EMERSON EVD Series Variable Speed Drives User Manual

June 7, 2024
Emerson

emerson

EMERSON EVD Series Variable Speed Drives User Manual

EMERSON EVD Series Variable Speed Drives

Safety

Safety instructions
EVD series variable speed drives are manufactured according to the latest China Safety Standard. Particular emphasis has been placed on the user’s safety. Safety icons are explained below and safety instructions applicable to the products in this bulletin are grouped on page 3. These instructions should be retained throughout the lifetime of the drive. You are strongly advised to follow these safety instructions.

Safety icon explanation

FIG 1 Safety icon explanation

Instructions pertaining to risk of electrical shock, fire, or injury to persons

  Electrical shock hazard

  • Disconnect and lock out power before servicing
  • Discharge all capacitors before servicing
  • Use compressor with grounded system only
  • Molded electrical plug must be used when required
  • Refer to original equipment wiring diagrams

  Burn hazard

  • Failure to follow these warnings could result in serious personal injury or property damage
  • Ensure that materials and wiring do not touch high temperature areas of the compressor
  • Use caution when brazing system components
  • Personal safety equipment must be used

Use of Residual Current Device (RCD) and Ground Fault Interrupt GFE). There are three common types of GFI/RCD:

  1. AC – detects AC fault currents

  2. A – detects AC and pulsating DC fault currents
    (provided the DC current reaches zero at least once every half cycle)

  3. B – detects AC, pulsating DC and smooth DC fault currents
    • Type AC should never be used with drives
    • Type A can only be used with single phase drives
    • Type B must be used with three phase drives
    • The GFI and RCD must be a high-speed type breaker of 30 mA (<0.1 seconds)

Only type B GFI / RCD are suitable for use with 3 phase inverter drives
It is important to check requirements with applicable legislation prior to installing a GFI or RCD

  Drive handling

  • Caution must be used when lifting and installing the drive. Failure to use caution may result in bodily injury
  • Personal safety equipment must be used
  • Failure to follow these warnings could result in personal injury or property damage

Safety Statements

  • Only qualified and authorized HVAC or refrigeration personnel are permitted to install, commission and maintain this equipment.
  • Electrical connections must be made by qualified electrical personnel.
  • All valid standards and codes for installing, servicing, and maintaining electrical and refrigeration equipment must be observed.

Introduction

Product description
The inverter drive has been developed specifically for the variable speed compressors. The drive will power the compressor, control the running speed, provide compressor and drive protection and communicate with the master controller. The drive requires cooling and is typically installed in a system near the compressor.

Theory of Drive Operation
The primary purpose of the drive is to convert the 50/60 Hz AC input voltage into a variable frequency, variable voltage output to power the variable speed scroll compressor. The drive conditions the AC input Voltage through a series of conditioning processes to arrive at the desired output. The drive first converts the AC input voltage into a DC bus. The DC voltage is then pulse- width modulated to replicate a sinusoidal current at the desired frequency and voltage.

Nomenclature
The model number of the drive includes the power rating and nominal voltage input to the drive. See Addendum for all of the alpha and numeric characters in the drive model number.

Installation

Drive Handling

Caution must be used when lifting and installing the drive. Failure to use caution may result in bodily injury.

  • Correct handling and storage of the drive is essential in preventing mechanical damage.
  • The box and the protection bag inside need to be carefully opened. Do not use any sharp objects to open the protection bag, which may damage the drive.
  • Never cut across the drive with any sharp materials.
  • Do not hold on to the components on the drive or drive accessories, this may damage them.
  • Once opened do not stack the drives on top of each other.
  • When handling the drive, the only correct way is hold it by the edges of the heatsink.
  • Do not drop any mechanical tools on the drive or drive accessories.
  • It is always recommended to use ESD wrist straps while touching any part of the drive.

NOTICE

Personnel handling the drives in a manufacturing plant environment should guard against static electricity by using the appropriate equipment – antistatic wrist straps and mats.

Mounting
The drive should be located within 5 feet of the compressor since the wiring between the drive and compressor is unshielded.

Air-cooled drives are supported inside the HVAC system by an extended heatsink plate. The plate mounts through an opening in the cabinet sheet metal to expose the heat exchanger to the condenser fan air stream. The flange contains a gasketed surface to prevent water from entering the electronics side of the control box.

The flat plate option accommodates installation to systems using the mating gas or liquid cooled cold plate heat exchanger. The mating cold plate is designed by OEM to accommodate the system design. There are holes in the drive mounting flange for mounting purposes. These holes will accommodate a M5 sized screw for mounting.

The drive has plastic tray with PCBA and heatsink. It is preferred that the mounting hole is same to plastic tray and it is preferred that heatsink is isolated with system ground.

Drive Accessories and Dimensions
For dimensions and accessories, please contact Application Engineering for detailed dimensions with tolerance and drawings.

Wiring Diagram
There are three types wiring diagram for different drive. One is for 1PH EVD drive, refer to Figure 2. Another one is for 3PH EVD drive except 36KW drive, refer to Figure 3. The last one is for EVD1-36KW drive, refer to Figure 4.

Operation and function

Hi-pot procedure / set-up
Refer to the Addendum for hi-pot procedure and setup. Please call your Application Engineer for additional details.

Temperature and humidity

FIG 2 Temperature and humidity

Pre-operation checks
Check the drive carefully before use it. Make sure that all the wires are correctly and tightly connected. Improper operation may cause fire or injury to persons.

Check the drive carefully before use. Make sure that all the wires are correctly and tightly connected. Improper operation may cause fire or injury to persons.

Power On/Off

NOTICE

The drive should use rated AC power supply: 3PH, 50/60Hz, 340-440V on EVD1xxxB-Dx-xxx models and 1PH, 50/60Hz, 160-265V on EVD2080B-Cx-xxx drive models.

Use of incorrect power supply may damage the drive. User should make sure that the correct combination of power supply, drive and accessories are used.

When powering off the drive, make sure to wait at least 2 minutes to ensure that the drive is completely turned off.

Communication setting
The communication hardware is RS485. And the communication protocol is Modbus RTU. Please refer to the Addendum 1 and 2 for definition and format. For read function, the drive can support 20 addresses for one time.

FIG 3 Communication setting

Input voltage and input current
The drives are designed for rated AC power supply: 50/60Hz, 340-440V on EVDxxxxB-Dx-xxx models, 190~254V on EVD1xxxB-Jx-xxx and 160-265V on EVD2080B- Cx-xxx drive models.

Published performance for the drive and compressor combination will have a performance tolerance specified on the compressor performance data sheet when the Drive input voltage is in the specified range as above.

FIG 4 Input voltage and input current

Power Factor Correction
The drive has active power factor correction for single phase and passive power factor correction for three phase. The drive is capable of correcting the AC input current to maximize system efficiency.

Speed Control
The frequency range of EVD is from 15Hz to 120Hz. If the frequency set by system controller is less than 15Hz but not zero, then the compressor will work at 15Hz. Similarly, if the frequency set by system controller is greater than 120Hz, then the compressor will work at 120Hz.

Start-up
Refer to the Addendum for start-up procedures and requirements.

Shutdown
Refer to the Addendum for shutdown procedures and requirements.

Fault Clearing
In the Modbus relationship, the drive is considered a slave, and the system controller is the master. Faults will not clear unless they are commanded to.

To clear faults, use the following method:

  1. The compressor has been shut down for at least 35 seconds.
  2. The fault condition no longer exists (registers 78-79)
  3. The drive has received a zero speed command (register 101 = 0).
  4. The drive has been disabled (register 100 = 0).
  5. Write ‘1’ to register 103.

Faults will not clear unless all items above are true.

Drive Configuration
Another feature available on the drive is the option to change Slave address, configure the drive to use different types of compressors. Modbus registers 104 – 106 serve this function (refer to Modbus Map within the Addendum for details).

Register 104 defines the slave address for communication, the default value is 45 and it can always be connected with master controller, if you change the default value to different value A, it means both A and 45 can be used for slave address to connect.

Register 105 is for different compressor model. When the value is changed in register 105, you should power off for two mins and the new parameter will be available when the power on again.

Register 106 is for shut down rate for compressor.

Drive Cooling
Because of the power electronics used in the drive and the associated heat generation, drive cooling is required to keep the drive components in their design temperature range. The allowable temperature range of the drive (The ambient air surrounding the drive) is -25°C to 65°C. Drive temperature should be monitored during system development at system extreme conditions to ensure that the maximum allowable drive temperature isn’t exceeded. The highest drive temperature will typically occur during high load conditions and/or during high drive ambient.

Drive Over Temperature Protection
The drive is self-protected against high internal temperature. There are different modes of protection; temperature high and foldback. When temperature is too high, the compressor speed will decrease until the internal temperature recover or the compressor speed is in minimum speed.

Air Cooled Heat Exchanger
Drives cooled by the aluminum air cooled heat exchanger are designed to be in the air flow stream of the condenser. The air-cooled heat exchanger must be installed so that the heat exchanger fins are parallel to the cooling air flow. The airflow must be a minimum of 3 meters/sec measured at the outlet of heatsink in the direction of airflow.

Foldback
To protect the drive components or the compressor, the compressor speed will ‘foldback’ or slow down to help reduce risk to components. The foldback event(s) will be flagged in the drive’s Modbus registers. This will allow the operating system to respond and mitigate the conditions causing foldback.

For further information refer to the Addendum.

EMC Guidelines:

  • Mount the EMI filter as close as possible to the drive.

  • Install the star earth (ground) connection as close as possible to the drive. A non-coating screw is recommended for installation on service panel to maintain good ground connection. The star connection includes:
    – System Input ground
    – Drive Heat-sink ground
    – EMI filter ground

  • The usage of additional ferrites and numbers of turns in the input power supply cables, compressor cables, sensor cables are optional but preferred based on system application and noise level.

  • Any of the input power supply cables, sensor cables, compressor cables and communication cables should not cross or touch each other to avoid noise coupling. Usage of shielded cable is optional depending on system application, but if used it’s mandatory to have correct connections on both sides of the cable.

Troubleshooting

The drive has a EMC filter board, capacitor board, choke and drive board, should issues occur follow the steps below.

When EMC filter board fails, the drive board will lose power, you can use multimeters to test the input and output voltage, and voltage discrepancies.

When choke fails, you can use multimeters to test for disconnection.

When capacitor board fails, you can read the drive DC voltage, or you can use multimeters to test the voltage between P and N. The voltage should be less than 1.3*input voltage.

The drive may indicate fault or protection for various reasons. When this occurs, users should power down the drive, inspect the drive, and check the drive’s running condition carefully. For the definitions of these faults, please refer to the Troubleshooting – Fault and Protection within the Addendum.

Fault and protection table

FIG 5 Fault and protection table

FIG 6 Fault and protection table

Figure

FIG 7 Figure

Figure 1: Electronics Nomenclature

Drive product list

FIG 8 Drive product list

FIG 9 Drive product list

Drive accessories product number list

FIG 10 Drive accessories product number list

Note: *514-0401-00 are capacitors and not a capacitor board. Each drive needs 2 capacitors.

Wire diagram for EVD2080B-Cx-xxx \(1PH\)

Figure 2: Wire diagram for EVD2080B-Cx-xxx (1PH)

FIG 12 Wire diagram for EVDxxxxB-Dx-xxx \(3PH\)

Figure 3: Wire diagram for EVDxxxxB-Dx-xxx (3PH)

FIG 13 Wire Diagram For EVD1360B-D1-xxx \(3PH\)

Figure 4: Wire Diagram For EVD1360B-D1-xxx (3PH)

FIG 14 S. N Nomenclature

Figure 5: S/N Nomenclature

Table

Table 1 – Ramp up procedure

Ramp up procedure

FIG 16 Ramp up procedure

Table 1 – Ramp up procedure

FIG 17 Ramp up procedure

Table 1 – Special shutdown logic

FIG 18 Special shutdown logic

Note: Contact our applications engineer for detailed documents.

Addendum

Addendum 1Modbus RTU definition
Half duplex asynchronous serial communication mode is used in this communication protocol. The drive works as the slave. When the slave receives the command from the host, it will answer after 100ms.

FIG 19 Modbus RTU definition

Communication diagram

Addendum 2 – Communication format
Half duplex asynchronous serial communication mode is used in this communication protocol. The drive works as the slave. When the slave receives the command from the host, it will answer after 100ms.

Transmission type

FIG 20 Transmission type

Data format
Each character or byte is sent in this order (left to right):

FIG 21 Data format

Message frame
The RTU message frame is defined by below:

FIG 22 Message frame

Note: * the maximum size of a modbus RTU frame is 256 bytes.

Modbus Message RTU Frame
A Modbus message is placed by the transmitting device into a frame that has a known beginning and ending points. This allows devices that receive a new frame to begin at the start of the message, and to know when the message is completed. Partial messages must be detected and errors must be set as a result.

In RTU mode, message frames are separated by a silent interval of at least 3.5 character times. In the following sections, this time interval is called t3.5.

FIG 23 Modbus Message RTU Frame

The entire message frame must be transmitted as a continuous stream of characters.

FIG 24 Modbus Message

If a silent interval of more than 1.5-character times occurs between two characters, the message frame is declared incomplete and should be discarded by the receiver.

FIG 25 Modbus Message RTU Frame

Data in Modbus Frame

  1. ADDRESS: Address of slave 1–247
  2. FUNCTION: Read or write function
  3. DATA: Data that correspond to read or write function
  4. ERROR CHECK: Data for checking the communication error

Function in Modbus Frame
Read Holding Registers (Code = 03): Read data of 16 bit register from slave. This function can read maximum 255 registers in the continuous address at one time. In the EMERSON driver, the maximum 24 register can be read:

FIG 26 Function in Modbus Frame

Preset Single Register (Code = 06): Write single data to 16 bit register of slave.

FIG 27 Preset Single Register

General information

Technical data are correct at the time of printing. Updates may occur, and should you need confirmation of a specific value, please contact Emerson clearly stating the information required.

Emerson cannot be held responsible for errors in capacities, dimensions, etc., stated herein. Products, specifications and data in this literature are subject to change without notice.

The information given herein is based on data and tests which Emerson believes to be reliable and which are in accordance with today’s technical knowledge. It is intended for use by persons having the appropriate technical knowledge and skill, at their own discretion and risk. Our products are designed and adapted for fixed locations. For mobile applications, failures may occur.

The suitability for this has to be assured from the plant manufacturer, which may include making appropriate tests.

Note:
The components listed in this catalogue are not released for use with caustic, poisonous or flammable substances. Emerson cannot be held responsible for any damage caused by using these substances.

About Emerson

Emerson (NYSE: EMR), headquartered in St. Louis, Missouri (USA), is a global technology and engineering company providing innovative solutions for customers in industrial, commercial, and residential markets. Our Emerson Automation Solutions business helps process, hybrid, and discrete manufacturers maximize production, protect personnel and the environment while optimizing their energy and operating costs. Our Emerson Commercial and Residential Solutions business helps ensure human comfort and health, protect food quality and safety, advance energy efficiency, and create sustainable infrastructure. For more information visit Emerson.com.

Contact lists

Asia Pacific Headquarte rs
Suite 2503-10A, 25/F, Exchange Tower,
33 Wang Chiu Road, Kowloon Bay,
Kowloon, Hong Kong
Tel: (852) 2866 3108
Fax: (852) 2520 6227

Australia
356 Chisholm Road
Auburn NSW 2144, Australia
Tel: (612) 9795 2800
Fax: (612) 9738 1699

China – Beijing
Room 1203-1205,
North Wing Junefield Plaza Central Tower,
No. 10 Xuan Wu Men Wai Street,
XiCheng District, Beijing, PRC
Tel: (8610) 5095 2188

China – Guangzhou
Guangzhou Office
Unit 2202B, 22/F, Leatop Plaza,
32 Zhujiang East Road, Tianhe Dist.,
Guangzhou 510623, PRC
Tel: (8620) 8595 5188

China – Shanghai
Shanghai Sales Office
7/F, Emerson Building, 1582 Gumei
Rd, Shanghai, PRC
Tel: (8621) 3338 7333

India – Mumbai
601-602, 6/F Delphi B-Wing,
Central Avenue,
Hiranandani Business Park,
Powai, Mumbai 400076, India
Tel: (9122) 6786 0793
Fax: (9122) 6662 050

India – Pune
Plot No. 23, Rajiv Gandhi Infotech Park,
Phase – II, Hinjewadi,
Pune 411 057, Maharashtra, India
Tel: (9120) 4200 2000
Fax: (9120) 4200 2099

Indonesia
23/F North Tower,
Sampoerna Strategic Square–
Jl. Jend. Sudirman Kav. 45-46,
12930, Jakarta Indonesia
Tel: (6221) 2509 1400,
(6221) 5793 1000
Fax: (6221) 5793 0883

Japan
No. 3-9-5 Shin-Yokohama,
Shin-yokohama Tosho Building,
Kohoku-ku, Yokohama,
222-0033 Japan
Tel: (8145) 475 6371
Fax: (8145) 475 3565

Malaysia
No. 1, Block A
Jalan SS13/5 Subang Jaya
Selangor 47500, Malaysia
Tel: (603) 5624 2888

Middle East & Africa
PO Box 26382
Jebel Ali Free Zone – South
Dubai, UAE
Tel: (9714) 811 8100
Fax: (9714) 886 5465

Philippines
10/F SM Cyber West Avenue,
EDSA cor. West Avenue,
Barangay Bungad, Diliman,
Quezon City 1105, Philippines
Tel: (632) 689 7200 ext. 4395

Saudi Arabia
PO Box 34332
3620 Building 7874, Unit 1,
67th street 2nd Industrial City
Dammam, Saudi Arabia
Toll Free: 800 844 3426
Tel: (966) 3814 7560
Fax: (966) 3814 7570

South Korea
5/F, NIA Building,
Cheonggyecheon-ro,
Jung-gu 04520, Seoul Korea
Tel: (822) 3483 1500
Fax: (822) 592 7883

Taiwan
3/F, No. 122 Lane 235,
Pao Chiau Rd., XinDianv Dist.,
New Taipei City 23145, Taiwan (R.O.C.)
Tel: (8862) 8912 1360
Fax: (8862) 8912 1890

Thailand
34/F, Interlink Tower,
1558/133, Bangna Trad,
Bangkok 10260, Thailand
Tel: (662) 716 4700
Fax: (662) 751 4241

United Arab Emirates
PO Box 26382
Jebel Ali Free Zone
Dubai, UAE
Toll Free: 800 441 3428
Tel: (971) 4811 8100
Fax: (971) 4886 5465

Vietnam
9.04/F, Block A2, Viettel Tower
285 Cach Mang Thang Tam, District 1
Ho Chi Minh City, Vietnam
Tel: (84) 28 6290 8243

Scan to visit:

Scan to visit

Emerson.com

Asia 01 00 Issued 07/2021 Emerson is a trademark of Emerson Electric Co. or one of its affiliated companies. ©2021 Emerson Electric Co. All rights reserved.

FIG 28 Sosial Media

EMERSON. CONSIDER IT SOLVED

Read More About This Manual & Download PDF:

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Emerson User Manuals

Related Manuals