ModCom II Automatic Temperature Control Specifications Manual
- June 8, 2024
- ModCom
Table of Contents
ModCom II
Automatic Temperature Control Specifications
Section 15950 Controls and Automation
PART 1: General
1.1 The system shall consist of a multiple zone capacity programmable
controller and communicating thermostats. Each controller shall communicate
with up to 20 devices total. Each controller shall also include a complete set
of air temperature sensors. The system control devices shall be capable of a
stand-alone applications, or as a multiple zone system networked in a
communication bus. The system components shall provide the capability to be
accessed locally and remotely through use of a Windows® based computer.
1.2 The installation of the ATC shall be in accordance with all National,
State and Local codes pertaining to this type of work.
1.3 All work must comply with Section 15050 – Basic material and Methods – and
all other Division 15 Sections, as applicable.
1.4 The scope shall include furnishing and installing a temperature control
system to include remote control panels, temperature control devices,
appurtenances, etc. to accomplish specific control sequences specified herein,
to provide overheating and freeze protection for HVAC units, sensing an
indicating devices, temperature indicating instruments, supporting structures
and other required components.
1.5 The scope shall include all thermostats, sensors, dampers, actuators,
microprocessor, central controllers, VAV diffusers, static pressure sensors,
fan powered boxes, re-heat products and all other new components of the system
requiring connections.
PART 2: General Instructions
2.1 The Building Automation System/Automatic Temperature Control (BAS/ATC)
Systems as specified herein shall be provided in their entirety by the BAS/ATC
Contractor. The BAS/ATC Contractor shall base his Bid on the system as
specified and on the sequence of operations.
2.2 As part of his Bid, the BAS/ATC Contractor shall submit for review by the
owner’s authorized representatives a written description of his BAS/ATC
systems, including block diagrams, showing all major components and control
panels and required cabling between each.
2.3 The BAS/ATC contractor shall include manufacturer’s literature for each
type of panel, controller, or device that may be shown on the Riser Diagram.
2.4 The Riser Diagram shall show schematically the entire building system with
all major components identified.
PART 3: Scope of Work
3.1 The BAS/ATC systems shall be supplied and installed completely under the
BAS/ATC Contract. Control components shall be mounted and wired by the BAS/ATC
Contractor.
3.2 The BAS/ATC Contractor shall provide the engineering, installation,
calibration, software programming and checkout necessary for complete and
fully operational BAS/ATC systems, as specified hereafter.
3.3 Wiring in exposed areas and in mechanical rooms shall be in EMT. Wiring in
accessible, concealed areas shall be plenum rated cable.
PART 4: Submittals
4.1 The following data/information shall be submitted for approval:
4.2 Complete sequence of operation.
4.3 Control system drawings, including all pertinent data, to provide a
functional operating system.
4.4 Damper schedules showing size, configuration, capacity and location of all
equipment.
4.5 Data sheets for all hardware control components.
4.6 A description of the installation materials including conduit, wire, flex,
etc.
4.7 Thermostat/Sensor locations
4.8 Control panel locations.
4.9 Provide as part of the submittal five copies of all data and control
drawings.
PART 5: Qualifications
5.1 The BAS/ATC Contractor shall have an office within a 100-mile radius of
the job site, staffed with factory-trained personnel capable of providing
instruction, routine maintenance, and 24-hour emergency maintenance for all
system components.
5.2 The BAS/ATC Contractor shall have a minimum of three years experience
installing and servicing similar microprocessor-based control systems.
5.3 The Contractor shall be prepared to provide evidence of this history as a
condition of acceptance and approval prior to bidding.
PART 6: System Description
6.1 The system shall be DDC based to centralize communications with a zoned
HVAC system, Standalone HVAC units and other HVAC mechanical devices. The
MODCOM II controller with onboard capacity control shall be capable of
controlling the zoned unit while Stand-alone equipment shall be controlled via
two-stage communicating thermostats. MODCOM II controller shall communicate
with up to 20 devices. Each controller shall also include a complete set of
air temperature sensors, displaying Outside Air Temperature along with SA/RA
from each unit in the system. The system control devices shall be capable of a
stand- alone application or as a multiple zone system networked by a
communications bus. The system components shall provide the capability to be
accessed locally and remotely through use of a Windows based computer either
on site of via a TCIP device over the Internet.
PART 7: Control Manufacturer
7.1 The control system will be the MODCOM II thermal management system as
manufactured by Zonex Systems, Huntington Beach, CA. Any substitution of the
above-specified control system will require a 10-day prior approval by the
engineer.
7.2 For pricing, contact the factory at
800-228-2966 or visit
www.zonexcontrols.com
7.3 For substitution, submit a complete description, engineering data, and
names of existing installations of substitute products.
7.4 For substitution, submit a complete description, engineering data, and
names of existing installations of substitute products.
7.5 Be prepared to provide field inspection by the engineer if he chooses to
observe the actual installation of proposed substitution.
PART 8: Product – General
8.1 The control system shall be available as a complete package, with the
required software, input sensors, communicating thermostats. It shall provide
complete control of communicating thermostats in stand-alone, zoning or VAV
applications through a single communications bus. The control system shall
support not less than 20 individual thermostats or devices. Stand-alone
thermostats shall provide not less than two heat and two cool stages with
independent fan control.
PART 9: MODCOM II Controller
9.1 The MODCOM II controller shall communicate with up to 20 devices total, to
include communicating stand-alone thermostats, communicating modulating zone
thermostats and communicating rely modules.
9.2 Controller shall manage 1 zoned HVAC unit with up to 20 modulating zones.
9.3 Controller shall communicate through a two-conductor twisted pair RS-485
data link and shall be daisy chained between all system communicating
components.
9.4 The controller shall be capable of establishing, adjusting and storing
both an occupied and unoccupied schedule in a seven day format. Scheduling
increments shall be in one-minute intervals, with four program periods
available per day.
9.5 The controller shall schedule individual or global thermostat set points
for each mode.
9.6 The controller shall provide individual thermostat name assignments up to
20 characters each.
9.7 The controller shall display up to twenty thermostats or devices
concurrently. Each thermostat or device listing shall display a numerical and
descriptive identification, occupied and unoccupied heating and cooling set
points with additional diagnostic information. Diagnostic information shall
include set point lock status, mode of operation, space temperature, date and
time of day.
9.8 The controller shall provide the ability to monitor and display at the
operating computer: outside air, return air and mixed air temperatures for
each HVAC unit or zoned system. Calibration of the system sensors shall be
adjustable from the controller without requiring sensor to be taken out of
service.
9.9 The controller and system software shall provide print capability of all
occupied and unoccupied heating and cooling set points, thermostat schedules
and diagnostic information.
9.10 The controller shall provide individual or global temporary mode
overrides (Occupied or Unoccupied) of the thermostat schedule. Upon the next
event, the thermostat will revert to its programmed schedule.
9.11 The controller shall provide up to 20 holiday schedules with up to 31
days per schedule. Additionally, an override feature shall be available to
temporarily revise one or more schedules.
9.12 The controller shall provide a remote or on-site Trend Logging function
with data storage to review a minimum 30 days of temperature and RA/SA
temperatures from every unit and thermostats in the system.
9.13 Controller operation shall be based on a poll of each thermostat or
communicating device in the control system every 60 seconds, providing
operating conditions and updates to the Controller.
9.14 The system components shall operate without use of an external time
clock. In the event of power loss, all program schedules shall be retained
indefinitely in non-volatile memory. The calendar date and time shall remain
uninterrupted during power loss. The system shall restart and resume normal
operation upon power restoration.
PART 10: Capacity Control
10.1 The MODCOM II controller shall contain a capacity control that receives
the heating and cooling signal and regulates the equipment (on and off) to
meet the building requirements.
10.2 The MODCOM II controller shall be equipped with a Leaving Air Temperature
Sensor constantly monitoring discharge temperature at the MODCOM II
controller.
10.3 The capacity control shall have the capability to shut down the stages
based on a rise or fall in leaving air temperature above or below a fully
adjustable range of temperature. The system shall provide protection from
short cycling and protect the unit from coil freeze up or overheating the heat
exchanger.
10.4 Staging operations shall be incorporated into the MODCOM II capacity
control function based on time and leaving air temperature strategy.
PART 11: Zone Temperature Sensors
11.1 ModCom II shall utilize Modulating Thermostats (ModStat), Stand-Alone 2H
/ 2C thermostats (DIGICOM), and Heat Pump thermostats (DIGIHP) to address
demands of individual systems, modulating zone dampers or VAV terminal units.
11.2 The typical Zone Temperature Sensor (Model ModStat) will contain all of
the electronics to:
11.3 Control fully modulating zone dampers and to provide for proper
temperature requirement.
11.4 Include push buttons on the face of control to set independent heating
and cooling set points and to maintain a minimum two-degree dead band.
11.5 The push buttons allow the operator to change or review the ModStat set
points.
11.6 The ModStat, if remotely locked from the System controller, shall provide
local control of +/- 2 degrees from the locked heating or cooling set point.
The adjustable temperature range is from 55 to 95 degrees F. Celsius display
shall also be available.
11.7 The ModStat shall contain one microprocessor that receives the current
temperature from the space, which communicates this information to the central
control microprocessor via a 2-wire unshielded data link.
11.8 The ModStat shall have a large digital display showing current space
temperature, the current mode of operation and the heating and cooling set
points established for that zone.
11.9 The ModStat shall also be equipped with an off switch; when initiated,
its zone damper will go fully closed.
11.10 Each ModStat can control up to three slaved dampers. The ModStat shall
be available with Remote sensor capability.
11.11 When utilizing perimeter electric or hot water baseboard heating for
supplemental heating, the thermostat operates a zone damper only for airflow
and energizes the supplemental heat when the temperature drops two degrees
below set point. At one degree below set point, it signals the system of a
heating call.
PART 12: DIGICOM and DIGIHP Thermostat
12.1 Each thermostat shall support stand-alone unit.
12.2 Each thermostat shall be capable of controlling two heat and two cool
stages with independent fan operation.
12.3 Each thermostat shall provide a cooling minimum run time of 120 seconds
upon stage initiation.
12.4 Each thermostat shall provide time and temperature conditions to inhibit
second stage operation.
12.5 Each thermostat shall provide a 2-minute minimum off delay to prevent
cooling equipment short cycling.
12.6 Each thermostat shall provide a continuous fan function during the
occupied mode of operation.
12.7 Each thermostat shall have the ability to automatically change over
between heat and cool modes.
12.8 Each thermostat shall receive command to lock set points and all
thermostat functions through the operating software without use of manual
jumpers or dip switches.
12.9 Each thermostat shall provide a continuous illuminated temperature
display.
PART 13: SENDCOM SENSOR – Remote Communicating Duct Temperature Sensor
13.1 The duct sensor shall be capable of broadcasting two duct air
temperatures for each stand-alone thermostat application.
13.2 The duct sensor shall be capable of broadcasting two duct air
temperatures for each additional SENDCOM installation.
13.3 The duct sensor shall provide a selectable address to coincide with its
respective stand-alone thermostat address.
13.4 The duct sensor shall integrate with the system without any software
editing.
13.5 The SENDCOM remote duct temperature sensor shall connect into the
communications bus at any point within the link.
PART 14: RLYCOM Communicating Relay Module
14.1 Each relay module shall provide generic device scheduling using on/off
logic, up to four events per day.
14.2 All event schedules shall be available to be entered in one-minute
increments.
14.3 Each relay module shall provide 2- SPDT dry relay contacts for pilot duty
switching applications.
14.4 Each relay module shall be capable of broadcasting operating modes
(Occupied and Unoccupied) locally and at the operating computer.
14.5 Each relay module shall provide a local mode override function to
alternate between operating modes without use of a computer.
14.6 Each relay module shall provide a unique address to identify the device
when queried by the controller.
PART 15: Bypass Dampers and Controls
15.1 The modulating bypass damper(s) are to be installed as shown on
accompanying drawings. When utilizing a ceiling return, there must be a short
return plenum with the bypass directly connected to the supply and return
plenum.
15.2 When the HVAC unit utilizes an economizer section, the return air inlet
to the return air plenum must contain counter balanced dampers to prevent air
pressurization of the return air system.
15.3 Each round bypass damper (Model STMPD) shall consist of 20-22 gauge
galvanized metal duct fitted with an elliptical damper to provide linear
airflow. The damper shall contain a foam seal to prevent leakage when fully
closed. Each damper will contain a full stall 24-volt modulating actuator,
which shall not draw more than 2 VA on one drive assembly. The damper shell
will be crimped on one end and beaded on both ends for damper rigidity.
15.4 Each rectangular bypass damper (Model STCD) shall be constructed of a
20-gauge “snap-lock” steel frame with S & Drive connections. The total length
of the damper will be 16”. Dampers 10” and smaller in height will utilize
single blade construction; dampers larger than 10” in height will utilize
opposed blade construction. The damper blades are of formed steel design with
gasketed stops to provide quiet operation and structural integrity.
15.5 The bypass damper shall be controlled by a static pressure sensing air
switch with a dead band.This device shall be located downstream of the bypass
connection from the supply plenum and upstream from the first zone damper.
This device continually senses the discharge air static pressure and signals
the bypass damper to modulate open or close.
15.6 Up to three bypass dampers can be slaved together with one static
pressure sensor and transformer.
15.7 The transformer powering the bypass damper shall only be energized when
the HVAC indoor blower is operating
PART 16: Zone Dampers
16.1 Each round zone damper shall consist of 20-22 gauge galvanized metal duct
fitted with an elliptical damper to provide linear airflow. The damper shall
contain a foam seal to prevent leakage when fully closed. Each damper will
contain a full stall 24-volt modulating actuator, which shall not draw more
than 2 VA on one drive assembly. The damper shell will be crimped on one end
and beaded on both ends for damper rigidity. Dampers shall be equipped with
min/max position stops and indicators.
16.2 Each rectangular zone damper shall be constructed of a 20-gauge “snap-
lock” steel frame with S & Drive connections. The total length of the damper
will be 16”. Dampers 10” and smaller in height will utilize single blade
construction; those dampers larger than 10” in height will utilize opposed
blade construction. The damper blades are of formed steel design with gasketed
stops to provide quiet operation and structural integrity. Dampers shall be
equipped with min/max position stops and indicators.
16.3 Zone dampers shall be fully modulating in operation based on input
received from each zone thermostat. Modulation shall be predicated on variance
from set point. If the system has satisfied all calls, all dampers shall
modulate to the 50% position for ventilation.
16.4 All zone dampers shall be connected to its zone thermostat by 3-wire,
18-gauge copper wiring. The zone thermostat shall continuously monitor room
temperature and modulate damper position based on variance from its set point
to provide effective temperature control as required.
PART 17: Transformers and Wiring
17.1 An independent 24-volt transformer sized at 2 VA per zone damper or
D-Fuser shall power the ModCom II Controller and be sized appropriately to
support all zone dampers in the system.
17.2 Bypass dampers shall be served by independent 40 VA/ 24-volt
transformers.
17.3 All power wiring of this system shall be 24-volt AC.
17.4 All communications wire shall be two-wire unshielded or shielded twisted
pair.
PART 18: Software
18.1 Access to the system, whether local or remote, shall be accomplished
using the Zonex Systems ModCom II Software.
18.2 The software shall be capable of, but not limited to: listing all
thermostat numerical and descriptive identification, occupied and unoccupied
operational modes, heating and cooling set points and current room
temperatures to include diagnostic information. Diagnostic information for
each communicating thermostat shall include set point lock status, thermostat
mode and space temperature indication. Diagnostic information for each system
shall include supply air, return air and mixed air temperatures, date and time
of day reference.
18.3 The software shall be capable of providing monitoring and modifying
system configurations for all components.
18.4 System software shall be nonproprietary, unlicensed and fully copyable to
enhance user access and interaction with the system.
PART 19: Service and Warranty
19.1 Upon completion of installation, the system shall be started up and
initial programming completed. The equipment being operated by the specified
control system shall be in operation and fully checked. The entire system must
be in operation for a period of 24 hours prior to seeking acceptance from the
owner/engineer.
19.2 The control system herein specified shall be free from defects in
workmanship and material under normal use and service. If, within 24 months
from date of acceptance by owner/engineer, any of the control equipment herein
described is proved to be defective in workmanship or material, the control
equipment manufacturer shall provide a replacement component.
19.3 Assist with the installation and setup of owner provided computers, phone
connections and startup, including loading of software and operator use of
system.
19.4 Program all applicable fields for thermostat scheduling as required to
suit building owner’s requirements.
19.5 Coordinate with owner the addressing and naming of all thermostats and
devices in the system.
End of Section 15950
Rev 9/20/10
ModCom II Automatic Temperature Control Specifications Manual – Download
[optimized]
ModCom II Automatic Temperature Control Specifications Manual –
Download
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>