BOSCH 65kW Worcester Condens Commercial Boiler Instruction Manual
- June 10, 2024
- Bosch
Table of Contents
65kW Worcester Condens Commercial Boiler
“`html
Specifications
-
Outputs: 50kW, 65kW, 85kW, 100kW, 125kW, 145kW
-
Cascading: Up to 6 boilers per bank, providing up to 858.6kW at
50/30 per bank -
Applications: Large domestic properties, multi-family housing,
commercial installations -
Output Flexibility: Control strategies for cascade and
sequencing up to 16 boilers at a time, up to 2.2MW power -
Efficiency: Up to 96.5% seasonal efficiency, low emissions with
class 6 levels of NOx as low as 25mg/kWh @ 0% O2
Product Usage Instructions
Installation
1. Ensure proper space requirements are met for
installation.
2. Follow the provided installation guide for single or cascade
applications.
Maintenance
1. Access components from the front for easy maintenance.
2. Regularly check and clean the heat exchanger for optimal
performance.
Commissioning
1. Register the product for warranty and commissioning
purposes.
2. Use the touch-screen display for faster commissioning and
fault-finding.
Operation
1. Set the desired heat output using the modulation feature to
match the heat demand.
2. Monitor the boiler’s performance and efficiency
regularly.
FAQ
Q: What are the typical use cases for the Condens 7000 WP?
A: The boiler is suitable for large domestic properties,
multi-family housing, and commercial installations. It can also be
used in combination with high output heat pumps.
Q: What is the warranty period for the Condens 7000 WP?
A: The product comes with a 5-year guarantee for peace of
mind.
Q: Does the boiler have energy-saving features?
A: Yes, each boiler can automatically modulate its output to
precisely match the heat demand, reducing fuel consumption and
improving overall seasonal efficiency.
“`
Condens 7000 WP Technical and specification guide
Quick installation, easy maintenance
5
Installer guide
Contents
Product overview
4
Typical use cases
31
Features and benefits
5
Single boiler application
31
Technical data
6
Cascade application
33
Installing a cascade
7
Getting started
34
Product breakdown
8
Registration / commissioning
34
The inside story
8
Packs and part numbers
35
Specification considerations
12
Single boiler packs
35
Space requirements
12
Cascade boiler packs
36
Water system connections
16
Accessories
38
Controls
19
Flues and ventilation
24
Training Courses
Our commercial trainers have many year’s experience as technical heating
technicians and deliver first-class training across a wide range of products,
including the Bosch Condens 7000 WP.
To book onto one of our Bosch Condens 7000 WP training courses:
Email training@uk.bosch.com
Visit our eAcademy worcesterbosch-academy.co.uk
*Terms & conditions apply. Please visit bosch-industrial.co.uk/guarantee-terms-and-conditions for details.
Why install the Condens 7000 WP?
5
Guaranteed
5 years peace of mind for you and your customers*
Quick installation
Rapid installation thanks to our new frame kit design
Efficient
Automatic modulation to match heat demand
Easy maintenance
Components accessible from the front
Connected
Touch-screen display for faster commissioning and fault-finding
High output
Outputs from 50kW up to 145kW with the ability to cascade up to 860kW
Condens 7000 WP 3
Product overview
Available in outputs of 50kW, 65kW, 85kW, 100kW, 125kW and 145kW. The Condens 7000 WP can be cascaded in banks of up to 6 boilers per bank providing up to 858.6kW at 50/30 per bank.
Applications
Our Condens 7000 WP is a wall-hung boiler suitable for large domestic
properties, multi-family housing and commercial installations. It can also be
used in combination with high output heat pumps to create a flexible hybrid
solution.
Output flexibility and compact size
An ideal choice for applications where space is restricted but there is a
demand for a modern high output, high efficiency heating solution. Control
strategies can provide cascade and sequencing for up to 16 boilers at a time
for up to 2.2MW of power.
High efficiency, low emissions
Our Condens 7000 WP boosts seasonal efficiencies of up to 96.5% using the much loved ALU plus heat exchanger with class 6 levels of NOx as low as 25mg/kWh @ 0% 02.**
Hydrogen blend ready
Our entire gas boiler range is able to run on a 20% hydrogen blend so your
customer can be confident it will run on gas for it’s lifetime.
Precise energy management
Each boiler can automatically modulate its output to precisely match the heat
demand, reducing fuel consumption and improving overall seasonal efficiency.
With cascades, modulation is from the lowest output of the smallest boiler up to the total load of all the boilers. The 50-100kW products can modulate at a ratio of 1:5 and both the 125kW and 145kW boilers modulate at 1:6.
Time and cost saving
The boiler’s small footprint increases installation flexibility, speeds up
installation time and improves access for servicing and maintenance, reducing
the need to have larger boiler rooms to achieve higher system outputs.
Patented ALU-Plus heat exchanger
The maintenance-reducing heat exchanger is lightweight, robust and allows for
a rapid transfer of heat. Combined with its fully insulated case, the boiler
is especially quiet in the industry, with our 50kW model being Quiet Mark
certified.
*Quiet Mark certification applicable to the Condens 7000 WP 50kW single boiler. **Applicable to GC7000 WP 50kW model variant only. Please refer to technical data table on page 6.
4 Product overview
Features and benefits
Eye-level control for easier commissioning
Innovative control display simple, self-explanatory menu guidance with
colour display and touch buttons
C8 heat exchanger continuously optimised over the past 15 years
Front cover easy to remove with just one click
Electrical connection easily accessible from the top with reliefs for secure
cables, MM100 module can be installed
Exhaust gas connection 100/160 as standard, rotatable by 360o, flue gas
measuring points integrated
Everything is ready PWM cable connection for the pump group for easy
connection
Easy to assemble simple and safe handling thanks to ergonomic handle design
Additional features and benefits
Condensing technology with up to 108.7% net efficiency saves fuel compared
to a standard efficiency boiler
Modulation to just 20% of total output* year round efficiency according to
seasonal demand
Cascade frame kits can be combined with site made hydraulic arrangements
Low emission levels cleaner combustion and increased carbon savings
Expect to save up to 60% on the average installation time compared to GB162
V2**
Integrates with solar thermal installations maximise savings from solar hot
water
Individual lift weight only 74kg for 50100 models
Easy manoeuvrability with built-in handles
Flexible control options, including Control 8000, Sense II and BMS System
increased system functionality and reduced running costs
LPG conversion available suitable for off mains locations.
*Modulation range will vary depending on model and system operating temperatures. **Time savings estimated and observed during customer installation studies. Ensure safe lifting methods and sufficient people appropriate for the weight to be lifted.
Features and benefits 5
Technical data
Condens 7000 WP Nominal heat output @ 80/60 °C
Nominal heat output @ 50/30 °C
Rated heat input
Net efficiency (partial load 30% in accordance with EN15502)
Seasonal efficiency (as L2B)
ErP class and seasonal efficiency
Standby loss (in accordance with EN15502)
Maximum working pressure
Maximum flow temperature
Maximum flow rate @ T=20k
Required flow rate @ T=20k
Resistance @ required flow rate (boiler only)
Maximum condensate rate
Noise level @ 1m
Full load
Fuel type
Gas category according to EN 437
Gas pressure min/max
Gas rating natural gas (G20)
Gas rating LPG (G31)
CO2 content NG (G20)
Full load Part load
CO2 emission G20
Full load
NOx emission G20 @ full load (in accordance with EN15502)
Residual head of fan
Flue gas mass flow rate
Full load
Flue gas temperature @ 80/60 °C
Part load Full load
Flue gas temperature @ 50/30 °C
Part load Full load
Flue type
Mains connection voltage / phase
Power supply rating
Electrical ingress protection
Electrical power consumption (without pump group)
Standby Part load Full load
Unit kW kW kW % % % % bar °C l/h l/h mbar l/h dB(A)
mbar m³/h m³/h
% ppm mg/kWh Pa g/s
°C °C
V
tW
50 kW
65 kW
85 kW
100 kW
13.0 46.5 13.0 62.6 18.9 80.0 19.0 94.5
14.3 49.9 14.3 69.5 20.8 84.5 20.8 99.5
13.3 47.5 13.3 64.3 19.3 82.0 19.3 96.5
125 kW
24.1 116.9
26.2 124.4
24.5 118.1
145 kW
24.1 138.8
26.2 143.1
24.5 140.1
108.4
108.7
109.1
108.7
109.3
109.6
96
96.3
96.5
96.2
96.7
97
A / 93
N/A
0.24
0.18
0.14
0.12
0.12
0.15
2200
6 *
85
5000
3000
3600
4300
7000
5300
6300
75
130
170
240
312
430
6 55
5.03 1.94 9.3 8.4 31
7.6 61
6.8 2.62 9.3 8.4 63
9.3
11
13.5
61 **
64 **
65**
Natural gas H (G20) LPG (G31)
GB/IE II2H,3P 20;37mbar
Natural gas 17/25 LPG 25/45
8.68
10.21
12.63
3.34
3.93
4.86
9.1
9.1
8.8
8.2
8.1
8.3
70
81
76
16.0 69**
15.14 5.83 8.7 8.3 85
25
34
34
38
35
38
71 21.6 56 59 32 39
2 8 31
130
162
226
145
29.2
38
44.7
56.3
56
56
56
56
62
66
72
67
32
34
34
43
50
53
50
B23, B53, C13, C33, C43, C53, C63, C83, C93
230 / single phase
230 VAC, 50 Hz, 130 Watts
IPX0D
2
2
2
2
8
12
12
15
65
88
133
145
200 67.5 56 71 53
2 15 243
*Standard 3 bar safety valve for 50kW to 100kW pump group and 4 bar safety valve for 125kW & 145kW. 4 & 6 bar safety valves available as accessory. **Noise level for 85, 100, 125 & 145 kW are indicative values.
6 Technical data
Installing a cascade
Our brand new installation concept allows you to install the boiler in less
than half the time of its predecessor, the GB162 V2*. Building from the ground
up allows you to quickly and efficiently install the Condens 7000 WP.
To help familiarise yourself with the installation process, there are step-by-
step installation videos available as a guide on our website:
bosch-industrial.co.uk/condens7000
*Time savings estimated and observed during customer installation studies.
Installing a cascade 7
Product breakdown
The inside story
GC7000WP 50-100kW
GC7000WP 125-145kW
4 1
4 1
5
2
2
6 6
5
3
1 Basic controller BC30.2 for EMS plus 2 Ceramic burner with modulation
ratio up to 1:5 3 Mounting option on the base frame
for floor installation with “push and click-in” function for easy assembly 4
Simple connection of the control components from the top 5 All components
accessible from the front for ease of maintenance and service 6 Patented ALU-
Plus heat exchanger
8 The inside story
3
1 Basic controller BC30.2 for EMS plus 2 PFK grade burner with modulation
ratio up to 1:6 3 Mounting option on the base frame
for floor installation with “push and click-in” function for easy assembly 4
Simple connection of the control components from the top 5 All components
accessible from the front for ease of maintenance and service 6 Patented ALU-
Plus heat exchanger
Hydraulics, gas, pump connections and handles
Front gas connection for easy access Easy electric connection box at
bottom for pump group connections Comfortable bottom handles
for confident handling “Slide and guide” self-guiding
transport slides Hydraulic CH connection
Modulating pump groups
Pump connection group for 50 and 65kW
Pump connection group for 85-145kW
5 1
9
5
9
1
4 2
4 2
3
8
7 3
8
7
6
6
1 Pressure Relief Valve (PRV)
2 Manometer
3 Service valve supply 4 Gas cock 5 Y-piece connector
Pump connection group for 50 and 65kW with WILO-Para STG 25/8
Supplied with 3 bar PRV as standard
6 Service valve return 7 Drain valve
8 Expansion vessel connection
9 Pump
Pump connection group for 85 and 100kW with Wilo-Para Maxo 8
85 and 100kW pump group supplied with 3 bar PRV as standard
Pump connection group for 125 and 145kW with WILO-Stratos PARA C-12
125 and 145kW pump group supplied with 4 bar PRV as standard
Upgrade your PRV
Product code Pressure relief valve 4 bar (50-145kW) Pressure relief valve 6 bar (50-145kW)
Part number 7-095-595 7-736-700-914
The inside story 9
Heat exchanger
Patented ALU-Plus heat exchanger
The precision engineered heat exchanger is constructed from a cast aluminium
silicate compound which is lightweight, robust and allows for a rapid transfer
of heat.
The heat exchanger uses the latest ALU-Plus technology that has been developed
by us, to increase durability and optimise efficiency. Fins on the outside of
the aluminium tubes increase the exterior surface area so that more hot flue
gas c omes into contact with the heat exchanger.
A spiral channel on the inside of the tube increases the internal surface
area, bringing more water in contact with the heating surface and ensuring an
optimum heat transfer. The wide channels on the heat exchanger ensure that the
flow resistance is minimised and this, combined with its fully insulated case,
makes the Condens 7000 WP incredibly quiet in operation.
Plasm-polymerised heat exchanger
The surfaces of the heat exchanger’s tubes are treated using a patented
plasma-polymerisation process which leaves the surfaces so smooth that the
heat exchanger effectively stays clean as no deposits can adhere to them.
Its extremely high efficiency is maintained and there is no need for
mechanical cleaning; the heat exchanger can be simply flushed through during
servicing.
Heat Cell 50-100kW
Heat Cell 125-145KW (C8)
7 10
3 5 6
8 19 2
4
10 7 2
1 11
8
3 4
5 6
9
1 Flue exhaust 110mm
2 Fan
3 Spark igniter, ionization sensor
4 Side wall mounting in boiler casing
5 Supply temperature limiter switch
6 Condensate tray 7 Secured gas way
EPDM tube 8 Gas valve 9 Air suction pipe 10 Auto air vent
1 Flue exhaust 110mm
2 Fan
3 Spark igniter, ionization sensor
4 Back wall mounting in boiler casing
5 Supply temperature limiter switch
6 Condensate tray with inspection opening
7 Secured gas way EPDM tube
8 Gas valve
9 Air suction pipe
10 Auto air vent
11 Integrated flue non-return valve
10 The inside story
Wiring and connections
The control design ensures you have top access to do your input and output connections. The unit has integrated cable routing to keep the wiring neat. One EMS plus module (such as the MU100 for 0-10v connection to a BMS system) can be integrated into the boiler.
Low voltage connections
High voltage connections
1 2
Control unit
1 Flue connection DN110/160
with integrated air supply grille HMI
2 Slot-in option for EMS plus module
Control display
Full colour display (38.5mm x 50.7mm) with touch buttons
1 2
3 4
8
7 5
6
1 Burner indicator 2 Heating button 3 Hot water button 4 Menu button 5 Button
OK
Chimney sweep mode
6 Return button
7 Heating water pressure indicator
8 Buttons and
The inside story 11
Specification considerations
These pages provide an overview of the main installation and system
requirements for the Condens 7000 WP. The full installation instructions
supplied with the boiler must be adhered to before any work on the heating
system takes place.
Space requirements
The Condens 7000 WP can be wall-mounted or as part of a cascade frame. When considering the final mounting position, it is important the required service and maintenance clearances are taken into account.
Minimum space required for the boiler:
Provide an unobstructed space of at least 100cm in front of the boiler to
allow maintenance to be carried out.
Distance from walls at sides:
Maintain a clearance of at least 5mm on either side of the boiler.
See page 9 of installation manual for full clearances.
CAD and BIM
Files are available for download in DWG and RFA format from the website here:
https://www.bosch-industrial.com/bim
50-100kW boiler
GC7000WP boiler on frame
GC7000WP boiler on wall
125 and 145kW boiler
GC7000WP boiler on frame
GC7000WP boiler on wall
12 Space requirements
Space requirements 13
In-line (TL) arrangement
GC7000WP TL front
GC7000WP TL 50-100kW
GC7000WP 125 and 145kW
Back-to-back arrangement
GC7000WP TL front
GC7000WP TL 50-100kW
GC7000WP 125 and 145kW
Orientation TL1 TL2 TL3 TL4 TL5 TL6
X1 + Y1 (mm) 520 + 50 = 570 1045 + 50 = 1095 1570 + 50 = 1620 2095 + 50 = 2145 2620 + 50 = 2670 3145 + 50 = 3195
Orientation TL1 TL2 TL3 TL4 TL5 TL6
X1 mm (boiler) 520 1045 1570 2095 2620 3145
Y1 mm (spigot) 50 50 50 50 50 50
L1 mm (LLH length) 492.8 492.8 796.5 796.5 796.5 796.5
Overall (mm) 1062.8 1587.8 2416.5 2941.5 3466.5 3991.5
14 Space requirements
Orientation TR2 TR3 & TR4 TR5 & TR6
X1 + Y1 (mm) 520 + 50 = 570 1045 + 50 = 1095 1570 + 50 = 1620
Orientation TR2 TR3 & TR4 TR5 & TR6
X1 mm (boiler) 520 1045 1570
Y1 mm (spigot) 50 50 50
L1 mm (LLH length) 492.8 492.8 796.5
Overall (mm) 1062.8 1587.8 2416.5
Space requirements 15
Water system connections
When to use a low loss header or plate heat exchanger The Condens 7000 WP must
be installed on a sealed system in accordance with BS EN 12828.
For open vented systems or systems that are particularly contaminated, a plate
heat exchanger should be used to separate the boiler circuit from the main
system. Matched plate heat exchanger packs for the boiler or cascade output
capacity are available to make selection simpler (see control section for
guidance on positioning of flow temperature sensor).
For clean sealed systems where multiple heating circuits or DHW circuits
controlled by separate pumps are used, it is necessary to incorporate a low
loss header. Cascade kits with the appropriately sized low loss header
included are available as a pack (please refer to page 35 for part numbers).
The low loss header acts to hydraulically separate the boiler pump groups from
the heating circuit pumps and avoids hydraulic issues that could affect the
correct control of the heating system. Always use a low loss header (or plate
heat exchanger) where there is more than one pump in the system.
Residual pump head For single boiler applications, the matched boiler pump
group has been selected to cope with typical radiator heating systems that are
constructed in accordance with UK building regulations requirement of
separating zones above 150m2. Under these circumstances the residual head
available from the boiler pump should be sufficient to cope with most typical
radiator heating circuit resistance.
For older heating circuits that do not comply with modern building
regulations, or for applications with high system resistance, a low loss
header should be used.
50 and 65kW residual pump head
Head (mbar)
900 800 700 600 500 400 300 200 100
0 0
500
1000
Heat cell resistance Residual head @ 100% pump
1500
2000
Flow rate (l/h)
Heat cell + connection Residual head @ 65% pump
2500
3000
3500
Heat cell + connection + check valve
85 and 100kW residual pump head
Head (mbar)
900 800 700 600 500 400 300 200 100
0 0
500
1000
1500
Heat cell resistance Residual head @ 100% pump
2000
2500
3000
Flow rate (l/h)
Heat cell + connection Residual head @ 65% pump
3500
4000
4500
5000
Heat cell + connection + check valve
125 and 145kW residual pump head
Head (mbar)
1400 1200 1000
800 600 400 200
0 0
1000
2000
Heat cell + connections Residual head @ 80% pump
3000
4000
Flow rate (l/h)
Heat cell + connection + check valve
5000
6000
7000
Heat cell resistance Residual head @ 100% pump
16 Water system connections
Water system connections 17
Maximum temperature difference
Heating systems designed for use with condensing boilers such as our Condens
7000 WP are at their most efficient when the return temperature is below 55
degrees. To help achieve these conditions, industry guidance recommends
rebalancing older heating systems designed to operate at 82/71 to 80/60 (T
20K). When this is combined with weather compensated heating circuit
operation, the return temperature will regularly be below 55 degrees on all
but the coldest days.
However, the maximum temperature difference should be kept below T 25K. Above
this temperature difference the boiler will modulate its output to ensure it
continues to operate safely.
Water quality
We strongly recommend thoroughly flushing the system before filling it and
using only untreated tap water when filling the system. The use of dirty water
will lead to build-ups of sediment and corrosion, which can result in the
boiler malfunctioning and cause damage to the heat exchanger.
Do not treat the water with pH-adjusting substances (chemical additives) or
anti-freeze (other than Fernox Alphi 11) or water softeners. Sentinel X100 or
Fernox MB1 can be used to achieve the desired water quality. The concentration
of Sentinel or Fernox should be in accordance with the manufacturer’s
instructions for the volume of the water in the system.
Water treatment following the requirements of VDI 2035 may be used.
The pH of the heating system must be between 7 and 8.5. If this is not the
case, please contact our technical support team before proceeding, tel. 0330
123 9229.
Artificially softened water must not be used with the Condens 7000 WP.
Quality of the pipe work
When using plastic pipe work in the heating system, e.g. for underfloor
heating, it has to be oxygentight according to the relevant UK standards. If
plastic pipes do not comply with these standards, the system parts must be
separated using a plate heat exchanger.
Filling the system (water regulations)
In the UK, methods for filling heating systems are covered by the water
regulations. The regulations ensure that backflow of contaminated heating
system water does not enter the water supply. It is important to understand
these requirements and how they relate to the type of building (house or non-
house) as well as the boiler output size.
For most non-domestic applications there will be a need to comply with fluid
categories 4 and 5, meaning that a simple filler loop cannot meet the
requirements.
Gas supply requirements
Low gas pressure will lead to reduced boiler outputs, so it is important to
ensure the gas installation can provide the necessary supply capacity and
pressures.
For natural gas, the inlet supply pressure should be within 17mbar to 25mbar
(see installation manual for guidance when measuring gas pressures as the
appliance gas multi-function valve).
Before installation commences, the capacity of the gas meter supply should be
checked to be sufficient for all of the gas appliances connected to the
installation.
For the 50 and 65kW boilers in domestic properties where installers carrying
out the installation hold domestic ACS qualifications only, the installation
of the gas supply must comply with IGE/UP/1b. This means that the gas meter
must be no greater than 16m3/h, the pipework no more than 35mm and the
installation volume does not exceed 0.035m3.
LPG conversion
LPG conversion kits are available for all of the outputs. For LPG
installations, the gas supply pressure should be between 25mbar and 45mbar
with adequate protection for over and under pressure.
Ensure the siting of the appliance is not below ground level and that low
level ventilation meets the requirements of the appropriate standard.
Available conversion sets
Product Conversion set 3P (G31) (45-50KW) Conversion set 3P (G31) (60-70KW) Conversion set 3P (G31) (80-85KW) Conversion set 3P (G31) (90-100KW) Conversion set 3P (G31) (125KW) Conversion set 3P (G31) (145-150KW)
Part number 7-736-702-378 7-736-702-379 7-736-702-380 7-736-702-381 7-736-701-860 7-736-701-861
18 Water system connections
Which control is right for my install?
There are a range of control options for differing applications when using the
Condens 7000 WP either as a single boiler or as a cascade. Please use our
handy guide below to find the one best suited for your install.
YES
Single boiler installation?
NO (cascade)
Internet connection needed?
BMS led?
YES
NO
YES
NO
Go to A on page 20
Go to B on page 20
BMS controlling sequencing?
YES
HYBRID
Internet connection
needed?
YES
NO
Go to D on page 21
Go to E
Go to E
on page 22 on page 22
NO
Go to F on page 23
Go to C on page 21
Controls 19
A Single boiler installation internet-connected controls
Bosch EasyControl controller 7-736-701-341 (white) 7-736-701-392 (black)
The Bosch EasyControl is a smart internetconnected room thermostat, offering a
simple, stylish and intuitive solution to optimise home comfort.
When combined with our Smart TRVs, homeowners can easily control the heating
in each individual room, to achieve the perfect heating environment (feature
only available for 50-100kW models).
The device can be connected to the boiler using a 2-core cable.
3 way valve 7-736-701-881
3 way valve allows for priority DHW generation, must be used in conjunction
with a Sense II or EasyControl.
Plugs into the boiler’s harness plug 1 1/4″ connections.
You must ensure that the cylinder coil is rated to at least 50% of the
boiler’s output. If demand is lower than 50%, refer to control option B,
below.
B Single boiler installation standard controls
If an internet connection is not required for your install, the Sense II
controller in combination with expansion modules MM100 can be used. Where the
system also includes solar thermal, either the MS100 or MS200 can be used.
Where there are multiple heating circuits, a Sense I can be used to give
individual zone control.
Sense II 7-738-111-064 The Sense II control platform uses the EMS 2 Energy
Management System which allows advanced functions such as weather compensated
control and optimum start.
Weather compensation is particularly useful for larger buildings where it can
be difficult to locate a good reference room to suit the area being heated. A
north facing outside sensor is used to determine the correct flow temperature
needed to achieve the desired room temperature, based on a heating curve.
Local TRV’s on radiators, for example, can then fine tune the final room
temperature to suit the occupants.
Using weather compensation allows lower flow temperatures for large parts of
the heating season, which in turn leads to lower return temperatures to help
make the condensing boiler more efficient.
MM100 7-738-110-140 Used for additional heating circuit (maximum of 4) or additional DHW circuit (maximum of 1).
MS100 7-738-110-144
Module for integration of solar thermal panels.
20 Controls
The benefits of weather compensation
The Sense II controller can change the required temperature for different
heating circuits according to the outside temperature and is measured using a
small external sensor.
With mixed heating circuits this means that each individual circuit has its
own characteristics and the boiler will supply only the heat needed for
certain parts of the system. This is particularly effective in Spring and
Autumn so temperatures for the heating circuits can be reduced significantly
saving fuel and allowing the highest efficiency from the condensing process.
Flow Temp oC 45 62 75
Outside Temp oC 10 0 -10
Flow temperature oC
90
80
70
60
50
40
30
20 +15 +10 +5 0
-5 -10 -15 -20
Outside temperature oC
The graph above shows how the heating curve can be modified at any time using the Sense II controller, providing maximum comfort for the user.
C Cascade installation BMS Led (Bosch controlling sequencing)
MC400 cascade sequencer 7-738-111-001 The MC400 simplifies the optimum running
of a cascade system when interfacing with an existing BMS.
By rotating the lead boiler it eliminates excessive wear in any one unit and
also interprets the 0-10V input signal from the BMS to modulate the heat
output of the cascade. This is all achieved without the need for programming
or complex set up and is a true “plug and play” control.
An individual MC400 can control up to 4 boilers and up to 16 boilers can be
achieved when five MC400 units are linked together, up to 2.2MW.
Wet sensor (part number 7-735-600-657) must be used in conjunction with the
MC400 cascade sequencer.
D Cascade installation BMS Led (BMS controlling sequencing)
MU100 BMS interface module 7-738-110-145 The MU100 is used for each individual
boiler and modules when interfacing with an existing BMS.
It can create a 230V fault signal, and has a 0-10V contact for signals from
the BMS to control the boiler flow temperature.
Controls 21
E Cascade installation internet-connected controls
BFU room thermostat 5-720-720 The BFU is a remote control which allows the
temperature to be adjusted from the end user’s living or working space. This
includes a room temperature sensor.
Bosch CC8313 intelligent commercial control 7-736-602-245 The CC8313 is an
intelligent commercial control offering internet-connected remote access and
weather compensation as standard.
The control unit has the ability to work alongside or independent of a BMS
system. With the addition of plug-in function modules, the CC8313 can be
expanded to cascade boilers, add multiple heating circuits and provide control
of two separate DHW circuits.
The CC8313 can control a DHW circuit as standard, additional function modules
will be required for mixed or unmixed heating circuits. The CC8313 has the
space available for up to four additional function modules.
Wet sensor (part number 7-735-600-656) must be used in conjunction with this
control (please refer to page 21 for more details).
165mm
F Cascade installation standard controls
Gives cascade control for use with existing heating and hot water time and
temperature controllers.
MC400 cascade controller 7-738-111-001 For heating systems where an existing
control system will be reused and is not capable of sequencing and rotating a
cascade, the MC400 is the perfect solution. The MC400 can control up to four
boilers as a single control unit, but can be connected to other MC400
controllers to control up to 16 boilers (requires five MC400s). The controller
will sequence the boilers to match the demand and rotate the lead boiler to
ensure even use across the cascade.
MC400 has several different configuration options that allow 0-10VDC or 230V
enable signals from an existing external controller. A 230V alarm signal is
also available to indicate a fault situation.
A flow sensor (part number 7-735-600-657) is required for the low loss header
or plate heat exchanger.
FM-MW heating and DHW control module 8-718-598-831
This controls one mixed or one unmixed heating circuit and one DHW circuit
(with cylinder load and circulation pump).
All wiring has colour coded plugs for quick installation into the main control
unit (BFU as accessory).
FM-MM heating circuit control module 8-718-598-828
This controls up to two mixed or unmixed circuits. Comes supplied with one
FV/FZ temperature sensor.
All wiring has colour coded plugs for a quick installation into the main
control unit (BFU up to 2x as accessory). An additional FV/FZ sensor is
required if using two mixed circuits.
FM-CM cascade control module 7-736-602-098
The FM-CM can control the modulation and sequencing strategy from 2 to 4
boilers. A 0-10V input, for use with the BMS control.
22 Controls
Available controls, modules and sensors
Product Programmer MU100 MM100 mixer and LLH module MC400 cascade sequencer MS200 intelligent solar module Greenstar Sense II Greenstar Sense I CC8313 intelligent commercial control Control CC8310 (module extension) Module FM-CM
Part number 7-738-110-145 7-738-110-140 7-738-111-001 7-738-110-146 7-738-111-064 7-738-110-054 7-736-602-245 7-736-605-958 7-736-602-098
Product Module FM-MW Module FM-MM Module FM-AM FV/FZ temperature sensor set VPN router ERT50 Module FM-RM (VPN router mounting rail) Flow sensor (8313 controller) Flow sensor (MC400 controller)
Part number 8-718-598-831 8-718-598-828 7-736-602-079 5-991-376 7-736-603-505 8-732-900-362 7-735-600-656 7-735-600-657
Controls 23
Flues and ventilation
The topic of fluing and ventilation for commercial boilers is a detailed one that crosses several industry standards and regulations.
To help guide installers and system designers, we have produced a dedicated
flue and ventilation guide for commercial installations, which is available to
download from our website.
Additionally, a separate flue manual is available for the Condens 7000 WP
boiler range, also downloadable from our website.
Concentric flue options Standard flue options are available for individual
boilers using room sealed (RS) concentric flue systems. The Condens 7000 WP
has an extensive range of concentric flue components available for horizontal,
vertical and plume management terminations.
C13 and C33 concentric flue lengths and reductions The following equivalent
flue lengths and reduction for bends are applicable to the Condens 7000 WP
boiler range.
7000 WP boiler series
horizontal room sealed fluing options
Horizontal room sealed flue
Maximum equivalent 110/160 mm flue lengths
7000 WP 50kW
11m
90° Bend 1.5m
7000 WP 65kW
16m
1.5m
7000 WP 85 kW
11m
1.5m
7000 WP 100 kW
12m
1.5m
7000 WP 125 kW
3m
1.5m
7000 WP 145 kW
3m
1.5m
45° Bend 0.5m 0.5m 0.5m 0.5m 0.5m 0.5m
24 Flues and ventilation
110/160mm horizontal room sealed flue accessories
Components
Part number 7-738-113-669
Description
110/160mm dia. horizontal flue kit
7-738-113-100 7-738-113-099 7-738-113-101 7-738-113-105 7-738-113-104 7-738-113-103 7-738-113-102 7-738-113-677
110/160mm dia. 1m flue extension
110/160mm dia. 0.5m flue extension
110/160mm dia. 2m flue extension
110/160mm dia. 87º bend
110/160mm dia. 45º bend
110/160mm dia. 30° bend
110/160mm dia. 15° bend
Flue wall clamps 160mm dia. (pack qty. 3)
110/160mm horizontal flue kit
1 x wall finishing plate (white)
1 x external flue terminal (stainless)
1 x external wall finishing plate (stainless)
1 x 87º bend
1 x horizontal flue (500mm length)
Part No. 7-738-113-669
Standard horizontal flue assembly
Extension flue horizontal
Components
Part No. 110/160mm
7-738-113 669
Maximum lengths (mm) & no. of components required
7000 WP 50kW
1115mm
1
7000 WP 65kW
1115mm
1
7000 WP 85kW
1115mm
1
7000 WP 100kW
1115mm
1
7000 WP 125kW
1115mm
1
7000 WP 145kW
1115mm
1
Extension flue horizontal using a second 90º bend
Components
Part No. 110/160mm 7-738-113-669 7-738-113-100
Maximum lengths (mm) & no. of components required
7000 WP 50kW
11,000mm
1
up to 10
7000 WP 65kW
16,000mm
1
up to 15
7000 WP 85kW
11,000mm
1
up to 10
7000 WP 100kW
12,000mm
1
up to 11
7000 WP 125kW
3,000mm
1
up to 2
7000 WP 145kW
3,000mm
1
up to 2
Note: The maximum flue length must be reduced by the following amounts for each bend used.
7000 WP 50, 65, 85, 100, 125, 145kW 110/160mm flue
45° bend
87° bend
0.5m 1.5m
Components
Part No. 110/160mm
7-738-113-669 7-738-113-100 7-738-113-105
Maximum lengths (mm) & no. of components required
7000 WP 50kW 9.500mm
1
up to 8
1
7000 WP 65kW 14,500mm
1
up to 13
1
7000 WP 85kW
9,500mm
1
up to 8
1
7000 WP 100kW
10,500mm
1
up to 9
1
7000 WP 125kW
1,500mm
1
N/A
1
7000 WP 145kW
1,500mm
1
N/A
1
Flues and ventilation 25
Extension flue horizontal and upwards
Extension flue upwards and horizontal using a second 90º bend
Components
Part No. 110/160mm
7-738-113-669 7-738-113-100 7-738-113-105
Maximum lengths (mm) & no. of components required
7000 WP 50kW 11,000mm
1
up to 10
0*
7000 WP 65kW 16,000mm
1
up to 15
0*
7000 WP 85kW 11,000mm
1
up to 10
0*
7000 WP 100kW 12,000mm
1
up to 11
0*
7000 WP 125kW 3,000mm
1
up to 2
0*
7000 WP 145kW 3,000mm
1
up to 2
0*
*Horizontal flue kit includes a 90° bend.
Components
Part No. 110/160mm
7-738-113-669 7-738-113-100 7-738-113-105
Maximum lengths (mm) & no. of components required
7000 WP 50kW 9,500mm
1
up to 8
1*
7000 WP 65kW 14,500mm
1
up to 13
1*
7000 WP 85kW 9,500mm
1
up to 8
1*
7000 WP 100kW
10,500mm
1
up to 9
1*
7000 WP 125kW
1,500mm
1
N/A
1*
7000 WP 145kW
1,500mm
1
N/A
1*
*Horizontal flue kit includes a 90º bend, therefore only 1 additional bend needs to be ordered.
Notes: The short 0.5m flue extension may be used
as an alternative to the standard extension.
The maximum flue length must be reduced by the following amounts for each bend
used.
7000 WP 50, 65, 85, 100, 125, 145kW 110/160mm flue
45° bend
87° bend
0.5m 1.5m
26 Flues and ventilation
7000 WP boiler series vertical room sealed fluing options
Vertical room sealed flue
Maximum equivalent flue lengths
7000 WP 50kW
110/160 mm 21m
90° Bend 1.5m
7000 WP 65kW
22m
1.5m
7000 WP 85kW
16m
1.5m
7000 WP 100kW
16m
1.5m
7000 WP 125kW
5m
1.5m
7000 WP 145kW
5m
1.5m
45° Bend 0.5m 0.5m 0.5m 0.5m 0.5m 0.5m
110/160mm vertical flue kit
1 x flue terminal 1 x support bracket 1 x inner duct 1 x outer duct
Part No. 7-738-113-668
110/160mm vertical room sealed flue accessories
Components
Part number 7-738-113-668
Description
110/160mm dia. vertical flue kit
7-738-113-100 7-738-113-099 7-738-113-101 7-738-113-105 7-738-113-104
7-738-113-103 7-738-113-102 7-738-113-677 7-738-113-126
7-738-113-127
7-738-113-128 7-738-113-129
110/160mm dia. 1m flue extension
110/160mm dia. 0.5m flue extension
110/160mm dia. 2m flue extension
110/160mm dia. 87º bend
110/160mm dia. 45º bend
110/160mm dia. 30° bend
110/160mm dia. 15° bend
Flue wall clamps 160mm dia. (pack qty. 3)
110/160mm dia. Flat roof flashing 0° 170mm
110/160mm dia. Flat roof flashing 0° – 15° 170mm
110/160mm dia. 5 – 25° pitched roof flashing
110/160mm dia. 25 – 45° flashing
Notes: The short 0.5m flue extension may be used
as an alternative to the standard extension.
The maximum flue length must be reduced by the following amounts for each bend
used.
7000 WP 50, 65, 85, 100, 125, 145kW 110/160mm flue
45° bend
87° bend
0.5m 1.5m
Flues and ventilation 27
Standard vertical flue assembly
Vertical balanced flue system with two 45° bends
Components
Part No. 110/160mm 7-738-113-668
Maximum lengths (mm) & no. of components required
7000 WP 50kW
2,000mm
1
7000 WP 65kW
2,000mm
1
7000 WP 85kW
2,000mm
1
7000 WP 100kW
2,000mm
1
7000 WP 125kW
2,000mm
1
7000 WP 145kW
2,000mm
1
Vertical balanced flue system maximum height
Components
Part No. 110/160mm 7-738-113-668 7-738-113-100 7-738-113-104
Maximum lengths (mm) & no. of components required
7000 WP 50kW 20,000mm
1
up to 18
2
7000 WP 65kW
21,000mm
1
up to 19
2
7000 WP 85kW
15,000mm
1
up to 13
2
7000 WP 100kW
15,000mm
1
up to 13
2
7000 WP 125kW
5,000mm
1
up to 2
2
7000 WP 145kW
4,000mm
1
up to 2
2
Vertical balanced flue system with two 90° bends
Plume management flue kit For single boilers, sometimes finding a suitable
compliant flue termination position can be difficult. Plume management kits
allow termination positions to be raised up to a level where plume is less
likely to cause a nuisance, allowing more options for a compliant flue
termination position. The plume management kit replaces a standard horizontal
terminal and allows a concentric flue system to be used internally, where the
boiler is positioned some distance from the outside wall.
All external components are made from stainless steel to ensure a durable long
life flue system. Stainless steel bends and additional sections allow further
options depending on the site conditions.
For further information about permissible flue lengths, please refer to the
flue installation manual for the 7000 WP.
Available accessories
Product Plume management kit, Ø110/160 Pipe concentric Ø110/160 0,5m stainless Pipe concentric Ø110/160 1,0m stainless Pipe concentric Ø110/160 2,0m stainless Elbow concentric Ø110/160 15° stainless Elbow concentric Ø110/160 30° stainless Elbow concentric Ø110/160 45° stainless Elbow concentric Ø110/160 87° stainless
Part number 7-738-113-670 7-738-113-140 7-738-113-141 7-738-113-142 7-738-113-143 7-738-113-144 7-738-113-145 7-738-113-146
Product Supply air intake Ø110/160 stainless Wall bracket Ø160, 40-65mm stainless Extension wall bracket Ø160, 65-165mm Extension wall bracket Ø160, 178-284mm Extension wall bracket Ø160, 294-394mm Extension console Ø160, 54-187mm Extension console Ø160, 180-271mm Extension console Ø160, 271-362mm
Part number 7-738-113-147 7-738-113-149 7-738-113-150 7-738-113-151 7-738-113-152 7-738-113-153 7-738-113-154 7-738-113-155
Components
Part No. 110/160mm 7-738-113-668 7-738-113-100
Maximum lengths (mm) & no. of components required
7000 WP 50kW
21,000mm
1
up to 19
7000 WP 65kW
22,000mm
1
up to 20
7000 WP 85kW 16,000mm
1
up to 14
7000 WP 100kW 16,000mm
1
up to 14
7000 WP 125kW
5,000mm
1
up to 3
7000 WP 145kW
5,000mm
1
up to 3
28 Flues and ventilation
Components
Part No. 110/160mm 7-738-113-668 7-738-113-100 7-738-113-105
Maximum lengths (mm) & no. of components required
7000 WP 50kW
18,000mm
1
up to 16
2
7000 WP 65kW
19,000mm
1
up to 17
2
7000 WP 85kW
13,000mm
1
up to 11
2
7000 WP 100kW
13,000m
1
up to 11
2
7000 WP 125kW
2,000mm
1
N/A
2
7000 WP 145kW
2,000mm
1
N/A
2
Please refer to the installation manual and flue guidance document for further information.
B23 open flues For situations when a suitable room sealed flue run cannot be found, open flue systems using existing chimneys or purpose made flue systems can be used. The Condens 7000 WP has a range of flue components for use with B23 open flue systems.
Flue via an existing chimney For individual boilers, DN110 flue system components are available to line existing chimneys and connect the boiler to the lining. Rigid sections, available in 500mm, 1,000mm and 2,000mm, can be used with flue spacers, terminal, and base sections to build a complete flue system. For chimneys that are not straight, DN110 flexible liners are available in 15m and 25m lengths. Installation tools are also available.
C93 room sealed flues Where a room sealed flue arrangement is desired, but it is not possible to use a standard concentric flue to achieve this, the C93 flue option using an existing chimney is possible. The chimney must be inspected and found to be sound, clean and of minimum size before this option can be considered. C93 flue systems use the chimney as a supply duct for combustion air via a special terminal and base section. The inner exhaust duct uses standard flue components similar to those described in the B23 flue for both rigid and flexible options.
Flues and ventilation 29
Cascade combined flue systems One of the advantages of a Condens 7000 WP cascade is the ability to combine individual boiler flues into a common flue header using off-the-shelf recommended flue components. There are two types of cascade flue systems, which should be considered at the design stage.
Natural draught cascade flues Cascade flue systems that rely on natural
draught are durable due to their simplicity. They require a minimum vertical
height and diameter based on the cascade output and can use existing chimneys,
operating as an open flue system.
Where no chimney is available, flues can be run externally using standard twin
wall stainless steel components. Internal flue runs must consider any fire
protected areas they may pass through and local Building Regulations.
Standard cascade flue headers are available to suit all common cascade
arrangements.
Over pressure cascade flues Where the use of a natural draught flue system is
difficult to achieve, due to chimney size and height restrictions, an over
pressure flue system can be used. This provides greater flexibility to achieve
compliant flue options in demanding situations.
Over pressure flue systems use an individual nonreturn valve at each boiler
flue exit to ensure there are no possibilities of flue spillage when a boiler
is not operating. The Condens 7000 WP incorporates a flue safety sensor which
monitors the non-return valve is fully shut. If the non-return valve does not
shut completely, the flue sensor activates the boiler fan and creates an alarm
to maintain safety.
The over pressure non-return valve comes as standard with our Condens 7000 WP
125kW and 145kW range.
30 Flues and ventilation
Non Return Valve 7-736-701-917 Non return valve for overpressure flue cascade
kit 50-100kW (not required for 125 &145kW)
Boiler room safety
CO sensors for cascade flue systems Bosch has taken the decision to require
the mandatory use of CO detection for boiler systems using cascade flue
systems, such as the 7000 WP, where there is more than one appliance
connected. This is to reflect state of the art in the industry and will help
to raise safety standards.
The base cascade flue kits now contain a CO detector for use in the
installation. For third party cascade flue system, a CO detector that is
interlocked with the boilers will be required. A suitable CO detector is
available as an accessory.
Part Numbers: CO Detector – 7-736-606-211 CO-Detector & Cut-off module set –
7-736-606-214
Typical use cases
The Condens 7000 WP has been developed to allow specifiers and heating
engineers greater flexibility to design heating systems, providing reliable
and efficient performance for any project.
The following hydraulic schematics show just some of the many options that are
available for individual and cascade installations.
Single boiler application
Single boiler applications are most commonly found in large domestic or light
commercial applications such as restaurants, churches and more.
Single boiler (heating + hot water)
AV P
Example shows: Single boiler is installed without a low loss header. If residual head is less than 200 mbar, on most instances you would not need an additional low loss header and system pumps. An RTH converter can be used to enable use of third party controls.
Single Boiler with plate heat exchanger (heating + hot water)
AV P
LS IV
NRV IV
Example shows: Single boiler is installed in an open vented system. The boiler can only operate in a sealed system. Where header tanks are used, you must install a plate heat exchanger (PHE). Alternatively a PHE is often used when system water is contaminated helping to protect the boiler.
Single boiler application 31
Single Boiler (heating only)
P
Example shows: Single boiler is used for heating only applications. For single circuit applications that require less than 200mbr, you can achieve this without the need for an additional low loss header or system pumps.
Single boiler with diverter valve (heating + hot water)
AV
MON_GE
P
Sense II
Example shows: Single boiler is installed in a sealed system. The boiler pump group has the 3 way valve (7-736-701881) fitted to enable the hot water to be diverted to either the central heating or domestic hot water tank. This example represents a system with 1 heating circuit and 1 DHW circuit. For further information on the controls shown go to page 20.
Single boiler with LLH (heating + hot water)
Sense II
2 x MM100
AV
Example shows: Single boiler is installed with a low loss header. Hydraulic break is required when adding additional system pumps to avoid running pumps in parallel. This example represents a system with 1 heating circuit and 1 DHW circuit. For further information on the controls shown go to page 20.
NRV IV
P
IV
IV
NRV IV
32 Single boiler application
Cascade application
It is important that a cascade controller is always used when cascading our
7000 WP boilers. The following examples show how this is achieved using either
the MC400 or 8313 controllers.
Cascade with LLH (heating + hot water) using MC400 cascade sequencer (BMS run
signal)
Example shows: Cascade system is installed with a low loss header providing
hydraulic separation from the rest of the heating system. This will ensure
that flow volumes are balanced and hydraulic performance is optimised. Cascade
control sequencing is achieved through the MC400 module rotating the lead
boiler for consistency and switching boilers on to meet varying demand. The
MC400 can be used with a BMS system where the MC400 controls the sequencing
strategy.
MC400
AV
NRV IV
IV
MON_GE
P
MON_GE
P
IV
NRV IV
Cascade with LLH (heating + hot water) using CC8313 controller
Example shows: Cascade system is installed with a low loss header providing
hydraulic separation from the rest of the heating system. This will ensure
that flow volumes are balanced and hydraulic performance is optimised. Cascade
control and remote monitoring is achieved via the CC8313 control with function
modules. The CC8313 enables internet connection, remote monitoring and
diagnostics complying with Part L building regulations.
8313 FM-CM + FM-MM
AV
NRV IV
IV
MON_GE
P
MON_GE
P
IV
NRV IV
IV
Cascade boiler application 33
Getting started
REGISTER A PRODUCT
To register a boiler or cascade system and activate the 5 year guarantee,
click the link below, or scan the QR code: bosch-industrial.co.uk/guarantee
5
YEAR Boiler Guarantee*
BOOK COMMISSIONING
In order to book commissioning for a boiler or cascade system, simply visit
the below link, or scan the QR code, and complete the pre-commissioning
checklist:
bosch-industrial.co.uk/commissioning
*Terms & conditions apply. Please visit bosch-industrial.co.uk/guarantee-terms-and-conditions for details
34 Registration and commissioning
Boiler configurations Single boiler
The Condens 7000 WP can be configured in various ways to meet the heating
demands of your installation. Please use the numbered steps below to choose
the correct boiler configuration for your project. Please contact us if you
require assistance.
Dimensions 50-100kW
Width
520mm
Height
1,429mm
Depth
458mm
Dimensions 125-145kW
Width
520mm
Height
1,429mm
Depth
588mm
ErP only relevant to 50kW and 65kW models. Height with pump group
1 Boiler
Description Bosch Condens GC7000WP 50kW Bosch Condens GC7000WP 65kW Bosch
Condens GC7000WP 85kW Bosch Condens GC7000WP 100kW Bosch Condens GC7000WP
125kW Bosch Condens GC7000WP 145kW
Part number 7 736 702 194 7 736 702 195 7 736 702 196 7 736 702 197 7 736 702 198 7 736 702 199
2 Pump group (1 required per boiler)
Description
Pump group 70kW (3 bar PRV) (for use with 50kW and 65kW boilers)
Part number 7 736 701 864
Pump group 100kW (3 bar PRV) (for use with 85kW and 100kW boilers)
7 736 701 865
Pump group 150kW (4 bar PRV) (for use with 125kW and 145kW boilers)
7 736 702 214
3 Wall hung or frame set option
Wall hung Pump group insulation Pump group connection set
Part number 7 736 701 876 5 584 552
Floor standing frame TL1 frame set with insulation Pump group connection set
*TL1 floor standing frame available with flow and return headers if required, please contact your local CTM.
4 Hydraulic separation options (if required)
Low loss header**
Optional accessories Sinus LLH 180kW***
Part number 8 920 097 2
**Bosch 300kW LLH available if required, please contact your local CTM. ***Output requirements over 100kW must be designed to 20K T.
Plate heat exchanger
Optional accessories 50KW Plate heat exchanger 65KW Plate heat exchanger
80-100KW Plate heat exchanger 101-140KW Plate heat exchanger 141-180KW Plate
heat exchanger
Part number 7 733 600 013 7 733 600 014 7 733 600 016 7 733 600 017 7 733 600 018
Required accessories Temperature sensor pocket (R1/2″)
PHE connection type 1 ¼” Male BSPP flat face 1 ¼” Male BSPP flat face 1 ¼”
Male BSPP flat face 2″ Male BSPP flat face 2″ Male BSPP flat face
Part number 7 736 701 912 5 584 552
Part number 5 446 142
5 Controls
Bosch controls
Greenstar Sense II (interface controller) MM100 (one required per zone)
Part number 7 738 111 064
7 738 110 140
BMS integration MU100 Programmer
Part number 7 738 110 145
3rd party controls
Part number
RTH Converter
7 807 9
(included as standard with
50 and 65kW variants)
Single boiler packs 35
Boiler configurations Cascade boiler sets
Our Condens 7000 WP can be cascaded on a six boiler cascade frame set to
achieve up to 860kW.
An ideal choice for applications where space is restricted but there is a
demand for a modern high output, high efficiency heating solution. Control
strategies can provide cascade and sequencing for up to 16 boilers at a time
for up to 2.2MW of power.
1 Boiler
Description Bosch Condens GC7000WP 50kW Bosch Condens GC7000WP 65kW Bosch
Condens GC7000WP 85kW Bosch Condens GC7000WP 100kW Bosch Condens GC7000WP
125kW Bosch Condens GC7000WP 145kW
Part number 7 736 702 194 7 736 702 195 7 736 702 196 7 736 702 197 7 736 702 198 7 736 702 199
2 Pump group (1 required per boiler)
Description
Pump group 70kW (3 bar PRV) (for use with 50kW and 65kW boilers)
Part number 7 736 701 864
Pump group 100kW (3 bar PRV) (for use with 85kW and 100kW boilers)
7 736 701 865
Pump group 150kW (4 bar PRV) (for use with 125kW and 145kW boilers)
7 736 702 214
3 Cascade frame sets
Cascade setup Description
Part number
TL2
2 Boiler in-line cascade set with insulation
7 736 701 883
TL2
TL3
3 Boiler in-line cascade set with insulation
7 736 701 884
TL4
4 Boiler in-line cascade set with insulation
7 736 701 885
TL5
5 Boiler in-line cascade set with insulation
7 736 701 886
TL5
TL6
6 Boiler in-line cascade set with insulation
7 736 701 887
TL3
TL4
TL6
Cascade setup TR2 TR3 TR4 TR5 TR6
Description 2 Boiler back-to-back cascade set with insulation 3 Boiler back- to-back cascade set with insulation 4 Boiler back-to-back cascade set with insulation 5 Boiler back-to-back cascade set with insulation 6 Boiler back-to- back cascade set with insulation
Part number 7 736 701 888 7 736 701 889 7 736 701 890 7 736 701 891 7 736 701 892
TR2 TR5
TR3
TR4
TR6
4 Victaulic connections
Only required when NOT using a Bosch specified low loss header. If using a low
loss header skip to 6.
Cascade setup TL1 TL2/TR2 TL3/TR3 TL4/TR4 TL5/TR5 TL6/TR6
Description Victaulic 2.5″ to flange connection DN65 PN6 (Pack Qty. 2)
Victaulic 4″ to flange connection DN100 PN6 (Pack Qty. 2)
Part number 7 736 701 914
7 736 701 913
36 Cascade boiler sets
Boiler configurations Cascade with plate heat exchanger or low loss header
A plate heat exchanger can be used to separate the boiler from the system in both open vented and sealed systems. This provides greater protection for the boiler, especially where the water quality in the existing system is poor.
A low loss header is a device that hydraulically separates the boiler from the heating circuit. This helps to improve the efficiency and performance of the heating system by regulating the pressure and flow rate of the system.
5 Plate heat exchangers
Description 50KW Plate heat exchanger 65KW Plate heat exchanger 80-100KW Plate
heat exchanger 101-140KW Plate heat exchanger 141-180KW Plate heat exchanger
181-230KW Plate heat exchanger 231-280KW Plate heat exchanger 281-400KW Plate
heat exchanger 401-520KW Plate heat exchanger 521-640KW Plate heat exchanger
641-860kW Plate heat exchanger
Part number 7 733 600 013 7 733 600 014 7 733 600 016 7 733 600 017 7 733 600 018 7 733 600 020 7 733 600 021 7 733 600 023 7 733 600 025 7 733 600 026 7 733 600 027
PHE connection type 1 ¼” Male BSPP flat face 1 ¼” Male BSPP flat face 1 ¼” Male BSPP flat face 2″ Male BSPP flat face 2″ Male BSPP flat face 2″ Male BSPP flat face 2 ½” Male BSPP flat face 2 ½” Male BSPP flat face 2 ½” Male BSPP flat face 2 ½” Male BSPP flat face DN100 compact flange
6 Low loss header
Cascade Setup Description
TL1 TL2/TR2
Low loss header + Insulation 300kW
TL3/TR3
TL4/TR4 TL5/TR5
Low loss header + Insulation 900kW
TL6/TR6
Part number
Optional flanges
7 736 701 907 Threaded flange DN65 PN6
7 736 701 908 Threaded flange DN100 PN6
Part number 7 736 700 487
7 736 700 964
7 Controls
Bosch intelligent controls
8313 Control
Temperature sensor set EMS plus 200mm
FM-CM Module (cascade sequencer)
FM-MM Module (2 heating circuits)
FM-MW Module (1 heating, 1 hot water circuit)
Part number 7 736 602 245 7 735 600 656 7 736 602 098 8 718 598 828 8 718 598 831
Bosch sequencing controls Part number
MC400 Cascade sequencer
7 738 111 001
Temperature sensor set TF 7 735 600 657 HW EMS2 200mm (MC400 required accessory)
MM100 Zone control module
7 738 110 140
Greenstar Sense II (interface controller, MM100 required accessory)
7 738 111 064
BMS integration
MU100 Programmer (BMS interface module)
Part number 7 738 110 145
Cascade with plate heat exchanger or low loss header 37
Condens 7000 WP accessories
Pressure relief valve 4 bar
7-095-595 4 bar pressure relief valve for installation in the Condens 7000 WP
pump group.
Pressure relief valve 6 bar
7-736-700-914 6 bar pressure relief valve for installation in the Condens 7000
WP pump group.
Non-return valve return pipe
7-736-700-432 (Included in hydraulic frame kit) DN32 non-return valve. For
Condens 7000 WP installations not using the Bosch hydraulic cascade kit.
Connection set (hydraulic TL)
7-736-702-047 (Included in hydraulic frame kit) Connection set for hydraulic
cascade Condens 7000 WP boilers in a line (TL set up).
Connection set (hydraulic TR)
7-736-702-048 (Included in hydraulic frame kit) Connection set for hydraulic
cascade Condens 7000 WP boilers in a back-to-back configuration (TR set up).
Connection set (gas TL)
7-736-701-870 (Included in hydraulic frame kit) Gas connection set from pump
group to gas manifold. Front boiler assembly for Condens 7000 WP boilers in a
line (TL set up).
Connection set (gas TR)
7-736-701-872 (Included in hydraulic frame kit) Gas connection set from pump
group to gas manifold. Front boiler assembly for Condens 7000 WP boilers in a
back-to-back set up (TR set up).
RTH converter
7-807-9 RTH converter to enable the use of third party 230Vac controls.
Included as standard with the 50 and 65kW models.
38 Accessories
TL1 boiler frame set w. insul wo Gas
7-736-701-882 Single hydraulic frame kit (TL1 set up) with insulation for use
with the Condens 7000 WP boiler. Includes frame kit, insulation, hydraulic
headers and connection set (without gas header).
TL1 basic boiler frame set
7-736-701-912 Single frame kit (TL1 set up) with insulation for use with the
Condens 7000 WP boiler. Includes frame kit and insulation only.
Flange connection 2.5″ incl. victaulic
7-736-701-914 Hydraulic connections from victaulic 2.5 inch to flange DN65,
PN6 for the Condens 7000 WP hydraulic cascade kits. Please specify this when
using the cascade kit without low loss header or when using plate heat
exchangers (pack of 2).
Flange connection 4″ incl. victaulic
7-736-701-913 Hydraulic connections from victaulic 4 inch to flange DN100, PN6
for the Condens 7000 WP hydraulic cascade kits. Please specify this when using
the cascade kit without low loss header or when using plate heat exchangers
(pack of 2).
Gas cock
7-736-701-868 (Included in pump group) Gas isolating valve for Condens 7000 WP
pump group.
Victaulic coupling 2.5″
7-736-701-915 Victaulic coupling 2.5 inch (pack of 1).
Victaulic coupling 4″
7-736-701-916 Victaulic coupling 4 inch (pack of 1).
AS/HKV 32 connection set
5-584-552 Connection set for when using a pump group without hydraulic cascade
kit (1 1/4 inch).
Accessories 39
Training
Install with confidence
Learn all you need to know about the Condens 7000 WP commercial boiler range.
We specifically tailor all our product courses to meet your needs. This hands-
on course is perfect for those who want to specify and install the Condens
7000 WP boilers for commercial and domestic applications.
Supporting you
Our courses are here to support your installation from beginning to end. The
Condens 7000 WP course covers: Specification and installation Service and
maintenance Fault finding and diagnostics Our product training courses will
help you get hands-on experience and understand all the features and benefits.
Scan to start your training: worcester-bosch.co.uk/eacademy
Get in touch
Sales Tel: 03330 608 456 Email: commercial.industrial@uk.bosch.com
Technical Helpline Tel: 0330 123 0165 Email: technical-advice@uk.bosch.com
Controls Helpline Tel: 0330 123 3641
Training Tel: 0330 123 0166 Email: training@uk.bosch.com
Share
We would love to see your installations! Bosch Commercial Industrial Bosch
Industrial UK
Bosch Commercial and Industrial Cotswold Way, Warndon, Worcester. WR4 9SW
bosch-industrial.co.uk
Calls to and from Bosch Thermotechnology Ltd may be recorded for training and
quality assurance purposes. This brochure is accurate at the date of printing,
but may be superseded and should be disregarded if specification and/or
appearances are changed in the interest of continued improvement. The
statutory rights of the consumer are not affected.
8-716-111-872-0 G 12/23
References