Honeywell FocusPRO Thermostats 5000/6000 Series Installation Guide
- June 7, 2024
- Honeywell
Table of Contents
FocusPRO®5000 and 6000 SeriesThermostats
INSTALLER SETUP AND SYSTEM TEST POCKET GUIDE
This is a legacy product document supported by Resideo. It is no longer
manufactured
INSTALLER SETUP
FocusPRO®5000 Series
-
To begin, press and hold the and FAN buttons until the display changes.
-
Press or to change settings.
-
Press NEXT to advance to the next function.
-
Press DONE to exit and save settings.
-
Proceed to Installer Setup Functions on page 4.
FocusPRO ® 6000 Series
-
To begin, press and hold the and FAN buttons until the display changes.
-
Press or to change settings.
-
Press NEXT to advance to the next function.
-
Press DONE to exit and save settings.
-
Proceed to Installer Setup Functions on page 4.
INSTALLER SETUP FUNCTIONS.
Available options and default settings vary by the thermostat.
|
Table 1. Installer Setup
---|---
|
Setup functions
| |
Setting & Options
| | | (factory default in bold)
1| System type| 0| 1 heat / 1 cool Cony.
| | 1| 1 heat / 1 cool heat pump (no Aux. heat)
2| Heat only (2-wire, 3-wire zone valves [Series 20], and normally open zone
valves)
3| Heat only with fan
4| Cool only
5| 2 heat / 1 cool heat pump (with Aux. heat)
6| 2 heat / 2 cool Corm
7| 2 heat / 1 cool Cony.
8| 1 heat / 2 cool Corm
9| 2 heat / 2 cool heat pump
| (no Aux. heat)
10| 3 heat / 2 cool heat pump (with Aux. heat)
2| Changeover valve (0/B terminal)| 0| Controls valve in cooling
1| Controls valve in heating
3| Fan control (heating)| 0| Gas/Oil heat (equipment controls
heating fan)
1| Electric furnace (thermo-
stat controls heating fan)
5| First stage heat cycle rate| 5| Gas or oil furnaces of less
than 90%
efficiency
1| Steam or gravity
3| Hot water systems or fur-
naces of 90%+ efficiency
9| Electric furnaces
| [Other options: 1-12]
6| Second stage heat/Aux heat cycle rate| 5| Gas or oil furnaces of
less than 90% efficiency
1| Steam or gravity
3| Hot water systems or fur-
naces of 90%+ efficiency
9| Electric furnaces
| [Other options: 1-12]
7| Auxiliary heat cycle rate| 5| Gas or oil furnaces of less
than 90% efficiency
1| Steam or gravity
3| Hot water systems or fur-
naces of 90%+ efficiency
9| Electric furnaces
| [Other options: 1-12]
8| Emergency heat cycle rate| 9| Electric emergency heat
---|---|---|---
1| Steam or gravity
3| Hot water systems or fur-
naces of 90%+ efficiency
5| Gas or oil furnaces of less than 90% efficiency
| [Other options: 1-12]
9| First stage compressor cycle rate| 3| Recommended [Other options: 1-6]
10| Second stage compressor cycle rate| 3| Recommended [Other options: 1-6]
12| Manual/Auto changeover| 0| Manual changeover (Heat/Cool/Off)
1| Auto changeover (Heat/
| CooUAuto/Off)
2| Auto changeover only
| (Auto)
13| Adaptive Intel- ligent Recovery”| 1| On
0| Off
14| Temperature display| 0| Fahrenheit
1| Celsius
15| Compressor protection| 5| 5-minute compressor off time
| [Other options: 0-4 minutes]
16| Schedule format I| 0| 5/2 (weekdays
and weekends
1| programmable) 5/1/1 (weekdays,
| Saturday, and Sunday programmable)
26| Auxiliary heat control| 0| Comfort
1| Economy
27| Heat temperature range stops| 90| Max. heat temperature setting is 90°F
(32°C)
| [Other options: 40-89°F
| (4.5°C to 32°C)]
28| Cool temperature range stop| 50| Min. cool temperature setting is 50°F
(10°C)
| [Other options: 51-99°F
| (10.5°C to 37°C)]
INSTALLER SETUP TEST
Functions 13 and 16 are only available on the 6000 series; function 26 is only available on the 5000 series
FocusPRO ® 5000 Series
-
To begin, press and hold the and t buttons until the display changes.
-
Presss / to turn the system on/off.
-
Press NEXT to advance to the next test.
-
Press DONE to terminate the system test.
-
Proceed to Installer System Tests on page 8.
FocusPRO ® 6000 Series
-
To begin, press and hold the and buttons until the display changes.
-
Presss / to turn system on/off.
-
Press NEXT to advance to the next test.
-
Press DONE to terminate the system test.
-
Proceed to Installer System Tests on page 8.
INSTALLER SETUP TESTS
Test the system’s heating, emergency heat, cooling, and fan. Available tests vary by thermostat and system type.
Table 2. Installer System Test
System Test Number| Test Type| System Status Number
and Description
10| Heating system| 0 Heat and fan off
1 First stage heat on (Fan turns on if Setup Function 1 is set to 1, 5,
9, or 10 OR setup Function 3 is set to 1)
2 Second stage heat on
3 Third stage heat on
20| Emergency heating system| 0 Heat and fan off
1 Heat and fan on
2 Second stage heat (Aux. heat) turns on
30| Cooling system| 0 Compressor and fan off
1 Compressor and fan on
2 Second stage compressor on
40| Fan system| 0 Off
1 On
CAUTION
EQUIPMENT DAMAGE HAZARD.
Compressor protection is bypassed during testing. To prevent equipment damage,
avoid cycling the compressor quickly.
Printed in the U.S.A. on recycled paper containing at least 10% post-
consumer paper fibers. Automation and Control Solutions.
Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422
Honeywell Limited- Honeywell Limitée 35 Dynamic Drive Toronto, Ontario M1V 4Z9
http://yourhome.honeywell.com
® the U.S. registered Trademark © 2006 Honeywell International Inc. US Patent
No. 6595430, D509151; other Patents Pending. All Rights Reserved 69-2026 M.S.
09-06