure. (See Fig. 3)
    (Refer to the circuit diagram found on page 28~31 in this manual and on the control box.

2.2 AIR HANDLING PARTS
2.2.1 COVER (AT THE TOP)

  1. Remove the front grille. (Refer to section 2.1.1)
  2. Remove the cabinet. (Refer to section 2.1.2)
  3. Remove 11 screws which fasten the brace and covers.
  4. Remove the covers and the brace. (See Fig. 4)
  5. Re-install the components by referring to the removal procedure, above

2.2.2 BLOWER

  1. Remove the cover. (Refer to section 2.2.1)
  2. Remove the 3 screws which fasten the evaporator at the left side and the top side. (See Fig. 4)
  3. Move the evaporator sideward carefully.
  4. Remove the 2 terminals carefully (See Fig. 5, Electric Heater Model only)
  5. Remove the 3 screws which fasten the Heater Cover. (See Fig. 5, Electric Heater Model only)
  6. Remove the Heater Cover. (See Fig. 5, Electric Heater Model only)
  7. Remove the orifice from the air guide carefully. (See Fig. 6, Except Electric Heater Model)
  8. Remove the clamp which secures the blower with plier. (See Fig. 6)
  9. Remove the blower with plier or your hand without touching blades. (See Fig. 7)
  10. Re-install the components by referring to the removal procedure, above

2.2.3 FAN

  1. Remove the cabinet. (Refer to section 2.1.2)

  2. Remove the brace and shroud cover.
    (Refer to section 2.2.1)

  3. Remove the side cover with 2 screws.
    (See Fig. 8(b))

  4. Remove the 5 or 6 screws which fasten the condenser.

  5. Move the condenser sideways carefully.

  6. Remove the clamp which secures the fan.

  7. Remove the fan. (See Fig. 8(a), 8(b))

  8. Re-install the components by referring to the removal procedure, above

2.2.4 SHROUD

  1. Remove the fan. (Refer to section 2.2.3)
  2. Remove the 2 screws which fasten the shroud.
  3. Remove the shroud. (See Fig. 9(a), 9(b))
  4. Re-install the component by referring to the removal procedure, above

2.3 ELECTRICAL PARTS
2.3.1 MOTOR

  1. Remove the cabinet. (Refer to section 2.1.2)
  2. Remove the cover control and disconnect a wire housing in control box. (Refer to section 2.1.3)
  3. Remove the blower. (Refer to section 2.2.2)
  4. Remove the fan. (Refer to section 2.2.3)
  5. Remove the 4 screws which fasten the motor. (See Fig. 10(a), 10(b))
  6. Remove the motor.
  7. Re-install the components by referring to the removal procedure, above

2.3.2 COMPRESSOR

  1. Remove the cabinet. (Refer to section 2.1.2)

  2. Discharge the refrigerant system using FreonTM Recovery System.
    If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM . Leave the valve in place after servicing the system.

  3. Disconnect the 3 leads from the compressor.

  4. After purging the unit completely, unbraze the suction and discharge tubes at the compressor connections.

  5. Remove the 3 nuts and the 3 washers which fasten the compressor. (See Fig. 11)

  6. Remove the compressor.

  7. Re-instill the components by referring to the removal procedure, above

2.3.3 CAPACITOR

  1. Remove the control box. (Refer to section 2.1.3)
  2. Remove the screw and knobs which fasten the display panel.
  3. Disconnect the 2 leads from the rocker switch and remove the panel.
  4. Remove a screw and unfold the control box. (See Fig. 12)
  5. Remove the screw and the clamp which fastens the capacitor. (See Fig. 12)
  6. Disconnect all the leads of capacitor terminals.
  7. Re-install the components by referring to the removal procedure, above

2.3.4 POWER CORD

  1. Remove the control box. (Refer to section 2.1.3)

  2. Unfold the control box. (Refer to section 2.3.3)

  3. Disconnect the grounding screw from the control box.

  4. Disconnect 2 receptacles.

  5. Remove a screw which fastens the clip cord.

  6. Pull the power cord. (See Fig. 13)

  7. Re-install the component by referring to the removal procedure, above.
    (Use only one ground-marked hole for ground connection.)

  8. If the supply cord of this appliance is damaged, it must be replaced by the special cord.
    (The special cord means the cord which has the same specification marked on the supply cord fitted to the unit.

2.3.5 THERMOSTAT

  1. Remove the control box. (Refer to section 2.1.3)
  2. Unfold the control box. (Refer to section 2.3.3)
  3. Remove the 2 screws which fasten the thermostat.
  4. Disconnect all the leads of thermostat terminals.
  5. Remove the thermostat. (See Fig. 14)
  6. Re-install the components by referring to the removal procedure, above.

2.3.6 ROTARY SWITCH

  1. Remove the control box. (Refer to section 2.1.3)
  2. Unfold the control box. (Refer to section 2.3.3)
  3. Remove 2 screws which fasten the rotary switch.
  4. Disconnect all the leads of the rotary switch terminals.
  5. Remove the rotary switch. (See Fig. 15)
  6. Re-install the components by referring to the above removal procedure, above

2.3.7 SYNCHRONOUS MOTOR

  1. Remove the control box. (Refer to section 2.1.3)
  2. Unfold the control box. (Refer to section 2.3.3)
  3. Remove the crankshaft.
  4. Disconnect all the leads of the synchronous motor.
  5. Remove the 2 screws which fasten the synchronous motor. (See Fig. 16)
  6. Re-install the components by referring to the removal procedure, above

2.4 REFRIGERATION CYCLE

CAUTION
Discharge the refrigerant system using FreonTM Recovery System.
If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system

2.4.1 CONDENSER

  1. Remove the cabinet. (Refer to section 2.1.2)

  2. Remove the brace and the shroud cover.
    (Refer to section 2.2.1)

  3. Remove 2 screws which fasten the side cover.(See Fig. 17(b))

  4. Remove the 5 or 6 screws which fasten the condenser.

  5. After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections.

  6. Remove the condenser.

  7. Re-install the components by referring to notes. (See Fig. 17

2.4.2 EVAPORATOR

  1. Remove the cabinet. (Refer to section 2.1.2)

  2. Remove the top cover and the brace.
    (Refer to section 2.2.1)

  3. Discharge the refrigerant completely.

  4. Remove the 3 screws which fasten the evaporator at the left side and the top side.

  5. Move the evaporator sideward carefully and then unbraze the interconnecting tube at the evaporator connectors.

  6. Remove the evaporator.

  7. Re-install the components by referring to notes. (See Fig. 18

2.4.3 CAPILLARY TUBE

  1. Remove the cabinet. (Refer to section 2.1.2)
  2. Remove the brace. (Refer to section 2.2.1)
  3. After discharging the refrigerant completely, unbraze the interconnecting tube at the capillary tube.
  4. Remove the capillary tube.
  5. Re-install the components by referring to notes

NOTES
— Replacement of the refrigeration cycle.

  1. When replacing the refrigeration cycle, be sure to discharge the refrigerant system using a FreonTM recovery System.
    If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.

  2. After discharging the unit completely, remove the desired component, and unbrace the pinch-off tubes.

  3. Solder service valves into the pinch-off tube ports, leaving the valves open.

  4. Solder the pinch-off tubes with Service valves.

  5. Evacuate as follows.

  1. Connect the vacuum pump, as illustrated Fig. 19A.
  2. Start the vacuum pump, slowly open manifold valves A and B with two full turns counterclockwise and leave the valves closed.
    The vacuum pump is now pulling through valves A and B up to valve C by means of the manifold and entire system.
    CAUTION
    If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise.
    This will keep oil from foaming and being drawn into the vacuum pump.
  3. Operate the vacuum pump for 20 to 30 minutes, until 600 microns of vacuum is obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.
  4. Remove the hose from the vacuum pump and place it on the charging cylinder. See Fig. 19B. Open valve C.
    Discharge the line at the manifold connection.
  5. The system is now ready for final charging
  1. Recharge as follows :
  1. Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened.
  2. Connect the charging cylinder as shown in Fig. 19B. With valve C open, discharge the hose at the manifold connection.
  3. Open valve A and allow the proper charge to enter the system. Valve B is still closed.
  4. If more charge is required, the high-side will not take it. Close valve A.
  5. With the unit running, open valve B and add the balance of the charge.
    a. Do not add the liquid refrigerant to the Low-side.
    b. Watch the Low-side gauge; allow pressure to rise to 30 lbs.
    c. Turn off valve B and allow pressure to drop.
    d. Repeat steps B and C until the balance of the charge is in the system.
  6. When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection

Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pinch-off tool capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve

INSTALLATION

3.1 HOW TO INSTALL THE UNIT

  1. To avoid vibration and noise, make sure the unit is installed securely and firmly.

  2. Install the unit where the sunlight does not shine directly on the unit.
    If the unit receives direct sunlight, build an awning to shade the cabinet.

  3. There should be no obstacle, like a fence, within 20″ which might restrict heat radiation from the condenser.

  4. To prevent reducing performance, install the unit so that louvers of the cabinet are not blocked.

  5. Install the unit a little obliquely outward not to leak the condensed water into the room (about 1/2″ or 1/4 bubble with level).

  6. Install the unit with its bottom portion 30~60″ above the floor level.

  7. Stuff the foam between the top of the unit and the wall to prevent air and insects from getting into the room.

  8. The power cord must be connected to an independent circuit. The green wire must be grounded.

  9. Connect the drain tube to the base pan hole in the rear side if you need to drain (consult a dealer).
    Plastic hose or equivalent may be connected to the drain tube

3.2 HOW TO USE THE REVERSIBLE INLET GRILLE
The grille is designed to clean the filter both upward and downward.
A. BEFORE ATTACHING THE FRONT GRILLE TO THE CABINET, IF YOU WANT TO PULL OUT THE FILTER UPWARD;

  1. Open the inlet grille slightly (a).
  2. Turn inside out the front grille (a).
  3. Disassemble the inlet grille from the front grille with separating the hinged part by inserting a straight type screw-driver tip (b).
  4. Then, rotate the inlet grille 180 degrees and insert the hooks into bottom holes of the front grille.
  5. Insert the filter and attach the front grille to the cabinet

B. IF YOU WANT TO PULL OUT THE FILTER DOWNWARD;
The grille is already designed for that way.

3.3 WINDOW REQUIREMENTS
NOTE : All supporting parts should be secured to firm wood, masonry, or metal.
The models of the specific area don’t contain installation kit.

3.3.1 WINDOW REQUIREMENTS

  1. This unit is designed for installation in standard double hung windows with actual opening widths from 29″ to 41″.
    The top and bottom window sashes must open sufficiently to allow a clear vertical opening of 18″ from the bottom of the upper sash to the window stool.

  2. The stool offset (height between the stool and sill) must be less than 1 1/4″

3.4 INSTALLATION KITS CONTENTS

3.5 SUGGESTED TOOL REQUIREMENTS
SCREWDRIVER(+, -), RULER, KNIFE, HAMMER, PENCIL, LEVEL
3.5.1 PREPARATION OF CHASSIS

  1. Remove the screws which fasten the cabinet at both sides and at the back. Keep these two screws which fasten the cabinet at both sides for later use.
  2. Slide the unit out from the cabinet by gripping the base pan handle and pulling forward while bracing the cabinet.
  3. Cut the window sash seal to the proper length. Peel off the backing and attach the Foam-PE to the underside of the window sash.
  4. Remove the backing from Foam-PE with 3 holes and attach it to the bottom of the Top retainer bar.
  5. Attach the Top retainer bar onto the top of the cabinet with 3 screws (Type A).
  6. Insert the Frame guides into the bottom of the cabinet.
  7. Insert the Frame Curtain into the Top retainer bar and Frame guides.
  8. Fasten the curtains to the unit with 10 screws (Type A) at both sides

3.6 CABINET INSTALLATION

  1. Open the window. Mark a line on the center of the window stool between the side window stop moldings.
    Loosely attach the sill bracket to the support bracket using the carriage bolt and the lock nut.

  2. Attach the sill bracket to the window sill using the screws (Type B).
    Carefully place the cabinet on the window stool and align the center mark on the bottom front with the center line marked window stool.

  3. Using the M-screw and the lock nut, attach the support bracket to the cabinet track hole. Use the first track hole after the sill bracket on the outer edge of the window sill.
    Tighten the carriage bolt and the lock nut. Be sure the cabinet slants outward. CAUTION: Do not drill a hole in the bottom pan. The unit is designed to operate with approximately 1/2″ of water in bottom pan.

  4. Pull the bottom window sash down behind the Top retainer bar until they meet
    NOTE: 1. Do not pull the window sash down so tightly that the movement of Frame curtain is restricted. Attach the cabinet to the window stool by driving the screws (Type B) through the cabinet into window stool.
    2. The cabinet should be installed with a very slight tilt downward toward the outside.

  5. Pull each Frame curtain fully to each window sash track, and pull the bottom window sash down behind the Top retainer bar until it meets.

  6. Attach each Frame curtain the window sash by using screws (Type C). (See Fig. 29)

  7. Slide the unit into the cabinet. (See Fig. 30)
    CAUTION: For security purpose, reinstall screws (Type A) at cabinet’s sides.

  8. Cut the Foam-strip to the proper length and insert between the upper window sash and the lower window sash. (See Fig. 31)

  9. Attach the Window locking bracket with a screw (Type C). (See Fig. 32

  10. Attach the front grille to the cabinet by inserting the tabs on the grille into the tabs on the front of the cabinet. Push the grille in until it snaps into place. (See Fig.33)

  11. Lift the inlet grille and secure it with a screw (Type A) through the front grille. (See Fig. 33)

  12. Window installation of room air conditioner is now completed.

TROUBLESHOOTING GUIDE

4.1 OUTSIDE DIMENSIONS

4.2 PIPING SYSTEM

Following is a brief description of the important components and their functions in the refrigeration system.
Refer to Fig. 35 to follow the refrigeration cycle and the flow of the refrigerant in the cooling cycle

4.3 TROUBLESHOOTING GUIDE
In general, possible trouble is classified in two causes.
The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit runs but poor cooling

COMPLAINT CAUSE REMEDY
Fan motor will not run. No power Check voltage at outlet. Correct if none.
Power supply cord Check voltage to rotary switch. If none. check power supply

cad. Replace cord if circuit is open.
Rotary switch| Check switch continuity. Refer to wiring diagram for terminal identification. Replace switch if defective.
Wire disconnected or connection loose| Connect wire. Refer to wiring diagram for terminal identification. Repair or replace loose terminal.
Capacitor (Discharge capacitor before testing.)| Test capacitor.
Replace if not within ±10% of manufacturers rating. Replace if shorted. open. or damaged.
Will not rotate| Fan blade hitting shroud or blower wheel hitting scroll. Realign assembly.
Units using stinger ring condenser fans must have ‘A to 5/16 inch clearance to the base. If it is hitting the base. shim up the bottom of the fan motor with mounting screw(s).
Check fan motor bearings: if motor shaft will not rotate. replace the motor.
Fan motor runs intermittently| Revolves on overload.| Check voltage. See limits on this page. If not within limits. call an electrician.
Test capacitor.
Check bearings. Does the fan blade rotate freely? If not. replace fan motor.
Pay attention to any change from high speed to low speed. If the speed does not change. replace the motor.
Fan motor noise.| Grommets| Check grommets: if worn or missing, replace them.
Fan| If cracked. out of balance. or partially missing. replace it.
Blower| If cracked. out of balance. or partially missing. replace it.
Loose set screw| Tighten it.
Worn bearings| If knocking sounds continue when running or loose. replace the motor. If the motor hums or noise appears to be internal while running. replace motor.
Compressor will not run, but fan motor runs.| Voltage| Check voltage. See the limits on the preceding. page. If not within limits, call an electrician.
Wiring| Check the wire connections, if loose, repair or replace the terminal. If wires are off, refer to wiring diagram for identification, and replace. Check wire locations. If not per wiring diagram, correct.
Rotary| Check for continuity, refer to the wiring diagram for terminal identification. Replace the switch if circuit is open.
Thermostat| Check the position of knob If not at the coldest setting, advance the knob to this setting and restart unit.
Check continuity of the thermostat. Replace thermostat if circuit is open.
Capacitor (Discharge capacitor before
servicing.)| Check the capacitor.
Replace if not within ±10% of manufacturers rating. Replace if shorted, open, or damaged.
Compressor| Check the compressor for open circuit or ground. If open or grounded, replace the compressor.
Overload| Check the compressor overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool it, and retest.)
Compressor cycles on overload.| Voltage| Check the voltage. See the limits on the preceding page. If not within limits, call an electrician.
Overload| Check overload, if externally mounted.
Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.)
Fan motor| If not running, determine the cause. Replace if required.
Condenser air flow restriction| Remove the cabinet. inspect the interior surface of the condenser; if restricted, clean carefully with a vacuum cleaner (do not damage fins) or brush. Clean the interior base before reassembling.
Condenser fins (damaged)| If condenser fins are closed over a large area on the coil surface, head pressures will increase, causing the compressor to cycle. Straighten the fins or replace the coil.
Compressor cycles on overload| Capacitor| Test capacitor.
Wiring| Check the terminals. If loose, repair or replace
Refrigerating system| Check the system for a restriction
Insufficient cooling or heating| Air filter| If restricted, clean of replace
Exhaust damper door| Close if open.
Unit undersized| Determine if the unit is properly sized for the area to be cooled.
Excessive noise| Blower or fan| Check the set screw or clamp. If loose or missing, correct. If the blower or fan is hitting air guide, rearrange the air handling parts.
Copper tubing| Remove the cabinet and carefully rearrange tubing not to contact cabinet, compressor, shroud, and barrier
Auto air-swing fails.| Rotary switch.| Set the knob to HIGH COOL or LOW COOL while rocker switch is ON.
Wiring| Check terminals. If loose, repair or replace.
Synchronous motor.| Check the synchronous motor for open circuit.

MODEL : R1803H

NO. DESCRIPTION Q’TY PER SET
1 POWER CORD 1
2 ROTARY SWITCH 1
3 FAN MOTOR 1
4 CAPACITOR 1
5 THERMOSTAT 1
6 OVERLOAD PROTECTOR 1
7 COMPRESSOR 1
8 ELECTRIC HEATER 1
9 SYNCHRONOUS MOTOR 1

EXPLODED VIEW

• MODEL: R1803H

LOCATION NO. DESCRIPTION PART NO. REMARK
R1801H R1803H LWC243NSABO
130410 BASE ASSEMBLY, SINGLE 3041A30002B 3041A30002B
130910 CABINET ASSEMBLY, SINGLE 3091AR6057A 3091AR6057A
135312 GRILLE ASSEMBLY, FRONT (SINGLE) 3531A20005H 3531A20005H
3531A20073E R
135313 GRILLE, INLET 3530AR1603A 3530AR1603A
135510 COVER ASSEMBLY, CONTROL 3550AR7245A 3550AR7245A
137215 PANEL ASSEMBLY, CONTROL 3721A200020 3721A200020
146812 MOTOR ASSEMBLY, SYNC. 2H01102A 21-101102A
147581-1 LOUVER, HORIZONTAL 4758AR7264C 4758AR7264C
147581-2 LOUVER, HORIZONTAL 4758AR7278C 4758AR7278C
147582 LOUVER, VERTICAL 4758AR6157A 4758AR6157A
148000 BRACE 4800AR7272A 4800AR7272A
149410 KNOB ASSEMBLY 4941A30001A 4941A30001A
149980 SHROUD 4998AR1597A 4998AR1597A
152302 FILTER(MECH), A/C 5231AR6159A 5231AR6159A
249950 CONTROL BOX ASSEMBLY 4995A20051A 4995A20051A
264110 POWER CORD ASSEMBLY 2H00677U 2H00677U
266002 SWITCH,ROCKER
266003 SWITCH, ROTARY 2H00598F 2H00598F
269310 THERMOSTAT, ASSEMBLY 2H01127B 2H01127B
346811 MOTOR ASSEMBLY, SINGLE 4681AR6033B 4681AR6033K
349001 DAMPER, VENTILATION 4900AR7265A 4900AR7265A
349480 ORIFICE
349600 MOUNT, MOTOR 4960AR1596A 4960AR1596A
35211A TUBE ASSEMBLY, SUCTION 5211A30065A 5211A20204A
352111 TUBE ASSEMBLY, CONNECTOR 5211AR7059C 5211AR7059C
352113 TUBE ASSEMBLY, DISCHARGE 5211A30066A 5211A30066K
352115 TUBE EVAPORATOR 5210A30009C/D 5210A203516/52B
352390 AIR GUIDE ASSEMBLY 5239A20001G 5239A20001G
354210 EVAPORATOR ASSEMBLY, FIRST 5421A20017B 5421A20059A
359012 FAN ASSEMBLY, BLOWER 5834AR1599B 5834AR1599B
550140 ISOLATOR, COMP 4H00982C 4H00982C
552101 TUBE CAPILLARY 3H03750S 5210A30040N
552102 TUBE,CAPILLARY BEND
554031 CONDENSER ASSEMBLY, BENT 5403A20004F 5403A20004F
554160 COMPRESSOR 5417AR2256E 5416AR20003J
559010 FAN ASSEMBLY, AXIAL 5900AR1508A 5900AR1508A
753000 HEATER, ELECTRIC 5300AR1571B 5300AR1571B
753010 HEATER ASSEMBLY, ELECTRIC 5301A30001A 5301A30001A
WOCZZ CAPACITOR, DRAWING 6120AR2359E 6120AR2359E
W48602 CLAMP SPRING 3H02932C 3H02932C

NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer’s request.
(GCSC WEBSITE http://biz@LGservice.com)

P/No.: 3828A20140A
January, 2005
Printed in Korea

Documents / Resources

| Goldstar R1803H Room Air Conditioner [pdf] Instruction Manual
R1803H Room Air Conditioner, R1803H, Room Air Conditioner, Air Conditioner, Conditioner
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals