BOSCH 65kW Worcester Condens Commercial Boiler Instruction Manual

June 10, 2024
Bosch

65kW Worcester Condens Commercial Boiler

“`html

Specifications

  • Outputs: 50kW, 65kW, 85kW, 100kW, 125kW, 145kW

  • Cascading: Up to 6 boilers per bank, providing up to 858.6kW at
    50/30 per bank

  • Applications: Large domestic properties, multi-family housing,
    commercial installations

  • Output Flexibility: Control strategies for cascade and
    sequencing up to 16 boilers at a time, up to 2.2MW power

  • Efficiency: Up to 96.5% seasonal efficiency, low emissions with
    class 6 levels of NOx as low as 25mg/kWh @ 0% O2

Product Usage Instructions

Installation

1. Ensure proper space requirements are met for
installation.

2. Follow the provided installation guide for single or cascade
applications.

Maintenance

1. Access components from the front for easy maintenance.

2. Regularly check and clean the heat exchanger for optimal
performance.

Commissioning

1. Register the product for warranty and commissioning
purposes.

2. Use the touch-screen display for faster commissioning and
fault-finding.

Operation

1. Set the desired heat output using the modulation feature to
match the heat demand.

2. Monitor the boiler’s performance and efficiency
regularly.

FAQ

Q: What are the typical use cases for the Condens 7000 WP?

A: The boiler is suitable for large domestic properties,
multi-family housing, and commercial installations. It can also be
used in combination with high output heat pumps.

Q: What is the warranty period for the Condens 7000 WP?

A: The product comes with a 5-year guarantee for peace of
mind.

Q: Does the boiler have energy-saving features?

A: Yes, each boiler can automatically modulate its output to
precisely match the heat demand, reducing fuel consumption and
improving overall seasonal efficiency.

“`

Condens 7000 WP Technical and specification guide
Quick installation, easy maintenance
5

Installer guide

Contents

Product overview

4

Typical use cases

31

Features and benefits

5

Single boiler application

31

Technical data

6

Cascade application

33

Installing a cascade

7

Getting started

34

Product breakdown

8

Registration / commissioning

34

The inside story

8

Packs and part numbers

35

Specification considerations

12

Single boiler packs

35

Space requirements

12

Cascade boiler packs

36

Water system connections

16

Accessories

38

Controls

19

Flues and ventilation

24

Training Courses

Our commercial trainers have many year’s experience as technical heating technicians and deliver first-class training across a wide range of products, including the Bosch Condens 7000 WP.
To book onto one of our Bosch Condens 7000 WP training courses:

Email training@uk.bosch.com

Visit our eAcademy worcesterbosch-academy.co.uk

*Terms & conditions apply. Please visit bosch-industrial.co.uk/guarantee-terms-and-conditions for details.

Why install the Condens 7000 WP?

5

Guaranteed
5 years peace of mind for you and your customers*

Quick installation
Rapid installation thanks to our new frame kit design

Efficient
Automatic modulation to match heat demand

Easy maintenance
Components accessible from the front

Connected
Touch-screen display for faster commissioning and fault-finding

High output
Outputs from 50kW up to 145kW with the ability to cascade up to 860kW

Condens 7000 WP 3

Product overview

Available in outputs of 50kW, 65kW, 85kW, 100kW, 125kW and 145kW. The Condens 7000 WP can be cascaded in banks of up to 6 boilers per bank providing up to 858.6kW at 50/30 per bank.

Applications
Our Condens 7000 WP is a wall-hung boiler suitable for large domestic properties, multi-family housing and commercial installations. It can also be used in combination with high output heat pumps to create a flexible hybrid solution.

Output flexibility and compact size
An ideal choice for applications where space is restricted but there is a demand for a modern high output, high efficiency heating solution. Control strategies can provide cascade and sequencing for up to 16 boilers at a time for up to 2.2MW of power.

High efficiency, low emissions

Our Condens 7000 WP boosts seasonal efficiencies of up to 96.5% using the much loved ALU plus heat exchanger with class 6 levels of NOx as low as 25mg/kWh @ 0% 02.**

Hydrogen blend ready
Our entire gas boiler range is able to run on a 20% hydrogen blend ­ so your customer can be confident it will run on gas for it’s lifetime.

Precise energy management
Each boiler can automatically modulate its output to precisely match the heat demand, reducing fuel consumption and improving overall seasonal efficiency.

With cascades, modulation is from the lowest output of the smallest boiler up to the total load of all the boilers. The 50-100kW products can modulate at a ratio of 1:5 and both the 125kW and 145kW boilers modulate at 1:6.

Time and cost saving
The boiler’s small footprint increases installation flexibility, speeds up installation time and improves access for servicing and maintenance, reducing the need to have larger boiler rooms to achieve higher system outputs.

Patented ALU-Plus heat exchanger
The maintenance-reducing heat exchanger is lightweight, robust and allows for a rapid transfer of heat. Combined with its fully insulated case, the boiler is especially quiet in the industry, with our 50kW model being Quiet Mark certified.

*Quiet Mark certification applicable to the Condens 7000 WP 50kW single boiler. **Applicable to GC7000 WP 50kW model variant only. Please refer to technical data table on page 6.
4 Product overview

Features and benefits

Eye-level control ­ for easier commissioning
Innovative control display ­ simple, self-explanatory menu guidance with colour display and touch buttons
C8 heat exchanger ­ continuously optimised over the past 15 years
Front cover ­ easy to remove with just one click
Electrical connection ­ easily accessible from the top with reliefs for secure cables, MM100 module can be installed
Exhaust gas connection ­ 100/160 as standard, rotatable by 360o, flue gas measuring points integrated
Everything is ready ­ PWM cable connection for the pump group for easy connection
Easy to assemble ­ simple and safe handling thanks to ergonomic handle design

Additional features and benefits
Condensing technology with up to 108.7% net efficiency ­ saves fuel compared to a standard efficiency boiler
Modulation to just 20% of total output* ­ year round efficiency according to seasonal demand
Cascade frame kits can be combined with site made hydraulic arrangements
Low emission levels ­ cleaner combustion and increased carbon savings
Expect to save up to 60% on the average installation time compared to GB162 V2**

Integrates with solar thermal installations ­ maximise savings from solar hot water
Individual lift weight only 74kg for 50­100 models
Easy manoeuvrability with built-in handles
Flexible control options, including Control 8000, Sense II and BMS System ­ increased system functionality and reduced running costs
LPG conversion available ­ suitable for off mains locations.

*Modulation range will vary depending on model and system operating temperatures. **Time savings estimated and observed during customer installation studies. Ensure safe lifting methods and sufficient people appropriate for the weight to be lifted.

Features and benefits 5

Technical data

Condens 7000 WP Nominal heat output @ 80/60 °C

Nominal heat output @ 50/30 °C

Rated heat input

Net efficiency (partial load 30% in accordance with EN15502)

Seasonal efficiency (as L2B)

ErP class and seasonal efficiency

Standby loss (in accordance with EN15502)

Maximum working pressure

Maximum flow temperature

Maximum flow rate @ T=20k

Required flow rate @ T=20k

Resistance @ required flow rate (boiler only)

Maximum condensate rate

Noise level @ 1m

Full load

Fuel type

Gas category according to EN 437

Gas pressure ­ min/max

Gas rating ­ natural gas (G20)

Gas rating ­ LPG (G31)

CO2 content ­ NG (G20)

Full load Part load

CO2 emission G20

Full load

NOx emission G20 @ full load (in accordance with EN15502)

Residual head of fan

Flue gas mass flow rate

Full load

Flue gas temperature @ 80/60 °C

Part load Full load

Flue gas temperature @ 50/30 °C

Part load Full load

Flue type

Mains connection voltage / phase

Power supply rating

Electrical ingress protection

Electrical power consumption (without pump group)

Standby Part load Full load

Unit kW kW kW % % % % bar °C l/h l/h mbar l/h dB(A)
mbar m³/h m³/h
% ppm mg/kWh Pa g/s
°C °C
V
tW

50 kW

65 kW

85 kW

100 kW

13.0 ­ 46.5 13.0 ­ 62.6 18.9 ­ 80.0 19.0 ­ 94.5

14.3 ­ 49.9 14.3 ­ 69.5 20.8 ­ 84.5 20.8 ­ 99.5

13.3 ­ 47.5 13.3 ­ 64.3 19.3 ­ 82.0 19.3 ­ 96.5

125 kW
24.1 ­ 116.9
26.2 ­ 124.4
24.5 ­ 118.1

145 kW
24.1 ­ 138.8
26.2 ­ 143.1
24.5 ­ 140.1

108.4

108.7

109.1

108.7

109.3

109.6

96

96.3

96.5

96.2

96.7

97

A / 93

N/A

0.24

0.18

0.14

0.12

0.12

0.15

2200

6 *

85

5000

3000

3600

4300

7000

5300

6300

75

130

170

240

312

430

6 55
5.03 1.94 9.3 8.4 31

7.6 61
6.8 2.62 9.3 8.4 63

9.3

11

13.5

61 **

64 **

65**

Natural gas H (G20) ­ LPG (G31)

GB/IE II2H,3P 20;37mbar

Natural gas 17/25 ­ LPG 25/45

8.68

10.21

12.63

3.34

3.93

4.86

9.1

9.1

8.8

8.2

8.1

8.3

70

81

76

16.0 69**
15.14 5.83 8.7 8.3 85

25

34

34

38

35

38

71 21.6 56 59 32 39
2 8 31

130

162

226

145

29.2

38

44.7

56.3

56

56

56

56

62

66

72

67

32

34

34

43

50

53

50

B23, B53, C13, C33, C43, C53, C63, C83, C93

230 / single phase

230 VAC, 50 Hz, 130 Watts

IPX0D

2

2

2

2

8

12

12

15

65

88

133

145

200 67.5 56 71 53
2 15 243

*Standard 3 bar safety valve for 50kW to 100kW pump group and 4 bar safety valve for 125kW & 145kW. 4 & 6 bar safety valves available as accessory. **Noise level for 85, 100, 125 & 145 kW are indicative values.

6 Technical data

Installing a cascade
Our brand new installation concept allows you to install the boiler in less than half the time of its predecessor, the GB162 V2*. Building from the ground up allows you to quickly and efficiently install the Condens 7000 WP.

To help familiarise yourself with the installation process, there are step-by- step installation videos available as a guide on our website:
bosch-industrial.co.uk/condens7000

*Time savings estimated and observed during customer installation studies.

Installing a cascade 7

Product breakdown

The inside story
GC7000WP 50-100kW

GC7000WP 125-145kW

4 1

4 1

5

2

2

6 6

5

3
1 Basic controller BC30.2 for EMS plus 2 Ceramic burner with modulation
ratio up to 1:5 3 Mounting option on the base frame
for floor installation with “push and click-in” function for easy assembly 4 Simple connection of the control components from the top 5 All components accessible from the front for ease of maintenance and service 6 Patented ALU- Plus heat exchanger
8 The inside story

3
1 Basic controller BC30.2 for EMS plus 2 PFK grade burner with modulation
ratio up to 1:6 3 Mounting option on the base frame
for floor installation with “push and click-in” function for easy assembly 4 Simple connection of the control components from the top 5 All components accessible from the front for ease of maintenance and service 6 Patented ALU- Plus heat exchanger

Hydraulics, gas, pump connections and handles
Front gas connection for easy access Easy electric connection box at
bottom for pump group connections Comfortable bottom handles
for confident handling “Slide and guide” ­ self-guiding
transport slides Hydraulic CH connection

Modulating pump groups

Pump connection group for 50 and 65kW

Pump connection group for 85-145kW

5 1

9

5

9

1

4 2

4 2

3

8

7 3

8

7

6

6

1 Pressure Relief Valve (PRV)
2 Manometer

3 Service valve supply 4 Gas cock 5 Y-piece connector

Pump connection group for 50 and 65kW with WILO-Para STG 25/8
Supplied with 3 bar PRV as standard

6 Service valve return 7 Drain valve

8 Expansion vessel connection
9 Pump

Pump connection group for 85 and 100kW with Wilo-Para Maxo 8
85 and 100kW pump group supplied with 3 bar PRV as standard
Pump connection group for 125 and 145kW with WILO-Stratos PARA C-12
125 and 145kW pump group supplied with 4 bar PRV as standard

Upgrade your PRV

Product code Pressure relief valve 4 bar (50-145kW) Pressure relief valve 6 bar (50-145kW)

Part number 7-095-595 7-736-700-914

The inside story 9

Heat exchanger
Patented ALU-Plus heat exchanger
The precision engineered heat exchanger is constructed from a cast aluminium silicate compound which is lightweight, robust and allows for a rapid transfer of heat.
The heat exchanger uses the latest ALU-Plus technology that has been developed by us, to increase durability and optimise efficiency. Fins on the outside of the aluminium tubes increase the exterior surface area so that more hot flue gas c omes into contact with the heat exchanger.
A spiral channel on the inside of the tube increases the internal surface area, bringing more water in contact with the heating surface and ensuring an optimum heat transfer. The wide channels on the heat exchanger ensure that the flow resistance is minimised and this, combined with its fully insulated case, makes the Condens 7000 WP incredibly quiet in operation.

Plasm-polymerised heat exchanger
The surfaces of the heat exchanger’s tubes are treated using a patented plasma-polymerisation process which leaves the surfaces so smooth that the heat exchanger effectively stays clean as no deposits can adhere to them.
Its extremely high efficiency is maintained and there is no need for mechanical cleaning; the heat exchanger can be simply flushed through during servicing.

Heat Cell 50-100kW

Heat Cell 125-145KW (C8)

7 10
3 5 6

8 19 2
4

10 7 2
1 11
8
3 4
5 6
9

1 Flue exhaust 110mm
2 Fan
3 Spark igniter, ionization sensor
4 Side wall mounting in boiler casing
5 Supply temperature limiter switch

6 Condensate tray 7 Secured gas way
EPDM tube 8 Gas valve 9 Air suction pipe 10 Auto air vent

1 Flue exhaust 110mm
2 Fan
3 Spark igniter, ionization sensor
4 Back wall mounting in boiler casing
5 Supply temperature limiter switch

6 Condensate tray with inspection opening
7 Secured gas way EPDM tube
8 Gas valve
9 Air suction pipe
10 Auto air vent
11 Integrated flue non-return valve

10 The inside story

Wiring and connections

The control design ensures you have top access to do your input and output connections. The unit has integrated cable routing to keep the wiring neat. One EMS plus module (such as the MU100 for 0-10v connection to a BMS system) can be integrated into the boiler.

Low voltage connections

High voltage connections

1 2

Control unit

1 Flue connection DN110/160
with integrated air supply grille HMI
2 Slot-in option for EMS plus module

Control display
Full colour display (38.5mm x 50.7mm) with touch buttons

1 2

3 4

8
7 5
6

1 Burner indicator 2 Heating button 3 Hot water button 4 Menu button 5 Button OK
Chimney sweep mode

6 Return button
7 Heating water pressure indicator
8 Buttons and

The inside story 11

Specification considerations

These pages provide an overview of the main installation and system requirements for the Condens 7000 WP. The full installation instructions supplied with the boiler must be adhered to before any work on the heating system takes place.
Space requirements

The Condens 7000 WP can be wall-mounted or as part of a cascade frame. When considering the final mounting position, it is important the required service and maintenance clearances are taken into account.

Minimum space required for the boiler:
Provide an unobstructed space of at least 100cm in front of the boiler to allow maintenance to be carried out.

Distance from walls at sides:
Maintain a clearance of at least 5mm on either side of the boiler.
See page 9 of installation manual for full clearances.

CAD and BIM
Files are available for download in DWG and RFA format from the website here: https://www.bosch-industrial.com/bim

50-100kW boiler
GC7000WP boiler on frame

GC7000WP boiler on wall

125 and 145kW boiler
GC7000WP boiler on frame

GC7000WP boiler on wall

12 Space requirements

Space requirements 13

In-line (TL) arrangement
GC7000WP TL front

GC7000WP TL 50-100kW

GC7000WP 125 and 145kW

Back-to-back arrangement

GC7000WP TL front

GC7000WP TL 50-100kW

GC7000WP 125 and 145kW

Orientation TL1 TL2 TL3 TL4 TL5 TL6

X1 + Y1 (mm) 520 + 50 = 570 1045 + 50 = 1095 1570 + 50 = 1620 2095 + 50 = 2145 2620 + 50 = 2670 3145 + 50 = 3195

Orientation TL1 TL2 TL3 TL4 TL5 TL6

X1 mm (boiler) 520 1045 1570 2095 2620 3145

Y1 mm (spigot) 50 50 50 50 50 50

L1 mm (LLH length) 492.8 492.8 796.5 796.5 796.5 796.5

Overall (mm) 1062.8 1587.8 2416.5 2941.5 3466.5 3991.5

14 Space requirements

Orientation TR2 TR3 & TR4 TR5 & TR6

X1 + Y1 (mm) 520 + 50 = 570 1045 + 50 = 1095 1570 + 50 = 1620

Orientation TR2 TR3 & TR4 TR5 & TR6

X1 mm (boiler) 520 1045 1570

Y1 mm (spigot) 50 50 50

L1 mm (LLH length) 492.8 492.8 796.5

Overall (mm) 1062.8 1587.8 2416.5

Space requirements 15

Water system connections

When to use a low loss header or plate heat exchanger The Condens 7000 WP must be installed on a sealed system in accordance with BS EN 12828.
For open vented systems or systems that are particularly contaminated, a plate heat exchanger should be used to separate the boiler circuit from the main system. Matched plate heat exchanger packs for the boiler or cascade output capacity are available to make selection simpler (see control section for guidance on positioning of flow temperature sensor).
For clean sealed systems where multiple heating circuits or DHW circuits controlled by separate pumps are used, it is necessary to incorporate a low loss header. Cascade kits with the appropriately sized low loss header included are available as a pack (please refer to page 35 for part numbers). The low loss header acts to hydraulically separate the boiler pump groups from the heating circuit pumps and avoids hydraulic issues that could affect the correct control of the heating system. Always use a low loss header (or plate heat exchanger) where there is more than one pump in the system.

Residual pump head For single boiler applications, the matched boiler pump group has been selected to cope with typical radiator heating systems that are constructed in accordance with UK building regulations requirement of separating zones above 150m2. Under these circumstances the residual head available from the boiler pump should be sufficient to cope with most typical radiator heating circuit resistance.
For older heating circuits that do not comply with modern building regulations, or for applications with high system resistance, a low loss header should be used.

50 and 65kW residual pump head

Head (mbar)

900 800 700 600 500 400 300 200 100
0 0

500

1000

Heat cell resistance Residual head @ 100% pump

1500

2000

Flow rate (l/h)

Heat cell + connection Residual head @ 65% pump

2500

3000

3500

Heat cell + connection + check valve

85 and 100kW residual pump head

Head (mbar)

900 800 700 600 500 400 300 200 100
0 0

500

1000

1500

Heat cell resistance Residual head @ 100% pump

2000

2500

3000

Flow rate (l/h)

Heat cell + connection Residual head @ 65% pump

3500

4000

4500

5000

Heat cell + connection + check valve

125 and 145kW residual pump head

Head (mbar)

1400 1200 1000
800 600 400 200
0 0

1000

2000

Heat cell + connections Residual head @ 80% pump

3000

4000

Flow rate (l/h)

Heat cell + connection + check valve

5000

6000

7000

Heat cell resistance Residual head @ 100% pump

16 Water system connections

Water system connections 17

Maximum temperature difference
Heating systems designed for use with condensing boilers such as our Condens 7000 WP are at their most efficient when the return temperature is below 55 degrees. To help achieve these conditions, industry guidance recommends rebalancing older heating systems designed to operate at 82/71 to 80/60 (T 20K). When this is combined with weather compensated heating circuit operation, the return temperature will regularly be below 55 degrees on all but the coldest days.
However, the maximum temperature difference should be kept below T 25K. Above this temperature difference the boiler will modulate its output to ensure it continues to operate safely.
Water quality
We strongly recommend thoroughly flushing the system before filling it and using only untreated tap water when filling the system. The use of dirty water will lead to build-ups of sediment and corrosion, which can result in the boiler malfunctioning and cause damage to the heat exchanger.
Do not treat the water with pH-adjusting substances (chemical additives) or anti-freeze (other than Fernox Alphi 11) or water softeners. Sentinel X100 or Fernox MB1 can be used to achieve the desired water quality. The concentration of Sentinel or Fernox should be in accordance with the manufacturer’s instructions for the volume of the water in the system.
Water treatment following the requirements of VDI 2035 may be used.
The pH of the heating system must be between 7 and 8.5. If this is not the case, please contact our technical support team before proceeding, tel. 0330 123 9229.
Artificially softened water must not be used with the Condens 7000 WP.
Quality of the pipe work
When using plastic pipe work in the heating system, e.g. for underfloor heating, it has to be oxygentight according to the relevant UK standards. If plastic pipes do not comply with these standards, the system parts must be separated using a plate heat exchanger.

Filling the system (water regulations)
In the UK, methods for filling heating systems are covered by the water regulations. The regulations ensure that backflow of contaminated heating system water does not enter the water supply. It is important to understand these requirements and how they relate to the type of building (house or non- house) as well as the boiler output size.
For most non-domestic applications there will be a need to comply with fluid categories 4 and 5, meaning that a simple filler loop cannot meet the requirements.
Gas supply requirements
Low gas pressure will lead to reduced boiler outputs, so it is important to ensure the gas installation can provide the necessary supply capacity and pressures.
For natural gas, the inlet supply pressure should be within 17mbar to 25mbar (see installation manual for guidance when measuring gas pressures as the appliance gas multi-function valve).
Before installation commences, the capacity of the gas meter supply should be checked to be sufficient for all of the gas appliances connected to the installation.
For the 50 and 65kW boilers in domestic properties where installers carrying out the installation hold domestic ACS qualifications only, the installation of the gas supply must comply with IGE/UP/1b. This means that the gas meter must be no greater than 16m3/h, the pipework no more than 35mm and the installation volume does not exceed 0.035m3.
LPG conversion
LPG conversion kits are available for all of the outputs. For LPG installations, the gas supply pressure should be between 25mbar and 45mbar with adequate protection for over and under pressure.
Ensure the siting of the appliance is not below ground level and that low level ventilation meets the requirements of the appropriate standard.
Available conversion sets

Product Conversion set 3P (G31) (45-50KW) Conversion set 3P (G31) (60-70KW) Conversion set 3P (G31) (80-85KW) Conversion set 3P (G31) (90-100KW) Conversion set 3P (G31) (125KW) Conversion set 3P (G31) (145-150KW)

Part number 7-736-702-378 7-736-702-379 7-736-702-380 7-736-702-381 7-736-701-860 7-736-701-861

18 Water system connections

Which control is right for my install?
There are a range of control options for differing applications when using the Condens 7000 WP either as a single boiler or as a cascade. Please use our handy guide below to find the one best suited for your install.

YES

Single boiler installation?
NO (cascade)

Internet connection needed?

BMS led?

YES

NO

YES

NO

Go to A on page 20

Go to B on page 20

BMS controlling sequencing?

YES

HYBRID

Internet connection
needed?

YES

NO

Go to D on page 21

Go to E

Go to E

on page 22 on page 22

NO

Go to F on page 23

Go to C on page 21

Controls 19

A Single boiler installation ­ internet-connected controls

Bosch EasyControl controller 7-736-701-341 (white) 7-736-701-392 (black)
The Bosch EasyControl is a smart internetconnected room thermostat, offering a simple, stylish and intuitive solution to optimise home comfort.
When combined with our Smart TRVs, homeowners can easily control the heating in each individual room, to achieve the perfect heating environment (feature only available for 50-100kW models).
The device can be connected to the boiler using a 2-core cable.

3 way valve 7-736-701-881
3 way valve allows for priority DHW generation, must be used in conjunction with a Sense II or EasyControl.
Plugs into the boiler’s harness plug ­ 1 1/4″ connections.
You must ensure that the cylinder coil is rated to at least 50% of the boiler’s output. If demand is lower than 50%, refer to control option B, below.

B Single boiler installation ­ standard controls
If an internet connection is not required for your install, the Sense II controller in combination with expansion modules MM100 can be used. Where the system also includes solar thermal, either the MS100 or MS200 can be used. Where there are multiple heating circuits, a Sense I can be used to give individual zone control.
Sense II 7-738-111-064 The Sense II control platform uses the EMS 2 Energy Management System which allows advanced functions such as weather compensated control and optimum start.
Weather compensation is particularly useful for larger buildings where it can be difficult to locate a good reference room to suit the area being heated. A north facing outside sensor is used to determine the correct flow temperature needed to achieve the desired room temperature, based on a heating curve. Local TRV’s on radiators, for example, can then fine tune the final room temperature to suit the occupants.
Using weather compensation allows lower flow temperatures for large parts of the heating season, which in turn leads to lower return temperatures to help make the condensing boiler more efficient.

MM100 7-738-110-140 Used for additional heating circuit (maximum of 4) or additional DHW circuit (maximum of 1).

MS100 7-738-110-144
Module for integration of solar thermal panels.

20 Controls

The benefits of weather compensation

The Sense II controller can change the required temperature for different heating circuits according to the outside temperature and is measured using a small external sensor.
With mixed heating circuits this means that each individual circuit has its own characteristics and the boiler will supply only the heat needed for certain parts of the system. This is particularly effective in Spring and Autumn so temperatures for the heating circuits can be reduced significantly ­ saving fuel and allowing the highest efficiency from the condensing process.

Flow Temp oC 45 62 75

Outside Temp oC 10 0 -10

Flow temperature oC

90

80

70

60

50

40

30

20 +15 +10 +5 0

-5 -10 -15 -20

Outside temperature oC

The graph above shows how the heating curve can be modified at any time using the Sense II controller, providing maximum comfort for the user.

C Cascade installation ­ BMS Led (Bosch controlling sequencing)
MC400 cascade sequencer 7-738-111-001 The MC400 simplifies the optimum running of a cascade system when interfacing with an existing BMS.
By rotating the lead boiler it eliminates excessive wear in any one unit and also interprets the 0-10V input signal from the BMS to modulate the heat output of the cascade. This is all achieved without the need for programming or complex set up and is a true “plug and play” control.
An individual MC400 can control up to 4 boilers and up to 16 boilers can be achieved when five MC400 units are linked together, up to 2.2MW.
Wet sensor (part number 7-735-600-657) must be used in conjunction with the MC400 cascade sequencer.
D Cascade installation ­ BMS Led (BMS controlling sequencing)
MU100 BMS interface module 7-738-110-145 The MU100 is used for each individual boiler and modules when interfacing with an existing BMS.
It can create a 230V fault signal, and has a 0-10V contact for signals from the BMS to control the boiler flow temperature.
Controls 21

E Cascade installation ­ internet-connected controls
BFU room thermostat 5-720-720 The BFU is a remote control which allows the temperature to be adjusted from the end user’s living or working space. This includes a room temperature sensor.
Bosch CC8313 intelligent commercial control 7-736-602-245 The CC8313 is an intelligent commercial control offering internet-connected remote access and weather compensation as standard.
The control unit has the ability to work alongside or independent of a BMS system. With the addition of plug-in function modules, the CC8313 can be expanded to cascade boilers, add multiple heating circuits and provide control of two separate DHW circuits.
The CC8313 can control a DHW circuit as standard, additional function modules will be required for mixed or unmixed heating circuits. The CC8313 has the space available for up to four additional function modules.
Wet sensor (part number 7-735-600-656) must be used in conjunction with this control (please refer to page 21 for more details).

165mm

F Cascade installation ­ standard controls
Gives cascade control for use with existing heating and hot water time and temperature controllers.
MC400 cascade controller 7-738-111-001 For heating systems where an existing control system will be reused and is not capable of sequencing and rotating a cascade, the MC400 is the perfect solution. The MC400 can control up to four boilers as a single control unit, but can be connected to other MC400 controllers to control up to 16 boilers (requires five MC400s). The controller will sequence the boilers to match the demand and rotate the lead boiler to ensure even use across the cascade.
MC400 has several different configuration options that allow 0-10VDC or 230V enable signals from an existing external controller. A 230V alarm signal is also available to indicate a fault situation.
A flow sensor (part number 7-735-600-657) is required for the low loss header or plate heat exchanger.

FM-MW heating and DHW control module 8-718-598-831
This controls one mixed or one unmixed heating circuit and one DHW circuit (with cylinder load and circulation pump).
All wiring has colour coded plugs for quick installation into the main control unit (BFU as accessory).

FM-MM heating circuit control module 8-718-598-828
This controls up to two mixed or unmixed circuits. Comes supplied with one FV/FZ temperature sensor.
All wiring has colour coded plugs for a quick installation into the main control unit (BFU up to 2x as accessory). An additional FV/FZ sensor is required if using two mixed circuits.

FM-CM cascade control module 7-736-602-098
The FM-CM can control the modulation and sequencing strategy from 2 to 4 boilers. A 0-10V input, for use with the BMS control.

22 Controls

Available controls, modules and sensors

Product Programmer MU100 MM100 mixer and LLH module MC400 cascade sequencer MS200 intelligent solar module Greenstar Sense II Greenstar Sense I CC8313 intelligent commercial control Control CC8310 (module extension) Module FM-CM

Part number 7-738-110-145 7-738-110-140 7-738-111-001 7-738-110-146 7-738-111-064 7-738-110-054 7-736-602-245 7-736-605-958 7-736-602-098

Product Module FM-MW Module FM-MM Module FM-AM FV/FZ temperature sensor set VPN router ERT50 Module FM-RM (VPN router mounting rail) Flow sensor (8313 controller) Flow sensor (MC400 controller)

Part number 8-718-598-831 8-718-598-828 7-736-602-079 5-991-376 7-736-603-505 8-732-900-362 7-735-600-656 7-735-600-657

Controls 23

Flues and ventilation

The topic of fluing and ventilation for commercial boilers is a detailed one that crosses several industry standards and regulations.

To help guide installers and system designers, we have produced a dedicated flue and ventilation guide for commercial installations, which is available to download from our website.
Additionally, a separate flue manual is available for the Condens 7000 WP boiler range, also downloadable from our website.

Concentric flue options Standard flue options are available for individual boilers using room sealed (RS) concentric flue systems. The Condens 7000 WP has an extensive range of concentric flue components available for horizontal, vertical and plume management terminations.
C13 and C33 concentric flue lengths and reductions The following equivalent flue lengths and reduction for bends are applicable to the Condens 7000 WP boiler range.

7000 WP boiler series

horizontal room sealed fluing options

Horizontal room sealed flue

Maximum equivalent 110/160 mm flue lengths

7000 WP 50kW

11m

90° Bend 1.5m

7000 WP 65kW

16m

1.5m

7000 WP 85 kW

11m

1.5m

7000 WP 100 kW

12m

1.5m

7000 WP 125 kW

3m

1.5m

7000 WP 145 kW

3m

1.5m

45° Bend 0.5m 0.5m 0.5m 0.5m 0.5m 0.5m

24 Flues and ventilation

110/160mm horizontal room sealed flue accessories

Components

Part number 7-738-113-669

Description
110/160mm dia. horizontal flue kit

7-738-113-100 7-738-113-099 7-738-113-101 7-738-113-105 7-738-113-104 7-738-113-103 7-738-113-102 7-738-113-677

110/160mm dia. 1m flue extension
110/160mm dia. 0.5m flue extension
110/160mm dia. 2m flue extension
110/160mm dia. 87º bend
110/160mm dia. 45º bend
110/160mm dia. 30° bend
110/160mm dia. 15° bend
Flue wall clamps 160mm dia. (pack qty. 3)

110/160mm horizontal flue kit

1 x wall finishing plate (white)

1 x external flue terminal (stainless)

1 x external wall finishing plate (stainless)

1 x 87º bend
1 x horizontal flue (500mm length)

Part No. 7-738-113-669

Standard horizontal flue assembly

Extension flue horizontal

Components

Part No. 110/160mm

7-738-113 669

Maximum lengths (mm) & no. of components required

7000 WP 50kW

1115mm

1

7000 WP 65kW

1115mm

1

7000 WP 85kW

1115mm

1

7000 WP 100kW

1115mm

1

7000 WP 125kW

1115mm

1

7000 WP 145kW

1115mm

1

Extension flue horizontal using a second 90º bend

Components

Part No. 110/160mm 7-738-113-669 7-738-113-100

Maximum lengths (mm) & no. of components required

7000 WP 50kW

11,000mm

1

up to 10

7000 WP 65kW

16,000mm

1

up to 15

7000 WP 85kW

11,000mm

1

up to 10

7000 WP 100kW

12,000mm

1

up to 11

7000 WP 125kW

3,000mm

1

up to 2

7000 WP 145kW

3,000mm

1

up to 2

Note: The maximum flue length must be reduced by the following amounts for each bend used.

7000 WP 50, 65, 85, 100, 125, 145kW 110/160mm flue
45° bend
87° bend

0.5m 1.5m

Components

Part No. 110/160mm

7-738-113-669 7-738-113-100 7-738-113-105

Maximum lengths (mm) & no. of components required

7000 WP 50kW 9.500mm

1

up to 8

1

7000 WP 65kW 14,500mm

1

up to 13

1

7000 WP 85kW

9,500mm

1

up to 8

1

7000 WP 100kW

10,500mm

1

up to 9

1

7000 WP 125kW

1,500mm

1

N/A

1

7000 WP 145kW

1,500mm

1

N/A

1

Flues and ventilation 25

Extension flue horizontal and upwards

Extension flue upwards and horizontal using a second 90º bend

Components

Part No. 110/160mm

7-738-113-669 7-738-113-100 7-738-113-105

Maximum lengths (mm) & no. of components required

7000 WP 50kW 11,000mm

1

up to 10

0*

7000 WP 65kW 16,000mm

1

up to 15

0*

7000 WP 85kW 11,000mm

1

up to 10

0*

7000 WP 100kW 12,000mm

1

up to 11

0*

7000 WP 125kW 3,000mm

1

up to 2

0*

7000 WP 145kW 3,000mm

1

up to 2

0*

*Horizontal flue kit includes a 90° bend.

Components

Part No. 110/160mm

7-738-113-669 7-738-113-100 7-738-113-105

Maximum lengths (mm) & no. of components required

7000 WP 50kW 9,500mm

1

up to 8

1*

7000 WP 65kW 14,500mm

1

up to 13

1*

7000 WP 85kW 9,500mm

1

up to 8

1*

7000 WP 100kW

10,500mm

1

up to 9

1*

7000 WP 125kW

1,500mm

1

N/A

1*

7000 WP 145kW

1,500mm

1

N/A

1*

*Horizontal flue kit includes a 90º bend, therefore only 1 additional bend needs to be ordered.

Notes: The short 0.5m flue extension may be used
as an alternative to the standard extension.
The maximum flue length must be reduced by the following amounts for each bend used.

7000 WP 50, 65, 85, 100, 125, 145kW 110/160mm flue
45° bend
87° bend

0.5m 1.5m

26 Flues and ventilation

7000 WP boiler series vertical room sealed fluing options

Vertical room sealed flue

Maximum equivalent flue lengths
7000 WP 50kW

110/160 mm 21m

90° Bend 1.5m

7000 WP 65kW

22m

1.5m

7000 WP 85kW

16m

1.5m

7000 WP 100kW

16m

1.5m

7000 WP 125kW

5m

1.5m

7000 WP 145kW

5m

1.5m

45° Bend 0.5m 0.5m 0.5m 0.5m 0.5m 0.5m

110/160mm vertical flue kit
1 x flue terminal 1 x support bracket 1 x inner duct 1 x outer duct
Part No. 7-738-113-668

110/160mm vertical room sealed flue accessories

Components

Part number 7-738-113-668

Description
110/160mm dia. vertical flue kit

7-738-113-100 7-738-113-099 7-738-113-101 7-738-113-105 7-738-113-104 7-738-113-103 7-738-113-102 7-738-113-677 7-738-113-126
7-738-113-127
7-738-113-128 7-738-113-129

110/160mm dia. 1m flue extension
110/160mm dia. 0.5m flue extension
110/160mm dia. 2m flue extension
110/160mm dia. 87º bend
110/160mm dia. 45º bend
110/160mm dia. 30° bend
110/160mm dia. 15° bend
Flue wall clamps 160mm dia. (pack qty. 3)
110/160mm dia. Flat roof flashing 0° 170mm
110/160mm dia. Flat roof flashing 0° – 15° 170mm
110/160mm dia. 5 – 25° pitched roof flashing
110/160mm dia. 25 – 45° flashing

Notes: The short 0.5m flue extension may be used
as an alternative to the standard extension.
The maximum flue length must be reduced by the following amounts for each bend used.

7000 WP 50, 65, 85, 100, 125, 145kW 110/160mm flue
45° bend
87° bend

0.5m 1.5m

Flues and ventilation 27

Standard vertical flue assembly

Vertical balanced flue system with two 45° bends

Components

Part No. 110/160mm 7-738-113-668

Maximum lengths (mm) & no. of components required

7000 WP 50kW

2,000mm

1

7000 WP 65kW

2,000mm

1

7000 WP 85kW

2,000mm

1

7000 WP 100kW

2,000mm

1

7000 WP 125kW

2,000mm

1

7000 WP 145kW

2,000mm

1

Vertical balanced flue system maximum height

Components

Part No. 110/160mm 7-738-113-668 7-738-113-100 7-738-113-104

Maximum lengths (mm) & no. of components required

7000 WP 50kW 20,000mm

1

up to 18

2

7000 WP 65kW

21,000mm

1

up to 19

2

7000 WP 85kW

15,000mm

1

up to 13

2

7000 WP 100kW

15,000mm

1

up to 13

2

7000 WP 125kW

5,000mm

1

up to 2

2

7000 WP 145kW

4,000mm

1

up to 2

2

Vertical balanced flue system with two 90° bends

Plume management flue kit For single boilers, sometimes finding a suitable compliant flue termination position can be difficult. Plume management kits allow termination positions to be raised up to a level where plume is less likely to cause a nuisance, allowing more options for a compliant flue termination position. The plume management kit replaces a standard horizontal terminal and allows a concentric flue system to be used internally, where the boiler is positioned some distance from the outside wall.
All external components are made from stainless steel to ensure a durable long life flue system. Stainless steel bends and additional sections allow further options depending on the site conditions.
For further information about permissible flue lengths, please refer to the flue installation manual for the 7000 WP.

Available accessories

Product Plume management kit, Ø110/160 Pipe concentric Ø110/160 0,5m stainless Pipe concentric Ø110/160 1,0m stainless Pipe concentric Ø110/160 2,0m stainless Elbow concentric Ø110/160 15° stainless Elbow concentric Ø110/160 30° stainless Elbow concentric Ø110/160 45° stainless Elbow concentric Ø110/160 87° stainless

Part number 7-738-113-670 7-738-113-140 7-738-113-141 7-738-113-142 7-738-113-143 7-738-113-144 7-738-113-145 7-738-113-146

Product Supply air intake Ø110/160 stainless Wall bracket Ø160, 40-65mm stainless Extension wall bracket Ø160, 65-165mm Extension wall bracket Ø160, 178-284mm Extension wall bracket Ø160, 294-394mm Extension console Ø160, 54-187mm Extension console Ø160, 180-271mm Extension console Ø160, 271-362mm

Part number 7-738-113-147 7-738-113-149 7-738-113-150 7-738-113-151 7-738-113-152 7-738-113-153 7-738-113-154 7-738-113-155

Components

Part No. 110/160mm 7-738-113-668 7-738-113-100

Maximum lengths (mm) & no. of components required

7000 WP 50kW

21,000mm

1

up to 19

7000 WP 65kW

22,000mm

1

up to 20

7000 WP 85kW 16,000mm

1

up to 14

7000 WP 100kW 16,000mm

1

up to 14

7000 WP 125kW

5,000mm

1

up to 3

7000 WP 145kW

5,000mm

1

up to 3

28 Flues and ventilation

Components

Part No. 110/160mm 7-738-113-668 7-738-113-100 7-738-113-105

Maximum lengths (mm) & no. of components required

7000 WP 50kW

18,000mm

1

up to 16

2

7000 WP 65kW

19,000mm

1

up to 17

2

7000 WP 85kW

13,000mm

1

up to 11

2

7000 WP 100kW

13,000m

1

up to 11

2

7000 WP 125kW

2,000mm

1

N/A

2

7000 WP 145kW

2,000mm

1

N/A

2

Please refer to the installation manual and flue guidance document for further information.

B23 open flues For situations when a suitable room sealed flue run cannot be found, open flue systems using existing chimneys or purpose made flue systems can be used. The Condens 7000 WP has a range of flue components for use with B23 open flue systems.

Flue via an existing chimney For individual boilers, DN110 flue system components are available to line existing chimneys and connect the boiler to the lining. Rigid sections, available in 500mm, 1,000mm and 2,000mm, can be used with flue spacers, terminal, and base sections to build a complete flue system. For chimneys that are not straight, DN110 flexible liners are available in 15m and 25m lengths. Installation tools are also available.

C93 room sealed flues Where a room sealed flue arrangement is desired, but it is not possible to use a standard concentric flue to achieve this, the C93 flue option using an existing chimney is possible. The chimney must be inspected and found to be sound, clean and of minimum size before this option can be considered. C93 flue systems use the chimney as a supply duct for combustion air via a special terminal and base section. The inner exhaust duct uses standard flue components similar to those described in the B23 flue for both rigid and flexible options.

Flues and ventilation 29

Cascade combined flue systems One of the advantages of a Condens 7000 WP cascade is the ability to combine individual boiler flues into a common flue header using off-the-shelf recommended flue components. There are two types of cascade flue systems, which should be considered at the design stage.

Natural draught cascade flues Cascade flue systems that rely on natural draught are durable due to their simplicity. They require a minimum vertical height and diameter based on the cascade output and can use existing chimneys, operating as an open flue system.
Where no chimney is available, flues can be run externally using standard twin wall stainless steel components. Internal flue runs must consider any fire protected areas they may pass through and local Building Regulations.
Standard cascade flue headers are available to suit all common cascade arrangements.
Over pressure cascade flues Where the use of a natural draught flue system is difficult to achieve, due to chimney size and height restrictions, an over pressure flue system can be used. This provides greater flexibility to achieve compliant flue options in demanding situations.
Over pressure flue systems use an individual nonreturn valve at each boiler flue exit to ensure there are no possibilities of flue spillage when a boiler is not operating. The Condens 7000 WP incorporates a flue safety sensor which monitors the non-return valve is fully shut. If the non-return valve does not shut completely, the flue sensor activates the boiler fan and creates an alarm to maintain safety.
The over pressure non-return valve comes as standard with our Condens 7000 WP 125kW and 145kW range.
30 Flues and ventilation

Non Return Valve 7-736-701-917 Non return valve for overpressure flue cascade kit 50-100kW (not required for 125 &145kW)
Boiler room safety
CO sensors for cascade flue systems Bosch has taken the decision to require the mandatory use of CO detection for boiler systems using cascade flue systems, such as the 7000 WP, where there is more than one appliance connected. This is to reflect state of the art in the industry and will help to raise safety standards.
The base cascade flue kits now contain a CO detector for use in the installation. For third party cascade flue system, a CO detector that is interlocked with the boilers will be required. A suitable CO detector is available as an accessory.
Part Numbers: CO Detector – 7-736-606-211 CO-Detector & Cut-off module set – 7-736-606-214

Typical use cases
The Condens 7000 WP has been developed to allow specifiers and heating engineers greater flexibility to design heating systems, providing reliable and efficient performance for any project.
The following hydraulic schematics show just some of the many options that are available for individual and cascade installations.
Single boiler application
Single boiler applications are most commonly found in large domestic or light commercial applications such as restaurants, churches and more.
Single boiler (heating + hot water)

AV P

Example shows: Single boiler is installed without a low loss header. If residual head is less than 200 mbar, on most instances you would not need an additional low loss header and system pumps. An RTH converter can be used to enable use of third party controls.

Single Boiler with plate heat exchanger (heating + hot water)

AV P

LS IV

NRV IV

Example shows: Single boiler is installed in an open vented system. The boiler can only operate in a sealed system. Where header tanks are used, you must install a plate heat exchanger (PHE). Alternatively a PHE is often used when system water is contaminated ­ helping to protect the boiler.

Single boiler application 31

Single Boiler (heating only)
P

Example shows: Single boiler is used for heating only applications. For single circuit applications that require less than 200mbr, you can achieve this without the need for an additional low loss header or system pumps.

Single boiler with diverter valve (heating + hot water)

AV
MON_GE
P

Sense II

Example shows: Single boiler is installed in a sealed system. The boiler pump group has the 3 way valve (7-736-701881) fitted to enable the hot water to be diverted to either the central heating or domestic hot water tank. This example represents a system with 1 heating circuit and 1 DHW circuit. For further information on the controls shown go to page 20.

Single boiler with LLH (heating + hot water)

Sense II
2 x MM100
AV

Example shows: Single boiler is installed with a low loss header. Hydraulic break is required when adding additional system pumps to avoid running pumps in parallel. This example represents a system with 1 heating circuit and 1 DHW circuit. For further information on the controls shown go to page 20.

NRV IV

P

IV

IV

NRV IV

32 Single boiler application

Cascade application
It is important that a cascade controller is always used when cascading our 7000 WP boilers. The following examples show how this is achieved using either the MC400 or 8313 controllers.
Cascade with LLH (heating + hot water) using MC400 cascade sequencer (BMS run signal)
Example shows: Cascade system is installed with a low loss header providing hydraulic separation from the rest of the heating system. This will ensure that flow volumes are balanced and hydraulic performance is optimised. Cascade control sequencing is achieved through the MC400 module ­ rotating the lead boiler for consistency and switching boilers on to meet varying demand. The MC400 can be used with a BMS system where the MC400 controls the sequencing strategy.
MC400
AV

NRV IV

IV

MON_GE
P

MON_GE
P

IV

NRV IV

Cascade with LLH (heating + hot water) using CC8313 controller
Example shows: Cascade system is installed with a low loss header providing hydraulic separation from the rest of the heating system. This will ensure that flow volumes are balanced and hydraulic performance is optimised. Cascade control and remote monitoring is achieved via the CC8313 control with function modules. The CC8313 enables internet connection, remote monitoring and diagnostics complying with Part L building regulations.
8313 FM-CM + FM-MM
AV

NRV IV

IV

MON_GE
P

MON_GE
P

IV

NRV IV

IV

Cascade boiler application 33

Getting started

REGISTER A PRODUCT
To register a boiler or cascade system and activate the 5 year guarantee, click the link below, or scan the QR code: bosch-industrial.co.uk/guarantee
5
YEAR Boiler Guarantee*

BOOK COMMISSIONING
In order to book commissioning for a boiler or cascade system, simply visit the below link, or scan the QR code, and complete the pre-commissioning checklist:
bosch-industrial.co.uk/commissioning

*Terms & conditions apply. Please visit bosch-industrial.co.uk/guarantee-terms-and-conditions for details
34 Registration and commissioning

Boiler configurations Single boiler
The Condens 7000 WP can be configured in various ways to meet the heating demands of your installation. Please use the numbered steps below to choose the correct boiler configuration for your project. Please contact us if you require assistance.

Dimensions 50-100kW

Width

520mm

Height

1,429mm

Depth

458mm

Dimensions 125-145kW

Width

520mm

Height

1,429mm

Depth

588mm

ErP only relevant to 50kW and 65kW models. Height with pump group

1 Boiler
Description Bosch Condens GC7000WP 50kW Bosch Condens GC7000WP 65kW Bosch Condens GC7000WP 85kW Bosch Condens GC7000WP 100kW Bosch Condens GC7000WP 125kW Bosch Condens GC7000WP 145kW

Part number 7 736 702 194 7 736 702 195 7 736 702 196 7 736 702 197 7 736 702 198 7 736 702 199

2 Pump group (1 required per boiler)

Description
Pump group 70kW (3 bar PRV) (for use with 50kW and 65kW boilers)

Part number 7 736 701 864

Pump group 100kW (3 bar PRV) (for use with 85kW and 100kW boilers)

7 736 701 865

Pump group 150kW (4 bar PRV) (for use with 125kW and 145kW boilers)

7 736 702 214

3 Wall hung or frame set option

Wall hung Pump group insulation Pump group connection set

Part number 7 736 701 876 5 584 552

Floor standing frame TL1 frame set with insulation Pump group connection set

*TL1 floor standing frame available with flow and return headers if required, please contact your local CTM.

4 Hydraulic separation options (if required)

Low loss header**

Optional accessories Sinus LLH 180kW***

Part number 8 920 097 2

**Bosch 300kW LLH available if required, please contact your local CTM. ***Output requirements over 100kW must be designed to 20K T.

Plate heat exchanger
Optional accessories 50KW Plate heat exchanger 65KW Plate heat exchanger 80-100KW Plate heat exchanger 101-140KW Plate heat exchanger 141-180KW Plate heat exchanger

Part number 7 733 600 013 7 733 600 014 7 733 600 016 7 733 600 017 7 733 600 018

Required accessories Temperature sensor pocket (R1/2″)
PHE connection type 1 ¼” Male BSPP flat face 1 ¼” Male BSPP flat face 1 ¼” Male BSPP flat face 2″ Male BSPP flat face 2″ Male BSPP flat face

Part number 7 736 701 912 5 584 552
Part number 5 446 142

5 Controls
Bosch controls
Greenstar Sense II (interface controller) MM100 (one required per zone)

Part number 7 738 111 064
7 738 110 140

BMS integration MU100 Programmer

Part number 7 738 110 145

3rd party controls

Part number

RTH Converter

7 807 9

(included as standard with

50 and 65kW variants)

Single boiler packs 35

Boiler configurations Cascade boiler sets

Our Condens 7000 WP can be cascaded on a six boiler cascade frame set to achieve up to 860kW.
An ideal choice for applications where space is restricted but there is a demand for a modern high output, high efficiency heating solution. Control strategies can provide cascade and sequencing for up to 16 boilers at a time for up to 2.2MW of power.

1 Boiler
Description Bosch Condens GC7000WP 50kW Bosch Condens GC7000WP 65kW Bosch Condens GC7000WP 85kW Bosch Condens GC7000WP 100kW Bosch Condens GC7000WP 125kW Bosch Condens GC7000WP 145kW

Part number 7 736 702 194 7 736 702 195 7 736 702 196 7 736 702 197 7 736 702 198 7 736 702 199

2 Pump group (1 required per boiler)

Description
Pump group 70kW (3 bar PRV) (for use with 50kW and 65kW boilers)

Part number 7 736 701 864

Pump group 100kW (3 bar PRV) (for use with 85kW and 100kW boilers)

7 736 701 865

Pump group 150kW (4 bar PRV) (for use with 125kW and 145kW boilers)

7 736 702 214

3 Cascade frame sets

Cascade setup Description

Part number

TL2

2 Boiler in-line cascade set with insulation

7 736 701 883

TL2

TL3

3 Boiler in-line cascade set with insulation

7 736 701 884

TL4

4 Boiler in-line cascade set with insulation

7 736 701 885

TL5

5 Boiler in-line cascade set with insulation

7 736 701 886

TL5

TL6

6 Boiler in-line cascade set with insulation

7 736 701 887

TL3

TL4

TL6

Cascade setup TR2 TR3 TR4 TR5 TR6

Description 2 Boiler back-to-back cascade set with insulation 3 Boiler back- to-back cascade set with insulation 4 Boiler back-to-back cascade set with insulation 5 Boiler back-to-back cascade set with insulation 6 Boiler back-to- back cascade set with insulation

Part number 7 736 701 888 7 736 701 889 7 736 701 890 7 736 701 891 7 736 701 892

TR2 TR5

TR3

TR4

TR6

4 Victaulic connections
Only required when NOT using a Bosch specified low loss header. If using a low loss header skip to 6.

Cascade setup TL1 TL2/TR2 TL3/TR3 TL4/TR4 TL5/TR5 TL6/TR6

Description Victaulic 2.5″ to flange connection DN65 PN6 (Pack Qty. 2)
Victaulic 4″ to flange connection DN100 PN6 (Pack Qty. 2)

Part number 7 736 701 914
7 736 701 913

36 Cascade boiler sets

Boiler configurations Cascade with plate heat exchanger or low loss header

A plate heat exchanger can be used to separate the boiler from the system in both open vented and sealed systems. This provides greater protection for the boiler, especially where the water quality in the existing system is poor.

A low loss header is a device that hydraulically separates the boiler from the heating circuit. This helps to improve the efficiency and performance of the heating system by regulating the pressure and flow rate of the system.

5 Plate heat exchangers
Description 50KW Plate heat exchanger 65KW Plate heat exchanger 80-100KW Plate heat exchanger 101-140KW Plate heat exchanger 141-180KW Plate heat exchanger 181-230KW Plate heat exchanger 231-280KW Plate heat exchanger 281-400KW Plate heat exchanger 401-520KW Plate heat exchanger 521-640KW Plate heat exchanger 641-860kW Plate heat exchanger

Part number 7 733 600 013 7 733 600 014 7 733 600 016 7 733 600 017 7 733 600 018 7 733 600 020 7 733 600 021 7 733 600 023 7 733 600 025 7 733 600 026 7 733 600 027

PHE connection type 1 ¼” Male BSPP flat face 1 ¼” Male BSPP flat face 1 ¼” Male BSPP flat face 2″ Male BSPP flat face 2″ Male BSPP flat face 2″ Male BSPP flat face 2 ½” Male BSPP flat face 2 ½” Male BSPP flat face 2 ½” Male BSPP flat face 2 ½” Male BSPP flat face DN100 compact flange

6 Low loss header

Cascade Setup Description

TL1 TL2/TR2

Low loss header + Insulation 300kW

TL3/TR3

TL4/TR4 TL5/TR5

Low loss header + Insulation 900kW

TL6/TR6

Part number

Optional flanges

7 736 701 907 Threaded flange DN65 PN6

7 736 701 908 Threaded flange DN100 PN6

Part number 7 736 700 487
7 736 700 964

7 Controls

Bosch intelligent controls
8313 Control
Temperature sensor set EMS plus 200mm
FM-CM Module (cascade sequencer)
FM-MM Module (2 heating circuits)
FM-MW Module (1 heating, 1 hot water circuit)

Part number 7 736 602 245 7 735 600 656 7 736 602 098 8 718 598 828 8 718 598 831

Bosch sequencing controls Part number

MC400 Cascade sequencer

7 738 111 001

Temperature sensor set TF 7 735 600 657 HW EMS2 200mm (MC400 required accessory)

MM100 Zone control module

7 738 110 140

Greenstar Sense II (interface controller, MM100 required accessory)

7 738 111 064

BMS integration
MU100 Programmer (BMS interface module)

Part number 7 738 110 145

Cascade with plate heat exchanger or low loss header 37

Condens 7000 WP accessories
Pressure relief valve 4 bar
7-095-595 4 bar pressure relief valve for installation in the Condens 7000 WP pump group.
Pressure relief valve 6 bar
7-736-700-914 6 bar pressure relief valve for installation in the Condens 7000 WP pump group.
Non-return valve ­ return pipe
7-736-700-432 (Included in hydraulic frame kit) DN32 non-return valve. For Condens 7000 WP installations not using the Bosch hydraulic cascade kit.
Connection set (hydraulic TL)
7-736-702-047 (Included in hydraulic frame kit) Connection set for hydraulic cascade Condens 7000 WP boilers in a line (TL set up).
Connection set (hydraulic TR)
7-736-702-048 (Included in hydraulic frame kit) Connection set for hydraulic cascade Condens 7000 WP boilers in a back-to-back configuration (TR set up).
Connection set (gas TL)
7-736-701-870 (Included in hydraulic frame kit) Gas connection set from pump group to gas manifold. Front boiler assembly for Condens 7000 WP boilers in a line (TL set up).
Connection set (gas TR)
7-736-701-872 (Included in hydraulic frame kit) Gas connection set from pump group to gas manifold. Front boiler assembly for Condens 7000 WP boilers in a back-to-back set up (TR set up).
RTH converter
7-807-9 RTH converter to enable the use of third party 230Vac controls. Included as standard with the 50 and 65kW models.
38 Accessories

TL1 boiler frame set w. insul wo Gas
7-736-701-882 Single hydraulic frame kit (TL1 set up) with insulation for use with the Condens 7000 WP boiler. Includes frame kit, insulation, hydraulic headers and connection set (without gas header).
TL1 basic boiler frame set
7-736-701-912 Single frame kit (TL1 set up) with insulation for use with the Condens 7000 WP boiler. Includes frame kit and insulation only.
Flange connection 2.5″ incl. victaulic
7-736-701-914 Hydraulic connections from victaulic 2.5 inch to flange DN65, PN6 for the Condens 7000 WP hydraulic cascade kits. Please specify this when using the cascade kit without low loss header or when using plate heat exchangers (pack of 2).
Flange connection 4″ incl. victaulic
7-736-701-913 Hydraulic connections from victaulic 4 inch to flange DN100, PN6 for the Condens 7000 WP hydraulic cascade kits. Please specify this when using the cascade kit without low loss header or when using plate heat exchangers (pack of 2).
Gas cock
7-736-701-868 (Included in pump group) Gas isolating valve for Condens 7000 WP pump group.
Victaulic coupling 2.5″
7-736-701-915 Victaulic coupling 2.5 inch (pack of 1).
Victaulic coupling 4″
7-736-701-916 Victaulic coupling 4 inch (pack of 1).
AS/HKV 32 connection set
5-584-552 Connection set for when using a pump group without hydraulic cascade kit (1 1/4 inch).
Accessories 39

Training
Install with confidence
Learn all you need to know about the Condens 7000 WP commercial boiler range. We specifically tailor all our product courses to meet your needs. This hands- on course is perfect for those who want to specify and install the Condens 7000 WP boilers for commercial and domestic applications.
Supporting you
Our courses are here to support your installation from beginning to end. The Condens 7000 WP course covers: Specification and installation Service and maintenance Fault finding and diagnostics Our product training courses will help you get hands-on experience and understand all the features and benefits.
Scan to start your training: worcester-bosch.co.uk/eacademy

Get in touch
Sales Tel: 03330 608 456 Email: commercial.industrial@uk.bosch.com
Technical Helpline Tel: 0330 123 0165 Email: technical-advice@uk.bosch.com
Controls Helpline Tel: 0330 123 3641
Training Tel: 0330 123 0166 Email: training@uk.bosch.com

Share
We would love to see your installations! Bosch Commercial Industrial Bosch Industrial UK

Bosch Commercial and Industrial Cotswold Way, Warndon, Worcester. WR4 9SW bosch-industrial.co.uk
Calls to and from Bosch Thermotechnology Ltd may be recorded for training and quality assurance purposes. This brochure is accurate at the date of printing, but may be superseded and should be disregarded if specification and/or appearances are changed in the interest of continued improvement. The statutory rights of the consumer are not affected.
8-716-111-872-0 G 12/23