KIRBY KSF2000-4 DROP-IN Packaged Refrigeration Units Owner’s Manual
- July 26, 2024
- KIRBY
Table of Contents
KSF2000-4 DROP-IN Packaged Refrigeration Units
“`html
Specifications
-
Unit Type: KP Low Profile Series, KS Standard
Profile Series -
Release Number: 4
-
Refrigerant: R134a for M/T & R404A for
L/T -
Unit Capacity: Varies based on models
-
Supply: 240V/1Ph
Product Usage Instructions
Installation
Our packaged refrigeration units are designed to be ‘plug and
play’ systems, making them easy to install. Follow these steps for
installation:
-
Place the unit in the desired location with proper
ventilation. -
Connect the unit to a suitable power source (240V/1Ph).
-
Ensure the refrigerant charge matches the unit
specifications. -
Turn on the unit and set the desired temperature using the
Dixell control panel.
Maintenance
To ensure optimal performance, regular maintenance is
recommended:
-
Clean the unit and surrounding area to prevent dust
buildup. -
Check refrigerant levels and top up if necessary.
-
Inspect electrical connections for any signs of damage.
Troubleshooting
If you encounter any issues with the unit, refer to the user
manual for troubleshooting steps. If problems persist, contact
customer support for assistance.
FAQ
Q: What refrigerants are used in the medium and low-temperature
units?
A: The medium-temperature units use R134a, while the
low-temperature units use R404A.
Q: What is the electrical supply requirement for these
units?
A: The units require a supply of 240V/1Ph for operation.
“`
KIRBY® DROP-IN
Packaged Refrigeration Units
Our `plug and play’ systems come ready to run and easy to install
Exclusively distributed by
KIRBY® DROP-IN
Packaged Refrigeration Units
Introduction
The Kirby® Drop-in unit range will make it easier for you to install and
complete your job.
These `plug and play’, feature-packed systems are supplied complete ready to
run and
easy to install.
It means the hard work is taken out of the job, so you can be on your way,
sooner. Now supplied with a Dixell control installed as standard on all
models.
Features & Benefits
The Kirby® Drop-In Packaged Refrigeration Units offer:
· Evaporator coil corrosion protection, liquid line dryer, capillary tube
refrigerant control, pressure control & Dixell electronic control on all units
· Medium Temperature Units feature off cycle defrost only · Low Temperature
Units feature electric defrost with temperature switch termination and a
pressure safety switch · Fully wired with 3-pin domestic cable plug for all
units · All models use CFC-free foam insulation · New and improved, slimline
electrical box · Units are ready to install straight from the box ·
Encapsulated pressure controls · 3 different temperature probes
(one for the evaporator coil, one for the condenser coil, and one for the room
temperature) · All tubes in the top half of the drop-in units have been
modified and re-modelled · Tube support and saddles for the drier to reduce
vibration and noise · All low temperature units are fitted with a suction
accumulator · All models come with a high efficiency internal float oil
separator
Kirby® Drop-In Packaged Refrigeration Units Nomenclature
KS
C
Application
C = Cool Room Range, M/T F = Freezer Room Range, L/T
Unit Type
KP Low Profile Series KS Standard Profile Series
1800
4
Release Number
Unit Capacity (Watts) R134a for M/T & R404A for L/T eg: 1800 = 1800 Watts
2
13 23 50 | kirbyhvacr.com.au
PRODUCT NUMBER
KPC800-6 KPC1000-6 KPC1400-6 KPC1700-6
KSC2000-6 KSC2700-6 KSC3500-6
AMBIENT TEMP. (°C)
35 45 35 45 35 45 35 45
35 45 35 45 35 45
0
690 570 920 760 1,270 1,090 1,470 1,260
1,870 1,600 2,380 1,980 3,030 2,570
DROP-IN PACKAGED REFRIGERATION UNITS R134a Medium Temperature Performance Data
CAPACITY (W)
AIR ON TEMPERATURE
2
4
6
8
10
MEDIUM TEMPERATURE APPLICATION LOW PROFILE
750
810
870
940
1,010
630
680
740
800
870
990
1,080
1,160
1,260
1,360
840
920
1,000
1,090
1,180
1,370
1,480
1,590
1,710
1,830
1,180
1,280
1,380
1,490
1,600
1,570
1,690
1,810
1,950
2,090
1,360
1,460
1,570
1,700
1,820
MEDIUM TEMPERATURE APPLICATION STANDARD
2,010
2,170
2,310
2,500
2,690
1,740
1,890
2,050
2,210
2,380
2,580
2,800
3,030
3,260
3,510
2,170
2,380
2,590
2,810
3,040
3,290
3,550
3,830
4,120
4,420
2,800
3,040
3,300
3,580
3,860
REFRIGERANT
CHARGE (gm)
AIR FLOW (l/s)
HORSEPOWER
910
165
1/3
1,000
235
3/8
1,190
270
5/8
1,190
270
3/4
1,710
388
1
1,990
750
1-1/4
2,420
760
1-1/2
PRODUCT NUMBER
AMBIENT TEMPERATIRE
(°C)
35 KPF1000-4
43
35 KPF1200-4
43
35 KSF1500-4
43
35 KSF2000-4
43
DROP-IN PACKAGED REFRIGERATION UNITS R404A Low Temperature Low Profile Performance Data
CAPACITY (W)
AIR ON TEMPERATURE
REFRIGERANT CHARGE (gm)
AIR FLOW (l/s)
-25
-20
-15
-10
LOW TEMPERATURE APPLICATION LOW PROFILE
455
645
870
1,060
975
235
290
460
680
905
555
790
1,065
1,295
820
235
355
565
830
1,110
735
1,050
1,410
1,720
1,450
530
470
745
1,100
1,470
950
1,355
1,820
2,220
1,500
750
610
965
1,420
1,900
HORSEPOWER
3/4 1 1-1/4 1-1/2
13 23 50 | kirbyhvacr.com.au
3
PRODUCT NUMBER
KPC800-6 KPC1000-6 KPC1400-6 KPC1700-6
KSC2000-6 KSC2700-6 KSC3500-6
KPF1000-4 KPF1200-4 KSF1500-4 KSF2000-4
SUPPLY (V/Ph)
240 / 1 240 / 1 240 / 1 240 / 1
240 / 1 240 / 1 240 / 1
240 / 1 240 / 1 240 / 1 240 / 1
DROP-IN PACKAGED REFRIGERATION UNITS Technical Data
ELECTRICAL DATA
LRA
RLA
MCC
HEIGHT
(A/Ph)
(A/Ph)
(A/Ph)
MEDIUM TEMPERATURE LOW PROFILE
13.9
3.9
4.9
500
14.4
4.4
5.4
577
31.9
4.6
5.5
577
35.9
6.4
8
577
MEDIUM TEMPERATURE STANDARD
35.8
5.8
7.5
950
44.8
8.7
11.2
996
44.8
9.7
12.5
1,057
LOW TEMPERATURE LOW PROFILE
30.0
4.2
7.7
577
36.0
6.7
8.9
577
43.0
7.9
10.9
964
43.0
10.6
14.1
996
DIMENSIONS WIDTH (mm)
890 1,117 1,117 1,117
705 1,150 1,150
1,117 1,117 705 1,150
DEPTH
500 507 507 507
595 730 730
507 507 595 730
WEIGHT (kg)
35 50 65 65
112 145 177
48 60 108 155
PRODUCT NUMBER
KPC800-6 KPC1000-6 KPC1400-6 KPC1700-6 KSC2000-6 KSC2700-6 KSC3500-6
KPF1000-4 KPF1200-4 KSF1500-4 KSF2000-4
A (mm)
810 1,030 1,030 1,030 645 1,070 1,070
1,030 1,030 645 1,070
B (mm)
420 420 420 420 535 645 645
420 420 535 645
DROP-IN PACKAGED REFRIGERATION UNITS Physical Data
C (mm)
890 1,117 1,117 1,117 705 1,150 1,150
1,117 1,117 705 1,150
D (mm)
E (mm)
MEDIUM TEMPERATURE
500
290
507
351
507
351
507
351
595
436
730
420
730
420
LOW TEMPERATURE
507
351
507
351
595
385
730
420
F (mm)
210 226 226 226 566 576 637
226 226 579 576
G (mm)
60 35 35 35 105 130 130
35 35 105 130
H (mm)
500 577 577 577 1,013 996 1,057
577 577 964 996
K (mm)
20 33 33 33 20 25 25
33 33 20 25
4
13 23 50 | kirbyhvacr.com.au
Standard
A PLUG C
DROP-IN PACKAGED REFRIGERATION UNITS Physical Data
K
GH F
E
F
B PLUG D
Low Profile
13 23 50 | kirbyhvacr.com.au
5
13 23 50
kirbyhvacr.com.au
Exclusively distributed by
KIRBYDROP-IN_0224
The contents of this brochure are copyright protected and may not be
reproduced in any form without the written consent of Kirby HVAC&R Pty Ltd
(T/A Kirby). Recommendations and advice regarding the use of the products
described in this publication are to be taken as a guide only and are given
without liability on the part of the company or its employees. As Kirby
continually improves its product range and processes,
Kirby reserves the right to change product specifications without any prior
notification. Please refer to the kirbyhvacr.com.au website for the latest
version of this publication. The purchaser should independently determine the
suitability of the product for the intended use and application and that the
product complies with relevant standards. Kirby accepts no responsibility for
loss or damage (direct or indirect and
including consequential loss, loss of profits or opportunity and economic
loss) however arising which results from any errors or omissions in the
information contained in this publication or arising from the use or
application of the information contained herein.
© Copyright 2021 Kirby HVAC&R Pty Ltd
Kirby HVAC&R Pty Ltd continually strives to improve products and processes. We reserve the right to modify product features without notice
6
1In3for2m3at5io0n is| ckoirrrebcythatvtaimcer.ocfopmrin.tainug.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>