Honeywell PC3F2699IUF00 Hydronic Circulating 3 Speed Pump Datasheet

June 7, 2024
Honeywell

Honeywell PC3F2699IUF00 Hydronic Circulating 3 Speed Pump

APPLICATION
The PC3F in-line, wet rotor circulator with universal flange is designed for applications in closed-loop hydronic heating and cooling systems, as well as in solar-powered systems. The pump is non-submersible and for use in dry, frost-free, well-ventilated installations.

SPECIFICATIONS

Rate of flow: up to 34 gpm (128.7 lpm)
Pressure head: up to 31 ft (9 m)
Voltage: 115VAC +/-10% 60hz
Amperage: See “Speed switching” on page 2. Max. Pressure:
145 psi (at room temperature); 50 psi (at 200°F [93°C])
Temperature Range: Ambient temperature: 32°F to 104°F (0°C to 40°C) Media temperature: 14°F to 230°F (-10°F to 110°C) [to 200°F
(93°C) with optional check valve installed] Storage Temperature: -40°F to 100°F (-40° to 66°C)
Standards: Insulation Class F  Temperature Class FT 95image
1

L1 L2 L3 L4 L5
6.5 (165.5) 6.1 (155) 6.5 (165.5) 7.75 (197) 3.2 (80.2)

Shipping weight: 9.5 lbs (4.32 Kg)

Materials

Component Material
Pump body Cast iron
Impeller Polyamide
Shaft Ceramic
Bearing Ceramic
Bearing plate Stainless steel
Can Stainless steel

Control: 3-step switch with manual speed selection
Motor protection
The motor includes an internal thermal overload protection.  External motor protection is not required.
Speed switching
Three speed, with manual selector.

Speed Volts Amps Watts
1

115

| 1.09| 125
2| 1.52| 175
3| 1.78| 205

Flange Connections
Universal flange
Bolt hole spacing 3-5/32 in. (80.2 mm) Bolt holes 1/2 in. (12.7 mm)

Media
Clean water or water with up to 20% glycol. Up to 50% glycol may be used, but flow characteristics will differ from these specifications.image
2

Optional and Replacement Parts
Check valves: PCV125
Flange gasket: PCG100

Table 1. Cross Reference for Pump Replacement

Honeywell| Grundfos| Taco| Bell & Gossett| Armstrong| Wilo
---|---|---|---|---|---
Model| Pump Length| Speed| Single Speed| 3-Speed| Single Speed| 3-Speed|  |  | Single Speed| 3-Speed




PC3F2699IUF00

| ****


6.5”

| High| UP26-96F UP26-96F-FC UP26-116F UP26-116F-FC| UPS26-99 High UPS26-99-FC High| 0011F

0011F-IFC

0013F

0013F-IFC

|  | NRF-36 Med NRF-45 Med H-41| E7

Astro 50

Astro 50-3

| Star 30F Star 32F| S21 High
Medium| UP26-64F UP26-99FC| UPS26-99 Low UPS26-99-FC Low| 0014F

0014F-IFC

|  |  |  | Star 17 FX| S21 Med
Low|  |  |  |  | NRF-33|  |  | Star S21 Low

The information in this table is based on publicly available information as of the date of this publication. Honeywell is not liable if  information is found to be incorrect.
If the cross-referenced model uses a flow check valve, then use a flow check with the Honeywell model as well. Each Honeywell circulator replaces both regular and rotated flange models.

Automation and Control Solutions Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Honeywell User Manuals

Related Manuals