Small Linear Thermoelectric Actuator
PRODUCT DATA
Design
- Available in normally open or normally closed versions
- M30 x 1,5 connection (other connections available on request)
- Fits on specified RESIDEO and Heimeier thermostatic radiator valves and valve inserts for manifolds and compact radiators
- Power supply 24 V or 230 V
- Auxiliary switch models to drive pump or fan
Application
M100 small linear actuators are used with RESIDEO room temperature controllers and/or for time-controlled two-point regulation of heating and cooling systems equipped with fan coil units, radiators, floor heating systems, etc.
Features
- Small size allows limited space installation
- Reliable longtime operation
- No mounting tools required
- Noiseless operation
- Ready-to-wire connection cable
- Visual valve position indicator furnished with actuator
- Overload protection (4 kV) for 230 V versions
Specifications
Specifications| M100-AG; -AO; -BG; -BO:
approx. 3 min
M100-AGX; -AOX; -BGX; -BOX:
approx. 5.5 min
---|---
Closing time| see diagram on next page
Maximum stroke| 4 mm
Stem force| 90 N
Ambient temperature| max. 50 °C (122 °F)
Power supply| A..-Versions: 24 Vdc ± 20%; 50/60 Hz
B..-Versions: 230 Vac ± 20%; 50/60 Hz
Initial current| M100-AG; -AO: approx. 0.6
A M100-BG; -BO: approx. 0.3 A
M100-AGX; -AOX: approx. 0.2 A
M100-BGX; -BOX: approx. 0.05 A
Permanent current| M100-AG; -AO: 0.09 A
M100-BG; -BO: 0.013 A
M100-AGX; -AOX: 70 mA
M100-BGX; -BOX: 7 mA
Power| M100-AG; -AO; -BG; -BO: 3 W
Consumption| M100-AGX; -AOX; -BGX; -BOX: 2 W
Protection standard| IP43
Cable length| 1 m (3.3 ft), other cable lengths possible on request
Cable wires| 2 x 0.5 mm2
NOTE: Opening and closing times depend on ambient temperature. Current values at nominal voltage and resistance.
Dimensions
Fig. 1. Dimensions
NOTE: All dimensions in mm unless otherwise stated.
Function
When the operating current is applied, a thermostat containing an expanding medium is heated, which after a pause period causes stroke movement.
Opening and Closing Time
NOTE: Opening and closing times depend upon ambient temperature and model.
Ordering Information
OS no.| Description| Valve action (Valve opens when heated)|
Voltage| Cable| Power consumption
---|---|---|---|---|---
M100-AG| M100 small linear
thermoelectric actuator
| valve closed without current| 24 V| Lenght: 1 m Wires: 2 x 0.5 mm2| 3 W
M100-AO| valve open without current| 24 V
M100-BG| valve closed without current| 230 V
M100-BO| valve open without current| 230 V
M100-AGX| M100 small linear thermoelectric actuator — low initial power
consumption| valve closed without current| 24 V|
Lenght: 1 m Wires: 2 x 0.5 mm2
| 2 W
M100-AOX| valve open without current| 24 V
M100-BGX| valve closed without current| 230 V
M100-BOX| valve open without current| 230 V
Installation Positions
NOTE: Connection leads must not touch the piping (heat transfer).
Wiring Diagram
Accessories
ZA100M-D Adapter for Danfoss-Valve RAVL
ZA100M-GD Adapter for Danfoss-Valve RA
For more information
homecomfort.resideo.com/europe
Ademco 1 GmbH
Hardhofweg 40
74821 MOSBACH
GERMANY
Phone: +49 6261 810
Fax: +49 6261 81309
Manufactured for and on behalf of the Pittway Sàrl, La Pièce 4, 1180 Rolle, Switzerland by its Authorised Representative Ademco 1 GmbH EN0H-1512GE23 R0720 Subject to change © 2020 Pittway Sàrl. All rights reserved. This document contains proprietary information of Pittway Sàrl and its affiliated companies and is protected by copyright and other international laws. Reproduction or improper use without the specific written authorization of Pittway Sàrl is strictly forbidden. The Honeywell Home trademark is used under license from Honeywell International Inc.