Honeywell VR8305 Direct Ignition Combination Gas Control User Manual
- June 7, 2024
- Honeywell
Table of Contents
Honeywell VR8305 Direct Ignition Combination Gas Control User Manual
Application
These direct ignition combination gas controls are used in gas-fired appliances with capacities up to 300 feet3/hour at 1 inch wc pressure drop [8.5 meters3/hour at 0.25 kPa] on natural gas. They include a manual valve, two automatic operators, and a pressure regulator. See Table 1 for temperature ranges and regulator types. VR8305 set up for natural gas includes a 393691 LP Conversion Kit. The kit contains a cap screw, a pressure regulator adjustment screw, a tapered spring and a conversion label.
CAPACITY :
Size(Inlet x Outlet)| Capacity(at 1 inch wc pressure dropa)|
Minimum Regulated Capacity| Maximum Regulated Capacity
---|---|---|---
1/2 x 1/2| 240 feet 3 /hour [6.8 meter 3 /hour]| 30 feet 3 /hour [0.8 meter 3
/hour]| 340 feet 3 /hour [9.6 meter 3 /hour]
1/2 x 3/4| 270 feet3 /hour[7.6 meter 3 /hour]| 30 feet 3 /hour[0.8 meter 3
/hour]| 370 feet 3 /hour[10.5 meter 3 /hour]
3/4 x 3/4| 300 feet 3 /hour[8.5 meter 3 /hour| 30 feet 3 /hour 0.8 meter 3
/hour]| 415 feet 3 /hour[11.8 meter 3 /hour]
Capacity based on 1000 Btu/feet 3 , 0.64 specific gravity natural gas at 1 inch wc pressure drop [37.3 MJ/meter 3 , 0.64 specific gravity natural gas at 0.25 k Pa pressure drop].
Use conversion factors in Table 3 to convert capacities for other gasses.
TABLE 1—TEMPERATURE RANGES AND REGULATOR TYPES.
Model Number | Ambient Temperature Range | Regulator Type |
---|---|---|
VR8305H | 0° F to 175° F |
-18° C to +79° C]
| Slow-opening
VR8305K| -40° F to 175° F
[-40° C to +79° C]| Slow-opening
VR8305M| -40° F to 175° F [-40° C to +79° C]| Standard-opening
VR8305P| -40° F to 175° F [-40° C to +79° C]| Step-opening
APPROVALS:
American Gas Association design certificate:
UP-70-69A.
Canadian Gas Association design certificate:
UP-70-69A.
Australian Gas Association design certificate:
Applied for. Delta C: P-70-42A19
TABLE 2—FLANGE PART NUMBERS.
Inlet
Outlet
Pipe Size
| Flange
Type
| Part Number
---|---|---
Without
Hex
Wrench
| With
Hex
Wrench
1/2 inch NPT| Straight
Elbow
| 393690-6
393690-3
| 393690-16
393690-13
3/4 inch NPT| Straight
Elbow
| 393690-4
393690-5
| 393690-14
393690-15
NOTE: Flange Kits include one flange with attached Oring and four mounting screws.
TABLE 3—GAS CAPACITY CONVERSION FACTORS
Gas | Specific Gravity | Multiply Listed Capacity By |
---|---|---|
Manufactured | 0.60 | 0.516 |
Mixed
Propane
| 0.70
1.53
| 0.765
1.62
Installation
WHEN INSTALLING THIS PRODUCT…
- Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
- Check the ratings given in the instructions and on the product to ensure the product is suitable for your application.
- Ensure installer is a trained, experienced service technician.
- After installation is complete, use these instructions to check out product operation.
WARNING
FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH
Follow these warnings exactly.
- Disconnect power supply before wiring to prevent electrical shock or equipment damage.
- To avoid dangerous accumulation of fuel gas,turn off gas supply at the appliance service valve before starting installation, and perform Gas Leak Test after completion of installation.
- Always install sediment trap in gas supply line to prevent contamination of gas control.
- Do not force the gas control knob. Use only your hand to turn the gas control knob. Never use any tools. If the gas control knob will not operate by hand, the gas control should be replaced by a qualified service technician. Force or attempted repair may result in fire or explosion.
CAUTION
Never apply a jumper across or short the valve coil terminals. This may burn out the heat anticipator in the thermostat or damage the electronic direct ignition (DI) module.
IMPORTANT: These gas controls are shipped with protective seals over inlet and outlet tapping. Do not remove seals until ready to connect piping.
Follow the appliance manufacturer instructions if available; otherwise, use the Instructions provided below.
WARNING
FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH
- Do not use a gas control set for natural gas on LP gas or a gas control set for LP gas on natural gas.
- When making conversion, main and pilot burner orifices MUST be changed to meet appliance manufacturer specifications
VR8305 gas controls can be converted from one gas to another. To convert from natural gas to LP, use the 393691LP Conversion Kit that is included with the VR8305 Gas Control. To convert from LP to natural gas, use the 394588 Natural Gas Conversion Kit (order separately). Step-opening gas controls cannot be converted. To convert control from one gas to another:
-
Turn off main gas supply to the appliance.
-
Remove the regulator cap screw and pressure regulator adjusting screw.See Fig. 1.
Fig. 1—Top view of gas control -
Remove the existing spring.
-
Insert the replacement spring with tapered end down. See Fig. 2.
Fig. 2—Installation of conversion kit in regulated gas control. -
6. Check the regulator setting either with a manometer or by clocking the gas meter. Refer to Startup and Checkout.
-
Install the new cap screw.
-
Mount conversion label on control.
-
Install control and appliance according to appliance manufacturer instructions
Fig. 3—Install flange to gas control.
INSTALL ADAPTERS TO GAS CONTROL
Install adapters to gas control as follows:
Flanges
- Choose the appropriate flange for your application.
- Remove seal over gas control inlet or outlet.
- Ensure the O-ring is fitted in the flange groove. If the O-ring is not attached or is missing, do not use flange.
- With O-ring facing gas control, align the screw holeson the control with the holes in the flange. Insert and tighten the screws provided with the flange. See Fig. 3. Tighten the screws to 25 inch-pounds of torque to provide a gas-tight seal.
Bushings
- Remove seal over gas control inlet or outlet.
- Apply moderate amount of good quality pipe compound to bushing, leaving two end threads bare. On LP installation, use compound resistant to LP gas. Do NOT use Teflon tape.
- Insert bushing in gas control and thread pipe carefully into bushing until tight.
USING ADAPTERS TO SOLVE SWING RADIUS PROBLEMS
In some field service applications, it is difficult or impossible to thread the control onto the gas supply pipe because of space limitations. This problem can be resolved in many instances by using an adapter. The adapter in installed on the end of the supply pipe in place of the gas control, following the same precautions and instructions that are used for installing the gas control. After the adapter is installed, the gas control is attached to the adapter as outlined above. Note that using an adapter increases the overall length of the gas control.
CHOOSE GAS CONTROL LOCATION
Do not locate the gas control where it may be affected by steam cleaning, high humidity, dripping water, corrosive chemicals, dust or grease accumulation, or excessive heat. To ensure proper operation, follow these guidelines:
- Locate gas control in a well ventilated area.
- Mount gas control high enough above the cabinet bottom to avoid exposure to flooding or splashing water
- Ensure the ambient temperature does not exceed the ambient temperature ratings for each component.
- Cover gas control if appliance is cleaned with water, steam, or chemicals or to avoid dust and grease accumulation.
- Avoid locating gas control where exposure is possible to corrosive chemical fumes or dripping water. Locate the gas control in the appliance vestibule on the gas manifold. In replacement applications, locate the gas control in the same location as the old gas control.
Install Piping to Gas Control
All piping must comply with local codes and ordinances or with the National Fuel Gas Code (ANSI Z223.1 NFPA No. 54), whichever applies. Tubing installation must comply with approved standards and practices
- Use new, properly reamed pipe free from chips. If tubing is used, ensure the ends are square, deburred and clean. All tubing bends must be smooth and without deformation.
- Run pipe or tubing to the gas control. If tubing is used, obtain a tube-to-tube coupling to connect the tubing to the gas control.
- Install sediment trap in the supply line to the gas control. See Fig. 4.
Fig. 4—Install sediment trap.
Install Gas Control
- This gas control can be mounted 0-90 degrees, in any direction, including vertically, from the upright position of the gas control knob.
- Mount the gas control so gas flow is in the direction of the arrow on the bottom of the control.
- Thread pipe the amount shown in Table 4 for insertion into the gas control. DO NOT THREAD PIPE TOO FAR. Valve distortion or malfunction may result if the pipe is inserted too deeply into the gas control.
TABLE 4—NPT PIPE THREAD LENGTH IN INCHES.
**** Pipe
Size
| Thread Pipe
This Amount
| Maximum Depth
Pipe Can Be
Inserted Into Control
---|---|---
3/8| 9/16| 3/8
1/2| 3/4| ½
3/4| 13/16| 3/4
4. Apply a moderate amount of good quality pipe compound (do not use Teflon tape) to pipe only, leaving two end threads bare. On LP installations, use compound resistant to LP gas. Refer to Fig. 5.
Fig. 5—Use moderate amount of pipe compound
- Remove seals over gas control inlet and outlet if necessary
- Connect pipe to gas control inlet and outlet. Use wrench on the square ends of the gas control. If an adapter is used, place wrench on adapter rather than gas control. Refer to Figs. 1 and 6.
Fig. 6—Proper use of wrench on gas control with and without flanges
WIRING
Follow the wiring instructions furnished by the appliance manufacturer, if available, or use the general instructions provided below. All wiring must comply with applicable electrical codes and ordinances.
Disconnect power supply before making wiring connections to prevent electrical shock or equipment damage.
-
Check the power supply rating on the valve and ensure it matches the available supply. Install transformer, thermostat, and other controls as required.
-
Connect control circuit to gas control terminals. See Figs. 1, 7 and 8.
Fig. 7—VR8305 Wiring Connections in S87 Direct
Ignition System.- POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
- ALTERNATE LIMIT CONTROLLER LOCATION.
- MAXIMUM IGNITER-SENSOR CABLE LENGTH: 3 ft. [.9 m] OR LESS.
- 3 A REPLACEABLE FUSE.
- ALARM TERMINAL PROVIDED ON SOME MODELS. M9043
Fig. 8—VR8305 Wiring Connections in S89C Direct Ignition System
* POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. MAKE SURE L1 AND L2 ARE NOT REVERSED; THIS WOULD PREVENT FLAME DETECTION.
* ALTERNATE LIMIT CONTROLLER LOCATION.
* SEN TERMINAL AND Q354 FLAME SENSOR ON D MODELS ONLY.
- Adjust thermostat heat anticipator to 0.70 rating stamped on valve operator.
Start-Up and Checkout
WARNING
FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH
- Do not force the gas control knob. Use only your hand to turn the gas control knob. Never use any tools.
- If the gas control knob will not operate by hand, the gas control should be replaced by a qualified service technician.
GAS CONTROL KNOB SETTINGS
The gas control knob has two settings: OFF prevents main burner gas flow. ON permits main burner gas flow. Under control of the thermostat and direct ignition module, gas can flow to the main burner.
NOTE: Controls are shipped with the gas control knob in the ON position
PERFORM GAS LEAK TEST
WARNING:FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH Check for gas leaks with rich soap and water solution anytime work is done on a gas control.
GAS LEAK TEST
- Paint all pipe connections upstream of the gas control with a rich soap and water solution. Bubbles indicate a gas leak.
- If a gas leak is detected, tighten the pipe connection.
- Stand clear while lighting main burner to prevent injury caused from hidden gas leaks that could cause flashback in the appliance vestibule. Light the main burner.
- With the main burner in operation, paint all pipe joints (including adapters) and gas control inlet and outlet with rich soap and water solution.
- If another gas leak is detected, tighten adapter screws, joints, and pipe connections.
- Replace the part if gas leak cannot be stopped.
TURN ON SYSTEM
Rotate the gas control knob counterclockwise to ON
TURN ON MAIN BURNER
follow instructions provided by appliance manufacturer or turn thermostat up to call for heat.
-
Do not exceed the input rating stamped on the appliance nameplate, or manufacturer recommended burner orifice pressure for the size
orifice(s) used. Ensure the main burner primary air supply is properly adjusted for complete combustion (refer to the appliance manufacturer instructions). -
IF CHECKING GAS INPUT BY CLOCKING THE GAS METER:
- Ensure that the only gas flow through the meter is that of the appliance being tested.
- Ensure that other appliances are turned off and that their pilot burners are extinguished (or deduct their gas consumption from the meter reading).
- Convert the flow rate to Btuh as described in the Gas Controls Handbook (form 70- 2602) and compare to the Btuh input rating on the appliance nameplate.
-
IF CHECKING GAS INPUT WITH A MANOMETER (PRESSURE GAUGE):
- Ensure the gas control knob is in the PILOT position before removing the outlet pressure tap plug to connect the manometer.
- Turn the gas control knob back to PILOT when removing the manometer and replacing outlet pressure tap plug.
- Shut off the gas supply at the appliance service valve, or for LP gas at the gas tank, before removing the outlet pressure tap plug and before disconnecting the manometer to replace the outlet pressure tap plug.
- Perform the Gas Leak Test at the inlet pressure tap plug.
Standard-Opening and Slow-Opening Pressure Regulator
- The gas control outlet pressure should match the manifold pressure listed on the appliance nameplate.
- With the main burner operating, check the gas control flow rate using the meter clocking method or check the gas pressure using a manometer connected to the gas control outlet pressure tap. Refer to Fig. 1.
- If necessary, adjust the pressure regulator to match the appliance rating. Refer to Table 5 or 6 for the factory set nominal outlet pressures and adjustment ranges.
- Remove the pressure regulator adjustment cap and screw.
- Using a screwdriver, turn the inner adjustment screw clockwise to increase or counterclockwise to decrease the main burner gas pressure.
| | | Outlet Pressure
---|---|---|---
Nominal Factory|
| | Nominal Inlet| Setting| Setting Range
| Type of| Pressure| | Full| | Full
Model| Gas| Range| Step| Rate| Step| Rate
Standard-,| Natural| 5.0 – 7.0| | 3.5| | 3.0 – 5.0
|
Slow-opening| LP| 12.0 – 14.0| | 10.0| | 8.0 – 12.0
|
Step-| Natural| 5.0 – 7.0| 0.9| 3.5| | 3.0 – 5.0
opening| LP| 12.0 – 14.0| 2.2| 10.0| | 8.0 – 12.0
| | | Outlet Pressure
---|---|---|---
Nominal Factory|
| | Nominal Inlet| Setting| Settin g Range
Model| Type of
Gas| Pressure
Range| Step| Full
Rate| Step| Full
Rate
Standard-, Slow-opening| Natural
LP| 1.2 – 13
2.9 – 3.9| | 0.9
2.7| | 03 – 1.2
2.0 – 3.0
|
|
Step-| Natural| 1.2 – 13| 0.2| 0.9| | 03 – 1.2
opening| LP| 2.9 – 3.9| 0.9| 2.7| | 2.0 – 3.0 - Always replace the cap screw and tighten firmly to ensure proper operation.
- If the desired outlet gas pressure or gas flow rate cannot be achieved by adjusting the gas control, check the gas control inlet pressure using a manometer at the inlet pressure tap. If the inlet pressure is in the normal range (refer to Table 5 or 6), replace the gas control. Otherwise, take the necessary steps to provide proper gas pressure to the gas control.
Step-Opening Pressure Regulator
-
The gas control outlet pressure should match the manifold pressure listed on the appliance nameplate.
-
With the main burner operating, check the gas control flow rate using the meter clocking method or check the
gas pressure using a manometer connected to the gas control outlet pressure tap. Refer to Fig. 1. -
If necessary, adjust the pressure regulator to match
the appliance rating. Refer to Table 5 or 6 for factory set
nominal outlet pressures and adjustment ranges.-
Remove the pressure regulator adjustment cap screw.
-
Using a screwdriver, turn the inner adjustment screw
clockwise to increase or counterclockwise to decrease the main burner gas pressure. -
Always replace the cap screw and tighten firmly to
ensure proper operation.
-
-
If desired outlet pressure or flow rate cannot be achieved by adjusting the gas control, check the inlet pressure using a manometer at inlet pressure tap or upstream of the gas control. If the inlet pressure is in the normal range (refer to Table 5 or 6), replace the existing gas control. Otherwise, take the necessary steps to provide proper gas pressure to the gas control.
-
Carefully check main burner lightoff at the step pressure. Ensure the main burner lights smoothly and without flashback to the orifice and that all ports remain lit. Cycle the main burner several times, allowing at least 30 seconds between cycles for the regulator to resume the step function. Repeat after allowing main burner to cool. Readjust the full rate outlet pressure, if necessary, to improve lightoff characteristics.
CHECK SAFETY SHUTDOWN PERFORMANCE
WARNING: FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH Perform the safety shutdown test any time work is done on a gas system.
NOTE: Read steps 1-7 below before starting and compare to the safety shutdown or safety lockout tests recommended for the direct ignition (DI) module. Where they differ, use the procedure recommended for the module.
- Turn gas supply off.
- Set thermostat or controller above room temperature to call for heat.
- Watch for ignition spark or for glow at hot surface igniter either immediately or following prepurge. See DI module specifications.
- Time length of igniter operation. See DI module specifications.
- After the module locks out, open gas control and ensure there is no gas flow to main burner.
- Set thermostat below room temperature and wait one minute.
- Operate system through one complete cycle to ensure all controls operate properly
Maintenance
WARNING: FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH Improper cleaning or reassembly may cause gas leakage. When cleaning, ensure that control is reassembled properly and perform gas leak test.
Regular preventive maintenance is important in applications that place a heavy load on system controls, such as in the commercial cooking and agricultural and industrial industries because:
- The equipment operates 100,000-200,000 cycles per year in many such applications, particularly commercial cooking. Such heavy cycling can wear out the gas control in one to two years.
- Exposure to water, dirt, chemicals and heat can damage the gas control and shut down the control system.
The maintenance program should include regular checkout of the gas control, see Start-Up and Checkout, page 6, and the control system as described in the appliance manufacturer’s literature.
Maintenance frequency must be determined individually for each application. Some considerations are:
- Cycling frequency. Appliances that may cycle 100,000 times annually should be checked monthly.
- Intermittent use. Appliances that are used seasonally should be checked before shutdown and again before the next use.
- Consequence of unexpected shutdown. Where the cost of an unexpected shutdown would be high, the system should be checked more often.
- Dusty, wet, or corrosive environment. Since these environments can cause the gas control to deteriorate more rapidly, the system should be checked more often. The gas control should be replaced if:
- It does not perform properly on checkout or troubleshooting.
- The gas control knob is hard to turn or push down, or it fails to pop back up when released.
- The gas control is likely to have operated for more than 200,000 cycles.
WARNING: FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE, INJURY, OR DEATH Do not disassemble the gas control; it contains no replaceable components. Attempted disassembly or repair may damage the gas control.
CAUTION: Do not apply a jumper across or short the valve coil terminals. Doing so may burn out the heatanticipator in the thermostat or damage the DI module.
IMPORTANT: Allow 60 seconds after shutdown before re-energizing step- opening model to ensure lightoff at step pressure.
IF MAIN BURNER WILL NOT COME ON WITH CALL FOR HEAT:
- Ensure gas control knob is in the ON position
- 2. Adjust thermostat several degrees above room temperature.
- Using ac voltmeter, measure voltage across MV terminals at gas control.
- If no voltage is present, check control circuit for proper operation.
- If proper control system voltage is present, replace gas control.
INSTRUCTIONS TO THE HOME OWNER FOR YOUR SAFETY, READ BEFORE OPERATING:
FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH
Follow these warnings exactly:
- Pilot flame is lit automatically. Do not light the pilot flame manually.
- Before lighting pilot burner flame, smell around the appliance for gas. Be sure to smell next to floor because LP gas is heavier than air.
- IF YOU SMELL GAS:
- Turn off the gas supply at the appliance service valve. On LP gas systems, turn off gas supply at the gas tank.
- Do not light any appliances in the house.
- Do not touch electrical switches or use the phone.
- Leave the building and use a neighbor’s phone to call your gas supplier.
- If you cannot reach your gas supplier, call the fire department.
- Do not force the gas control knob. Use only your hand to push down or turn the gas control knob. Never use any tools. If the gas control knob will not operate by hand, the gas control should be replaced by a qualified service technician. Force or attempted repair may result in a fire or explosion.
- The gas control must be replaced in case of any physical damage, tampering, bent terminals, missing or broken parts, stripped threads, or evidence of exposure to heat.
IMPORTANT: Follow the operating instructions provided by the manufacturer of your heating appliance. The information below will be of assistance in a typical control application, but the specific controls used and the procedures outlined by the manufacturer of your appliance may differ, requiring special instructions.
STOP: READ THE WARNINGS ABOVE.
The pilot flame is lit automatically. If the appliance does not turn on when the thermostat is set several degrees above room temperature, follow these instructions.
-
Set the thermostat to its lowest setting to reset the safety control.
-
Disconnect all electric power to the appliance.
-
Remove the gas control access panel.
-
Push in the gas control knob slightly and turn
clockwise to OFF. -
Wait five minutes to clear out any unburned gas. If you then smell gas, STOP! Follow step 3 in the WARNING above. If you do not smell gas, continue with the next step.
-
Turn the gas control knob counterclockwise to ON.
-
Replace the gas control access panel.
-
Reconnect all electric power to the appliance.
-
Set the thermostat to the desired setting.
-
If the appliance does not turn on, set the gas control knob to OFF and contact a qualified service technician for assistance.
TURNING OFF THE APPLIANCE
VACATION SHUTDOWN—Set the thermostat to the desired room temperature while you are away. COMPLETE SHUTDOWN—Push the gas control knob in slightly and turn clockwise to OFF. Do not force. Appliance will completely shut off. Follow the lighting procedures above to resume normal operation.
Residential and Building Controls Division Honeywell Inc. 1985 Douglas Drive North Golden Valley, Minnesota 55422
Residential and Building Controls Division Honeywell Limited—Honeywell Limitée 740 Ellesmere Road Scarborough, Ontario M1P 2V9
Helping You Control Your World
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>