resideo T4398A,B Precision Electric Heating Thermostat User Manual
- June 7, 2024
- resideo
Table of Contents
T4398A,B Precision
Electric Heating Thermostat
PRODUCT DATA
APPLICATION
The T4398 Electric Heating Thermostat provides precise, accurate line
voltage control of electric heating equipment. A snap action switch makes the
heating circuit on temperature fall. B models feature double-line break in the
Off position.
FEATURES
- Controls both fan-forced and baseboard electric heaters.
- Vapor-filled dual diaphragm sensing element provides high-temperature sensitivity with minimum droop.
- Canadian Standards Association (CSA) Performance Certified up to 20A.
- CSA Certified, UL Listed up to 5 kW at 277 Vac.
- Long-life, industrial-grade Micro SwitchTM mechanism.
- Rugged-engineered, plastic mounting base with captive mounting screw.
- Color-coded flyleads compatible with aluminum wire for quick installation.
- Replaces any standard wall-mounted electric heat thermostat.
- Contemporary white styling.
- Operating temperature range of 50°F to 80°F (10° C to 30° C).
- Celsius and Fahrenheit models available.
- Optional thermometer.
- Altitude compensation feature.
- Frost protection setting (A models only).
- Optional locking cover and range stops available.
SPECIFICATIONS
Models:
T4398A: Makes heating circuit on temperature fall. With setting knob at far
left (counterclockwise) position, provides calibration-free frost protection
setting of 40°F (4°C). See Fig. 2.
T4398B: Makes heating circuit on temperature fall. With setting knob at Off
position, provides double line break for fuse-protected 240V heating circuits.
(See Fig. 3.)
Both models feature optional thermometer, located in the cover, to indicate
the actual room temperature.
Accessories (Not Included):
272804A Range Stop and Cover Locking Assembly: Allows field-selection of
minimum and maximum temperature settings. Includes range stop assembly, cover
lockingscrews and wrench.
Setting Range:
Fahrenheit Models: Indicates range of 50°F to 80°F with marking indications in
5°F increments. Celsius Models: Indicates range of 10°C to 25°C with marking
indications in 1°C increments.
Differential:
Approximately 2°F (1°C) mechanical and thermal, non-adjustable.
Switch Type:
Enclosed industrial-grade Micro Switch~TM snap switch.
T4398A: Single-line break (single-pole, single-throw).
T4398B: Double-pole, single-throw with double-line break (double-pole, single-
throw) in Off position.
Wiring Connections:
Six-inch (150 mm) stranded copper leadwires suitable for connecting to
aluminum wiring if approved special service CO/ALR connectors are used.
Electrical Rating:
22A non-inductive at 120/208/240 Vac. 19A non-inductive at 277 Vac.
Canadian Standards Association Performance Rating:
20A at 120/208/240 Vac.
Approval Ratings:
Underwriters Laboratories Inc: Listed; file no. E47434, guide no. XAPX.
Canadian Standards Association: File no. LR1322.
Mounting:
Direct mounting on NEMA standard vertical 2 in. x 4 in. switch box, or 4 in. x
4 in. box using 6-32 slot RobertsonTM screws.
Sensing Element:
Vapor-filled, hermetically-sealed, stainless steel, dual diaphragm.
Thermometer (Optional):
Coil bimetal 50°F to 90°F (10°C to 30°C).
Barometric Sensitivity: 1°F/500 ft (0.3°C/kPa).
Dimensions:
See Fig. 1.
INSTALLATION
WARNING
120-277 Volt Line Voltage Hazard. Can cause serious injury or death. Do not
install thermostat unless you are a trained, experienced electrical service
technician.
CAUTION
Electrical Shock Hazard.
Can cause personal injury and equipment damage.
Disconnect power supply before connecting wiring. Use a limit control when
wiring the thermostat.
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube,
do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding
recycling and the proper disposal of an old control.
When Installing This Product . . .
- Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
- Check the rating given in the instructions and on the product to make sure the product is suitable for your application.
- Installer must be a trained, experienced service technician.
- After installation is complete, check out product operation as provided in these instructions.
- Follow local codes for installation and application.
Selecting Location
— Mount the thermostat on an approved electrical junction box.
— Locate the thermostat 4 to 5 ft (1.5m) above the floor on an inside wall
where the thermostat can be exposed to average room temperature.
— Locate the thermostat away from concealed warm or cold water pipes, light
switches and dimmers, and refrigerators.
— Locate the thermostat away from drafts of hallways, fireplaces, stairways,
and fans.
Mounting
When replacing an old line voltage thermostat:
— Carefully remove the old thermostat to avoid damaging the wiring insulation.
— Check the old insulation for cracks, chips, or fraying and apply approved
electrical tape, where necessary, to ensure adequate insulation.
NOTE:
Make line voltage wiring connections directly to the leadwires installed on
the thermostat, using wire connectors approved for the number and size of
conductors.
IMPORTANT
When using aluminum conductors, all wiring connections to the thermostat must
be made to the factory-installed lead wire, using approved CO/ALR solderless
connectors.
-
Connect all wires with the thermostat cover in place. Be sure that all wire connectors are tight. Install any security features. See Fig. 2 and 3.
-
Pre-bend the solid conductors and push them into the electrical box.
-
Remove the thermostat cover by grasping both the top and bottom of the cover and pulling out.
IMPORTANT
Carefully handle the thermostat. Excessive pressure can damage the control knob or sensing element. -
Turn the dial so the setpoint indicator is at the 12 o’clock position. (This prevents accidental damage to the dial- stop during mounting.)
-
Using the screwdriver, secure the thermostat to the electrical box by tightening the two mounting screws. See Fig. 4.
-
Level the thermostat only for appearance.
-
Tighten the screws and replace the cover.
Fig. 2. T4398A typical hookup.
- POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
- USE SPECIAL SERVICE CO/ALR SOLDERLESS CONNECTORS WHEN CONNECTING ALUMINUM CONDUCTORS OR A FIRE HAZARD MAY RESULT.
- USE A SEPARATE LIMIT CONTROL IN THE HEATING APPLIANCE.
- BREAKS AND REMAKES BELOW -31 F (-35 C); NORMALLY THERMAL ACTIVATED. BREAKS ON TEMPERATURE RISE; MAKES ON TEMPERATURE FALL.
Fig. 3. T4398B typical hookup.
- POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
- USE SPECIAL SERVICE CO/ALR SOLDERLESS CONNECTORS WHEN CONNECTING ALUMINUM CONDUCTORS OR A FIRE HAZARD MAY RESULT.
- BREAKS AT POSITIVE OFF AND REMAKES UNDER 31 F (35 C); NORMALLY THERMALLY ACTIVATED. BREAKS ON TEMPERATURE RISE; MAKES ON TEMPERATURE FALL.
- USE A SEPARATE LIMIT CONTROL IN THE HEATING APPLIANCE.
- BREAKS AT POSITIVE OFF ONLY; NOT THERMALLY ACTIVATED.
- DO NOT CONNECT GROUNDED CONDUCTOR (NEUTRAL) ON 120 OR 227V CIRCUITS. INSULATE AND TAPE OR CUT OFF RED WIRES IF UNUSED.
Fig. 4. Mounting thermostat to outlet box.
OPERATION AND CHECKOUT
After the thermostat is installed and wired, check out normal operation as follows:
- Turn setting dial fully clockwise until the switch clicks and the electric heater starts to heat.
- Turn the dial fully counterclockwise; the power circuit breaks and the electric heater starts to cool.
- The T4398 is a more accurate thermostat, allowing users to be more comfortable at lower setpoint settings (saving energy and lowering heating costs). To determine final setting: a. Begin with setting the dial indicator at 68°F (20°C). b. After two operating hours, if not comfortable, adjust setpoint to raise or lower the temperature, adjusting temperature only a few degrees each time.
Calibration
IMPORTANT
Do not assume the thermostat is out of calibration until it is installed and
allowed to operate for several hours.
The T4398 is accurately calibrated at the factory under controlled conditions.
The snap switch turns on heat when the setpoint is raised to room temperature.
The vapor-filled diaphragm sensor is affected by barometric pressure and
altitude. Deviations up to 1°F (±1/2°C) are within normal operation. The
control point drops 2°F every 1000 ft (1°C/300m) above sea level. See Fig. 5
and 6.
Fig. 5. T4398 altitude correction in (ft).
Fig. 6. T4398 altitude correction in (m).
To calibrate (see Fig. 7):
-
Remove cover and place it in a location that allows it to sense the room temperature.
NOTE: Allow several minutes for the thermometer to stop being affected by the heat from your hand. -
Rotate the setpoint knob counterclockwise until you hear the switch click.
-
Hold the setpoint knob firmly and rotate the setpoint scale ring counterclockwise until 12 o’clock on the ring is aligned with the thermometer cover.
-
The heat from your hand will affect the diaphragm sensor so wait five minutes and verify the calibration.
Security Features
To install the locking cover (select models (Fig. 8):
- Remove cover by swinging up from the bottom.
- Insert the Tinnerman Speed Nut® (supplied) into the slot at the lower rear thermostat base.
- Drive Allen screw into Speed Nut until head is flush with lower edge of thermostat base.
- Reinstall cover and lock by backing out Allen screw until screw body protrudes through cover hole. 5. To unlock cover, drive Allen screw into thermostat base until screw body clears cover.
To install the range stops (select models) (Fig. 9):
- Set thermostat to desired setpoint and remove the cover.
- Install plastic dowels (supplied) into minimum and/or maximum range stop holes on the back of the cover.
- Reinstall the cover and check range stop operation.
Frost Protection (T4398A)
When the ambient temperature falls to 40°F (4°C), the vapor in the diaphragm
changes into liquid. The diaphragm collapse to a fraction its original
thickness, turning on the heat, regardless of setpoint. This feature
guarantees minimum, yet reliable, operation of heaters in spaces near
freezing.
NOTE: To prevent heat from turning on below 40°F (4°C), turn off the
circuit at the breaker panel, or install a T4398B.
Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502
69-1604–03 M.S. Rev. 05-21 | Printed in United States
© 2020 Resideo Technologies, Inc. All rights reserved.
This product is manufactured by Resideo Technologies, Inc. and its affiliates.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>