Gamko Photovoltaic Module Installation Guide
- June 7, 2024
- Gamko
Table of Contents
Photovoltaic Module
7FSTJPO(AMKO@97
AUTHORITY FOR GAMKO USE
Global Installation Manual for GAMKO Photovoltaic Module
CONTENTS
Purpose of this manual
02
Disclaimer
02
Safety and Transport
03
Mechanical Installation
04
Electrical Installation
10
AUTHORITY FOR GAMKO USE Grounding
Bypass Diodes and Block Diodes Maintenance
11 12 13
01
Purpose of this manual
This manual is used for GAMKO solar modules (here in after referred to as the
Module or Modules) only. This manual contains installation methods, operation
safety and relevant maintenance information of Gamko’s Modules . Modules mus t
b e installed by professionals . Please ready this manual carefully before
installation. T he ins taller s mus t follow all the rules describe d in this
manual strictly as well as local requirement s and regulations by law or
authorized organiz
SE ations . U B e fore ins t alling, th e ins t aller mus t b e f amiliar w
ith th eir m e chanic al and e le c tric al O re quirem ent s . Pleas e ke ep
this manual in a s afe p lace for f uture re ference (c are and K maintenance)
and in c ase of s ale or disp os al of the M o dules . D i s c l a i m e r Y
FOR GAM Gamko shall not be responsible for any loss arising from installation,
operation, use IT or maintenance of the Modules which is not complying with
the guidance of this R manual, including breakdown or damage of the Modules or
any other expenses O i n c u r r e d .
Any cus tomer shall not get any patent or authoriz ation of the patent when
using the
TH M o dules , e xpresse d or imp lie d. Any inf ringem ent of p atent s or
other right s of the third U par t y, which may result f rom the use of the
Module, is not within the responsibilit A y scope of Gamko.
The information in this manual is based on Gamko’s knowledge and experience
and is believe d to b e reliable, but such information including product
specification (without limitation) and relevant suggestions do not constitute
a warrant y, e xpressed or implied. Gamko reserves the right s to change the
manual, the Modules, the specifications or any other information of the
Modules without prior notice.
02
SA F E T Y&T R A N S P O R T
Unpacking and Storage
Keep all the Modules and electrical connectors clean and dry before
installation. Use dry and ventilated room when storing uninstalled modules.
Use both hands to carry Modules. Do not overlap Modules. Be cautious when
carrying Modules. Slip-proof gloves are necessary. Use supportive
disassembling tools when unpacking .
AUTHORITY FOR GAMKO USE Do not stamp on Modules or put weight on Modules.
Do not disassemble or drop Modules. Do not use mirrors or magnifiers
concentrated sunlight onto Modules. Do not lift the module by grasping the
junction box. Do not use any sharp object with Modules. Do not directly apply
pressure on the glass surface or backsheet of Modules. Must use both hands to
carry Modules. Do not touch the surface of the coated glass with bare hands.
Ensure all contacts and the operating environment are clean and dry.
Modules Carry and Installation Instruction
Both hands when handling Modules
Ensure Modules are fixed properly
Do not use sharp objects with Modules
Do not pulling the wiring cables or junction box
Do not stamp on Modules
Do not touch Modules with bare or dirty hands
Do not pile up Modules on uneven ground
Do not drop or throw Modules
03
MECHANICAL INSTALLATION
Location Selection
Select suit able places to ins t all Modules .
Ins t all Modules at the places with sufficient sunlight and without shade at any time.
If a module is shaded or even partially shade d, it will result in lower power
output. A permanent or regular shade will cause damage to the module, which will
void GAMKO ‘s warrant y. Do not place, install or use Modules at the places
where combustible gas is easily
SE generated or gathering. U The straight- line distance between the
installation site and coastline shall not KO be shorter than 1 km unless there
is a writ ten approval from GAMKO or an M engagement specified in the
contract.
I n s t a l l a t i o n A n g l e FOR GA Modules in the same string should be installed at the same angle. Modules installed in Y different angles w ill re ceive different ir r adiation, w hich w ill c aus e cur rent different . A s IT a result, it will de crease the op eration efficienc y of the s ystem. OR Please refer to Table 1 for the re commende d ins tallation angles of the Mo dules.
AUTH Local Latitude
Module installation angle
0°~ 15°
15°
15°~ 25°
Latitude
25°~ 30°
L atitude+5°
30°~ 35°
L atitude+10°
35°~ 40°
L atitude+15°
40°
L atitude+20°
Table 1
04
Module Installation
General Installtion
The mounting structure must be made of durable, corrosion-resistant and UV-
resistant materials. Always use a tested and certified mounting structure for
the system.
Make sure Modules are securely fastened to the mounting structure to withstand
AUTHORITY FOR GAMKO USE corresponding wind load and snow load.
Select a suitable height for the mounting system to prevent the lowest portion
of the Module covered by snow in winter. In addition, ensure the bottom of the
Module is high enough so that the Module will not be shaded by plants or
damaged by flying sands. A s for the system installed on the ground, the
minimum distance Gamko recommends between the bot tom of Modules and the
ground should b e 24 inches (6 0 cm). Before installing Modules onto a
rooftop, make sure the roof construction is suitable and the installed Modules
will not exceed the roof area. Besides, the roof must be properly sealed to
prevent leaks.
When installing Modules to a pole, the selected mounting structure and pole
shall be able to withstand the expected wind load and snow load in the area.
Make sure Modules are not subject to wind or snow loads exceeding the maximum
load permitted by GAMKO and not subjected to excessive force due to the
thermal e xpansion of the mounting sys tem. It is not allowed to overlap the
Modules .
Provide adequate ventilation to the back of the Module for cooling. A minimum
distance of 10cm between the installation surf ace and the Module is GAMKO
generally recommended. To prevent the linear thermal expansion of the Module
frames, GAMKO sugges t s that the minimum distance between two Modules should
not b e shorter than 2cm.
Always follow the guidance and safety rules specified in the mounting system.
Do not drill holes on the glass sur f ace or the frames of the Module, which
will void the warrant y.
05
Installation Method
Modules can be installed on the frame in the following 3 methods.
Mounting hole system: Use anticorrosive M8 bolts to install the Module on the
support frame through the installation holes on its own frame, as shown in
Figure 1.
AUTHORITY FOR GAMKO USE Module Mounting Structure
NM8ut(M8,SS) Springwasher Flat washer
Figure 1
1
MB8olt(M8,SS)
Clamping system: Use suitable clamps to fix the Module on the support frame, as shown in Figure 2.
M8
MN8ut(M8,SS) Springwasher
Flat washer Clamp
MB8olt(M8,SS)
Module
MS tor uu nctt
in ur
g e
2
M8
Figure 2
I n s e r t i o n s ys t e m : Ins e r t th e w h ol e2M o dul e into th e r ail, as sh ow n in Figure 3.
3
3 Figure 3
06
Mounting hole system
Select a suit able installation method depending on the load requirement s. More detailed information is shown in Figure 4.
It has been tested that Gamko’s Modules can withs t and the loads of 240 0 Pa, 380 0 Pa and 540 0 Pa (IEC 61215 Standard), which are respectively equivalent to 160 0 Pa (0. 232 psi), 250 0 Pa (0. 363 psi) and 360 0 Pa (0. 522 psi) under UL1703 Standard, when different installation methods are used.
AUTHORITY FOR GAMKO USE 2400Pa
3800Pa
5400PaSnow Loads Only
Permissible clamp
Use 4 mounting holes Permissible clamp
Use 8 mounting holes
Permissible clamp
Permissible clamp
Use 4 mounting clips Permissible clamp
Use 4 mounting clips
Use 4 mounting clips Permissible clamp
Use 6 mounting clips
Clamping system Attachment to the long frame
Clamping system Attachment to the short frame
Insertion system
Use 4 mounting clips Insertion system Insertion system
Use 4 mounting clips on short frame Use 2 mounting clips on long frame
Permissible clamp
Insertion system
Insertion system
07
2400Pa
3800Pa
5400PaSnow Loads Only
Mounting hole system
Clamping system Attachment to the long frame
Clamping system Attachment to the short frame
AUTHORITY FOR GAMKO USE Permissibleclamp
Use 4 mounting holes Permissible clamp
Use 8 mounting holes
Permissible clamp
Permissible clamp
Use 4 mounting clips Permissible clamp
Use 4 mounting clips
Use 4 mounting clips Permissible clamp
Use 6 mounting clips
Use 4 mounting clips
Use 4 mounting clips on short frame Use 2 mounting clips on long frame
Permissible clamp
Insertion system Insertion system
Figure 4
08
Insertion system
Module Specification (as shown in Figure 5 and Table 2)
Barcode
8-9X14Mounting hole
No.
AUTHORITY FOR GAMKO USE Groundinghole
Front View
Side View
Figure 5
Back View
Module Type A
B
C
D
E
F
G
H
GK60P-XXX
Frame Section
Unite:mm
We ight(kg)
1 GK60M-XXX
992 1640 35 941 990 1350 11
35
18.5
GK60MH-XXX
GK72P-XXX
2 GK72M-XXX
992 1956 35 941 1176 1676 11
35
22.5
GK72MH-XXX
3
GK96P-XXX
1008 2568 40 958 1428 1928 11
35
36.5
4
GK72PH-XXX 1020 1945 40 970 1176 1676 11
35
21.5
5 GK60DG-XXX 992 1658 6
NA NA NA NA NA
23
6 GK72DG-XXX
992 1968 6
NA NA NA NA NA
27
*”XXX”refers to Module Power Index. Table 2
09
ELECTRICAL INSTALLATION
DC power generated by the photovoltaic system can be converted into AC power
and fed into the grid. Policies on connecting renewable energy system to the
grid vary from region to region. Consult senior system designer before
designing the system. Generally, the system installation shall be formally
approved by the local public sector.
General Installation
AUTHORITY FOR GAMKO USE Installation structure should be compatible with
aluminum frame of module, in order
to avoid galvanic corrosion. Any defects caused by such corrosion will void
the w a r r a n t y. Negative grounding is recommended during installation of
Modules to prevent PID effect. Positive and negative part of the module should
use the same type of connector for electrical connection. It is forbidden for
non-professionals to open the lock nuts of the connector. Make sure that the
connectors are clean, dry and fully connected (A click sound should be heard
when fully connected), otherwise it may lead to electric arc sparks which will
damage the connector or cause a fire. All electrical components should have
ratings equal or greater to the system rating. Do not exceed the maximum of
system voltage marked on the module label. Under normal conditions, a Module
may produce more current and/or voltage than reported at standard test
conditions. Accordingly, the values of ISC and Voc marked on the Module should
be multiplied by a factor of 1.25 when determining component voltage ratings,
current ratings, fuse sizes, and size of controls connected to the PV output.
Completely cover the Modules with an opaque material to prevent electricity
from being generated during disassembling the conductors.
10
When connected in series, the maximum number of the Modules are determined by
the system design, inverter type and environment. ( shown in Figure 6).
When connected in parallel, the current output is equal to the sum of each
string’s current ( shown in Figure 7). Fuse is necessary for each module
string. Please take reference to the local regulation. Recommended maximum
parallel Modules configurations: Fuse rating/Isc+1.
AUTHORITY FOR GAMKO USE Figure 6
Figure 7
Please refer to the local regulations to determine the system wire size, types
and temperatures.
The cross section of the cables and the capacity of the connectors must be
selected to suit the maximum system short circuit current (The
recommended section area for a single piece of Module is 4 mm , and the
recommended rated current for the connector is greater than 10A),
otherwise the cables and connectors shall be overheated under large
current. Caution: The maximal temperature of the cable is 85 C while the
upper limited temperature of the connector is 105 C.
Make sure the electric components such as the connectors and inverters are off-state during the installation.
To reduce lightning damage, the loop area should be kept as small as possible when laying cables. It is recommended to use fuses in each string.
11
GROUNDING
All the module frames and mounting structures shall be grounded according to
regional and national electricity regulations. Use recommended hardware to
connect grounding cables and fasten to the Module frames. While using the
metal structure, make sure the surface of the system have been electroplated
to keep a good conducting circuit. Use suitable grounding conductors to
connect the Module frame to the mounting
AUTHORITY FOR GAMKO USE structure. This can achieve proper grounding effects.
The grounding conductor must be connected to ground via an appropriate
grounding electrode. It is recommended to use lugs to connect the grounding
cables. If it is only mechanically connected to a grounded module without
bolts and nuts, the mounting system should be grounded as well.
Grounding by lugs
First, peel the grounding cable to a proper length withot damage to the metal
core. Then insert the peeled cable into the lug, tighten the screw. As shown
in Figure 8, connect the lug to the aluminum frame with stainless steel bolts
and connection components. The recommended tightening torque for M3 bolts is
2.3 N·m.
Nut (M3,SS) Spring washer Flat washer
Frame
Grounding Lug Grounding cable
Star washer Bolt (M3,SS)
Figure 8
12
Grounding by cable
The grounding bolts must be made of stainless steel and be used in the specified
grounding holes. First, make the M3.5 stainless steel bolt pass through the spring washer,
flat washer, cup washer (copper conductor with a diameter of 2.1 mm) and star washer,
and then insert through the grounding hole, flat washer and spring washer on the frame.
Finally, tighten with a M3.5 nut. Caution: The upper limited temperature of the conductor
USE is 85. As for the installation, refer to Figure 9.
Nut (M3.5,SS)
Spring washer Flat washer
GAMKO Frame B y p ass ADUiToHdOReIsTYaFnORd B l o c k D io de s Copperwire
Figure 9
Star washer
Flat washer Cup washer Spring washer
Bolt (M3.5,SS)
In a system with two or more Modules connected in series, if part of a Module
is shaded while the other part is exposed to the sun, a very high reverse
current will go through the cells which have been partly or entirely covered
and it will cause overheat on the cells, which may damage the Module. Using
bypass diodes can protect Modules from this kind of risk. There are bypass
diodes in junction boxes, which can reduce the effects of partial shadows. Do
not privately disassemble the junction box to replace the diodes, even when
the diodes are broken. This should be processed by the professionals.
In a system with batteries, if the controller doesn’t have the function of
backswing protection, block diodes installed between the battery and the
Module can prevent the reverse current from damaging the Module.
13
MAINTENANCE
Normally, the Modules don’t need repair. Follow the maintenance methods below
to ensure the best performance of the Modules:
In most conditions, the normal rainwater can keep the module glass clean.
Clean the glass surfaces with wet soft sponge or cloth if necessary. Use mild
non-abrasive cleaning agent to remove stubborn dirt. Do not try to clean a
Module with broken glass or perforated backsheet. It will cause
AUTHORITY FOR GAMKO USE serious electrical shock.
Take a regular inspection on grounding, mechanical and electrical connections
every 6 months. Make sure all the Module connectors are connected, clean and
without damage or corrosion. When disassembling the connectors, must make sure
all the components are working well; otherwise the connectors shall be
replaced. Damage on the connector will cause water leakage. The tightening
torque of the nut should be 1.5 N·m – 3 N·m. Use opaque material to completely
cover the modules during repair to avoid electric shock. When exposed to the
sunshine, the Modules will produce high voltage. The repair work must be
carried out by professionals.
Warning: Shut down the system before any electric repair. Improper maintenance
may cause electric shock or fire.
14
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>