CHIPKIN FS-8705-120 GenX And RM Instructions

June 26, 2024
CHIPKIN

CHIPKIN FS-8705-120 GenX And RM

salesgroup1@chipkin.com
Tel: +1 866 383 1657
© 2024 CHIPKIN AUTOMATION SYSTEMS

Zonex Description

  • The Zonex Driver allows the FieldServer to poll and set data from Zonex devices over Ethernet using the HTTP protocol. The Zonex Driver uses HTTP request.
  • The driver was developed to communicate with Zonex web-server enabled devices, specifically GenX and RM devices.
  • The FieldServer acts as an HTTP Client. When configured the FieldServer polls for data from Zonex GenX and RM devices. This data is stored on the FieldServer to be mapped to BACnet IP or simply to be viewed. The Zonex driver will also periodically attempt to write any changes that were made to writable BACnet IP objects.
  • The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer.

Connection Diagram

This block diagram lists describes how the FieldServer connects to Zonex devices and makes the data available over BACnet IP

Zonex Configuration

To configure the Zonex driver, from the home page, either visit the following link: http://{ip_address}/chipkinCore/ui/#/driver/zonex
Or click on the Zonex Configuration Card from the main menu at http://{IP_ADDRESS}/chipkinCore/ui/

To configure the FieldServer, follow the instructions below to auto-generate the Zonex polling and write tasks as well as the BACnet IP Server configuration

Meta-Configurer
On the Zonex Configuration page, use the form to fill out the details required to connect to the Zonex web server as the general BACnet information to assign to the FieldServer.

Zonex Parameters


Name

| ****

Function

| ****

Legal Values

---|---|---
Url| The url of the Zonex web server| Text, must be a valid Url (include the http://)
Read Interval| How often to poll the Zonex web server for data (in seconds)| 1-3600, 30
Write Interval| How often to write values to the Zonex web server when data has changed via BACnet (in seconds)| 1-3600, 5

Bolded values are defaults

BACnet IP Configuration


Name

| ****

Function

| ****

Legal Values

---|---|---
Adapter| The FieldServer network adapter to use for BACnet IP Communication| N1 (or N2 if using a 2 port FieldServer)
Port| The UDP port to use for BACnet IP| Any legal IP port value (1 – 65535); 47808
Node ID| The BACnet Device Identifier to assign to this FieldServer acting as a BACnet Server device| 0-4194302; 389001
COV Enable| Enables or disables COV (Change of Value) for this BACnet device| Checked = enabled,

Unchecked = disabled

Saving the Server Configuration
When the configuration is complete, click on the “Save Configuration” button to save. The FieldServer will query the Zonex web server and build both the Zonex Configurtion as well as the BACnetIP Server Configuration based on the findings.

If an error occurs, an error message will appear at the top of the web page in a red banner. For example:

ERR_BAD_REQUEST – Error [99] Request failed with status code 401.

If the configuration was generated successfully, a success message will appear at the top of the web page in a green banner, prompting the user to return to the MSA Diagnostic (http://{IPAddress}/htm/fsgui.htm) page to perform a System Reboot for the changes to take effect.

• Zonex Configuration Successfully Saved. Navigate to FS GUI and click System Reboot.

Click on the link to return to the FS GUI page and click the System Reboot:

Importing and Exporting Configurations

It is possible to export the current configuration to back it up or simply to make some edits.

How to Export the Configuration

  1. Goto the system configuration page http://{IP_ADDRESS}/chipkin/ui/#/chipkinConfiguration
  2. Click the Export Configuration button.

How to Import the Configuration
The file to import the configuration must be a zip file. The zip file should contain the following folders:

  • ae – this folder contains any configuration files for the Zonex configuration
  • pe – this folder contains one config.csv file for the pe configuration.

To make sure the folder directory is correct, do an Export first, then extract the files, edit them, then zip them up again. To import the configuration:

  1. Goto the system configuration page http://{IP_ADDRESS}/chipkin/ui/#/chipkinConfiguration
  2. Click the “Browse” button in the “Import/Export System Configuration” section and select the zip file containing the configuration to import.
  3. Click the “Import Configuration” button and wait for the configuration to finish importing.
  4. If successful, a success message will appear prompting a reboot of the Fieldserver for the changes to take effect.

Appendix A – Troubleshooting

Appendix A.1 – Debugging a Zonex Connection

  • If the FieldServer is not receiving any data, verify the URL of the Zonex web server.

  • Verify the network and ensure that the FieldServer has direct access to the Zonex web server (either both devices are on the same subnet, or the network has been setup to allow for proper routing)

  • Double check the FieldServer Network settings in the FS GUI (MSA Diagnostics page)

  • Verify comms by taking a wireshark log or a FieldServer diagnostics log.

Appendix B – Example Configurations

Appendix C – BACnet IP Objects

The following table contains the BACnet IP Objects generated in the Meta- Configurer. The configuration uses the BACnet Object Instance of the objects to sort the objects.
*Note: Depending on the configuration of the Zonex devices, there can be a large amount of generated BACnet objects which could cause the discovery of this BACnet device to take a long time.
Supported Object Types:
AI = Analog Input
AV = Analog Value
BI = Binary Input
BV = Binary Value
MI = Multi-State Input
MV = Multi-State Value

Name Object Type Object Instance Notes

SysDiagnotistic Data Points
Genx_SysDiag_Leaving Air| AI| 0|
Genx_SysDiag_Return Air| AI| 1|
Genx_SysDiag_Outside Air| AI| 2|
Genx_SysDiag_AC Status| MI| 3| Off = 1,

Vent = 2,

Cool =3,

Heat = 4,

Changeover = 5,

Air balance = 6, Abort to reset = 7

Genx_SysDiag_FDD/ADR| MI| 4| No alert = 1, FDD alert = 2, ADR = 3

FDD & ADR = 4

SysConfig Data Points
GenX_SysCon_Fan Mode| BV| 30| Active = On,

Inactive = Auto

StatDataID Data Points

represents the Damper number attached to GENX (1-20)

Genx_StatDataID#_LockStatus| MV| #000| Unlock = 1,
 |  |  | Lock 2 Degrees = 2,

Lock = 3

---|---|---|---
Genx_StatDataID#_CurrentRoomTemperature| AI| #001|
Genx_StatDataID#_OccupiedCool| AV| #002|
Genx_StatDataID#_OccupiedHeat| AV| #003|
Genx_StatDataID#_PriorityVote| AV| #004|
Genx_StatDataID#_ZoneStatus| MV| #005| Off = 1,

Vent = 2

Cool = 3

Heat = 4

Genx_StatDataID#_ZoneCall| MV| #006| Off = 1,

Vent = 2

Cool = 3

Heat = 4

Genx_StatDataID#_AutoMode| MV| #007| Off = 1,

Auto on (heat/cool) = 2, Cool only = 3,

Heat only = 4

Genx_StatDataID#_StatType| MI| #008| Wireless = 1,

Wire = 2,

Stand Alone(wire) = 3 WUC = 4,

EztouchX = 5,

SATouch = 6,

BLE = 7

Genx_StatDataID#_LeavingAir| AI| #009|
Genx_StatDataID#_ReturnAir| AI| #010|
Genx_StatDataID#_Humidity| AI| #011|
Genx_StatDataID#_OccupiedMode| BI| #012| Active = Occupied Inactive = Unoccupied
Genx_StatDataID#_ADR| BV| #013| Active = Enable Inactive = Disabled
RMD Data Points

represents the RM number (1-20)


RM#_RMD_Leaving Air| AI| #00000|
RM#_RMD_Return Air| AI| #00001|
RM#_RMD_AC Status| MI| #00002| Off = 1,

Vent = 2,

Cool =3,

Heat = 4,

Changeover = 5, Air balance = 6,

Abort to reset = 7

RM#_RMD_FDD/ADR| MI| #00003| No alert = 1, FDD alert = 2, ADR = 3

FDD & ADR = 4

RMC Data Points

represents the RM number (1-20)

RM#_RMC_Fan Mode| BV| #00030| Active = On,

Inactive = Auto

RMS Data Points

represents the RM (1-20)

$$ represents the Damper number attached to RM # (01-20)

RM#_RMS$$_LockStatus| MV| #$$000| Unlock = 1,

Lock 2 Degrees = 2,

Lock = 3

RM#_RMS$$_CurrentRoomTemperature| AI| #$$001|
RM#_RMS$$_OccupiedCool| AV| #$$002|
RM#_RMS$$_OccupiedHeat| AV| #$$003|
RM#_RMS$$_PriorityVote| AV| #$$004|
RM#_RMS$$_ZoneStatus| MV| #$$005| Off = 1,

Vent = 2

Cool = 3

Heat = 4

RM#_RMS$$_ZoneCall| MV| #$$006| Off = 1,

Vent = 2

Cool = 3

Heat = 4

---|---|---|---
RM#_RMS$$_AutoMode| MV| #$$007| Off = 1,

Auto on (heat/cool) = 2, Cool only = 3,

Heat only = 4

RM#_RMS$$_StatType| MI| #$$008| Wireless = 1,

Wire = 2,

Stand Alone(wire) = 3 WUC = 4,

EztouchX = 5,

SATouch = 6,

BLE = 7

RM#_RMS$$_LeavingAir| AI| #$$009|
RM#_RMS$$_ReturnAir| AI| #$$010|
RM#_RMS$$_Humidity| AI| #$$011|
RM#_RMS$$_OccupiedMode| BI| #$$012| Active = Occupied Inactive = Unoccupied
RM#_RMS$$_ADR| BV| #$$013| Active = Enable Inactive = Disabled

Revision History

This table summarizes the update history for this document. Please contact Chipkin for an updated version of this document if required.

DATE

|

RESP

| DOC. REV.|

COMMENT

---|---|---|---
21 Feb 2024| AF| 1| Created initial document
05 Mar 2024| AF| 2| Fixed Import/Export configuration url

18 Apr 2024

|

AF

|

3

| Removed Schedule data points Added Fan Mode point for RM

© 2024 CHIPKIN AUTOMATION SYSTEMS

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals